8.2.2 Hi Limit cut-off temperature error
Hi Limit cutoff temperature Error
Issue
Diagnosis
Fix
Error – Water High-Limit
Exceeded
Water temperature exceeds
hi-limit. Boiler is in hard
lockout mode.
See
hi-limit temperature lockout on
page 88
8.2.3 Low Water Cut-off error
Low Water Cutoff Error
Issue
Diagnosis
Fix
Error - Low Water Cutoff
The Safety and Ignition
module has detected a low
water condition.
See
8.2.4 Aux. Interlock 1 or 2
Aux. Interlock 1 or 2
Issue
Diagnosis
Fix
Interlock 1 or 2 terminals are
open.
Jumper lead is loose or
compromised.
Replace the jumper lead.
External safety is in an alarm
state.
Inspect the external safety
devices.
90
Section: Troubleshooting