SAS0715
Page
14
BRINE VALVE ASSEMBLY
Windsor Cabinet
Model
Float Distance (X)
SAS0715
100mm
SAS0922
200mm
SAS1029
260mm
Adjustment of Softener Brine Valve
1.
Lift float rod to full up position.
2.
Set float to distance shown. Measure from
the top of the crown nut to the bottom of
the float.