Caution

Failure to position the O-ring as indicated will result in a gas leak, and affect burner operation.

 8.  Re-assemble in the reverse order of steps provided.

 9.  Check for gas leaks.

Combustion testing and adjustment

Danger

A combustion test checks that the gas valve is operating properly in the field. To perform a combustion test, you 

must be a qualified, trained and licensed gas fitter.

Making adjustments to the IBC gas valve without a properly calibrated gas combustion analyzer and by people 

who are not trained and experienced in its use is forbidden. Failure to use an analyzer can result in an 

immediate hazard.

Model Number

High Fire Input

EX 700

700 MBH

Table 1 

Rated input of a converted boiler

Normal ignition system sequence of operation:

The boiler control, upon a call for heat or DHW, turns on the combustion fan for a 20-second pre-purge, then energizes the 

spark electrode and gas valve for a 4-second trial for ignition.

If the burner does not light, the process is repeated until the burner lights and flame is detected. After 3 trials for ignition, the 

boiler locks out and will need to be manually reset by clearing the error on the touchscreen controller (Diagnostics > 

Advanced Diagnostics > Clear Errors). The boiler  automatically resets after 60 minutes, if no action is taken.

Combustion test target ranges

The Low Fire (zero-offset) valve adjustment screw on the gas valve has been factory set. See 

 in 

Figure 1 

.

The High Fire (gas-air) ratio adjustment screw on the gas valve has also been factory set. See 

 in 

Figure 1 

. It will have 

to be adjusted to attain optimum combustion results whenever fuel conversion is undertaken; however, no mixture 

adjustment shall be performed unless done by a qualified technician using properly functioning and calibrated combustion 

analyzing equipment.

4

|

Содержание EX 700

Страница 1: ...noxide may result causing property damage personal injury or loss of life The qualified service agency is responsible for the proper installation of this kit The installation is not proper and complet...

Страница 2: ...Gas valve and fan Fan Mixing device Gas high pressure switch Inlet gas pressure test port location of Gas low pressure switch Low fire adjustment zero offset High fire adjustment on the side Shutoff...

Страница 3: ...he boiler 3 Remove the four 4 5 16 hex bolts from the gas inlet to the mixing device Carefully separate the two parts remove and retain the O ring for re assembly See in image below 4 Remove the four...

Страница 4: ...turns on the combustion fan for a 20 second pre purge then energizes the spark electrode and gas valve for a 4 second trial for ignition If the burner does not light the process is repeated until the...

Страница 5: ...o 1 full turn to increase the fuel enrichen the mixture before firing up the boiler 6 Before you change the load to manual control note the load setting 7 Set the load to manual control and set the he...

Страница 6: ...correct settings Note Clock the gas meter to confirm full maximum rating plate input Check the measured results with Table 1 5 Run the boiler to low fire and check the results to confirm correct setti...

Страница 7: ...other appliances and pilots 2 Turn on the boiler and set the boiler to high fire 3 Ensure the boiler has a large load to heat so that the boiler will not shut off 4 With a Stop Watch record the number...

Страница 8: ...Where to place conversion labels on the boiler 8...