a. Change the heat output in the Installer Settings.
Go to the
Main Menu
>
Installer Settings
> Select the
Edit
button next to the
Manual
load type > In the
Heat Output
box, change the value to the minimum firing rate, and
select
Save
> Create a demand for heat > Select the
Back
button to return to the
Main Menu
.
b. Check the low fire (Flame Current) µA.
To check the flame current, go to the
Main Menu
>
Diagnostics
>
SIM Menu
>
Status
>
Flame Current
.
c. Identify the μA.__________
Low Fire μA should be greater than the minimum values prescribed in the table below.
Flame Minimum Signal
Model
Minimum Raw
Value
Anticipated Raw
Value
µA
Min.
Anticipated
Value µA
SL 10-85 G3
400
548
1.6
>2.2
SL 14-115 G3
498
871
2.0
>3.5
SL 20-160 G3
600
946
2.4
>3.8
SL 30-199 G3
498
871
2.0
>3.5