6.3.5 Testing the Hi-Limit cutoff temperature function
The hi-limit temperature function monitors the maximum supply temperature set in the safety ignition
module (SIM). If the water temperature exceeds the hi-limit temperature, the boiler goes into a lockout
condition, requiring a manual reset. Perform the test to ensure that the water temperature sensor is
functioning.
To test the Hi-limit temperature function:
1. Go to
>
SIM Menu
>
Hi-Limit Test
> Read the instructions.
You will need to enter a cutoff temperature below the actual supply temperature value currently
displayed. For example, if the Supply Temp. value is 180°F, enter 170°F in the Cut Off Temp.
box.
2. In the
Cut-Off Temp.
field, enter a number value >
OK
.
The message: "Hi-Limit Detected" is displayed.
3. To reset the boiler, select the
Reset
button. The cutoff value reverts to normal upon reset.
The message: "The SIM module has been reset" is displayed.
4. Tap
Close
>
Back
to exit the test.