BoilerNet Interface Controller II
5
V1.00.6
(1) If a dynamic IP address is to be obtained from a DHCP server, then "ipaddr", "ipmask", "ipgate", "ipdns1", and "ipdns2"
should all be set to "0.0.0.0" (a dynamic IP address is generally not recommended).
(2) "ipdns2" is optional. Set to "0.0.0.0" if not used.
(3) If a ntp server is specified, then the BACnet Time Synchronization will not be used. To use the BACnet Time
Synchronization, the ntp server parameter should be set to "0.0.0.0". Note that the BIC will only use the first BACnet time
synchronization message it receives after it starts-up. Subsequent time-sync messages will be ignored.
(4) This feature is not implemented in V1.0 of the BoilerNet Interface Controller.
(5) Enable one or both of these options.
(6) The SMTP server information in the "alerts.dat" file must be configured before enabling this option.
Important:
For the BIC II to use the new settings, you must set the "reconfig" flag to "1" before saving
the file. On start-up, the BIC II reads the "site.dat" file and checks the state of this flag. If
set, it copies these settings to its internal configuration registers, resets the flag, and then
starts the system using the new settings. Be sure to record the configuration settings, or
make a backup of the "site.dat" file if you alter it.
It will take approximately 3 to 4 minutes for the BIC II to restart when the settings have been altered.