6.5 Installation clearances
Warning
Exposed water piping and associated components (relief valves, circulators, etc.,
should not be in contact with combustible materials. Check local codes for required
clearances and / or provide adequate insulation.
EBX-Series
Surface
Minimum distance from combustible
surfaces
Recommended clearance
for installation and
service
Front
2"
24"
Left side
2"
4" (allow access to water
connections)
Right side
2"
4" (allow access to water
connections)
Top
2"
8" (to allow access to
elements)
Bottom
2"
6" (for drain and power
supply access)
Table 3
Clearance distances for boiler mounting sites
6.6 Closet installations
For installations in a confined space (such as a closet), ventilation openings may be needed
through a door or wall to prevent excessive heat from building up inside the space.
The appliance must not be exposed to surrounding air above 122°F (50°C) or below 32°F (0°C).
6.7 Water Piping
IBC recommends using unions on the inlet and outlet water connections. Unions simplify many
service procedures, notably the cleaning of the inlet water strainer. See
below for other piping recommendations.
22
Section: Installation
Содержание EBX Series
Страница 10: ...Intentionally left empty 10 Section Specifications ...
Страница 11: ...11 Connection specifications ...
Страница 12: ...Intentionally left empty ...
Страница 14: ...4 3 Internal view 14 Section Introduction ...
Страница 16: ...Intentionally left empty ...
Страница 18: ...Intentionally left empty ...
Страница 48: ...Intentionally left empty ...
Страница 50: ...Intentionally left empty ...
Страница 60: ...Intentionally left empty ...
Страница 61: ...61 Appendices Wiring diagrams Figure 29 EBX series Boilerinternal wiring diagram ...
Страница 62: ...Intentionally left empty ...
Страница 63: ...63 ...