Combustion Test Target Ranges
Figure: Gas valve and fan
The Low Fire (zero-offset) valve adjustment cap on the gas valve has been factory set. Do not adjust this screw in the field
unless indicated in these instructions.
After converting the appliance to propane, a combustion (CO
2
) reading must be taken by a qualified technician using
properly functioning and calibrated combustion analyzing equipment and the results compared to the values in Table 1.
Propane
CO
2
Value (%) at High Fire with front
cover open
CO
2
Value (%) at Low Fire with front
cover open
Max. CO
2
value
11.5%
Value at High Fire
Minus -
0.3%
Min. CO
2
value
9.8%
9.5%
Table 1
- CO
2
values at High and Low Fire
2
|