6.8.3 Hydronic heat pump circulator
The hydronic heat pump circulator must be field-installed and wired. Use a pump control module,
or bring low-voltage wires to the outside unit J6 terminals "CIRC PUMP" to switch a 24V relay
circuit indoors, as shown here:
Jumper at J1 (interlock) (Outdoor wiring)
J6 terminal, switch for "CIRC PUMP" (Outdoor wiring)
Indoor wiring
24V transformer
HPX hydronic heat pump circulator (field-supplied)
24V relay
Figure 16
HPX Series
circulator relay field wiring
IBC recommends the application of the either the IBC Sky 35 module for load circulator control
or, alternatively, using a pressure-activated load circulator for which control is unnecessary.
See also
Control wiring overview on page 40
. The
HPX Series
does not control load circulators.