background image

Installing a SIM+

Figure 1 SIM connections - SL 10-85 G3, SL 14-115 G3, SL

20-160 G3, SL 30-199 G3 series boilers

1. Disconnect the power to the boiler and close the

gas shut-off valve.

All the module’s connector plugs, except the

ignition lead, have retaining clips.

2. Note the position of the retaining clips for each

plug. The retaining clips must be depressed and

properly released before the connectors can be

unplugged.

3. Unplug all the connectors from the module.

4. Check that the wire connections are still solid and

secure.

5. To remove the existing module, hold it in place as

you unscrew the two mounting screws. Retain the

screws.

6. Position the new module, so that the mounting

holes align.

7. Insert the screws and lightly tighten to secure the

module in place.

8. Plug the connectors into their respective sockets

(see image above), ensuring that the retaining

2 │

www.ibcboiler.com

clips click into place properly. Each wire

connector plug should fit snugly into a socket.

9. (Optional) To replace the ignitor:

a. Unscrew the two Phillip head screws

holding the ignitor in place.

b. Position the new ignitor and gasket in

place, and attach using the two ignitor

screws supplied with the kit.

10. Leaving the gas off, restore power to the boiler.

If the ignitor was replaced, you should

pressurize the combustion chamber to check

for leaks around the ignitor gasket. The way to

pressurize the combustion chamber is to put

the fan into vent test mode that will drive the

fan into high speed.

11. To perform the leak test:

a. Apply an approved leak solution around

the ignitor gasket.

b. Remove any call for heat.

c. From the touchscreen controller's

Main

Menu

go to

Diagnostics

>

Fan

Operation

>Press the

Vent Test On/Off

button to drive the fan into high speed.

d. When finished, press the

On/Off

again,

and wipe off the excess solution.

12. Leaving the gas off, initiate a call for heat.

13. Look through the sight glass to check that a

spark is present during the ignition trial.

14. If the spark looks bright and stable, turn on the

gas and allow the boiler to go through another

trial for ignition. It should light off smoothly and

quietly.

Replacing the ignitor

1. Disconnect the power to the boiler and close

the gas shut-off valve.

Отзывы: