Introduction

Thank you for purchasing a water conditioner system
featuring the Series 255 with a model 940 Control.

The Model 940 Control provides dependable time
clock based operation. The Series 255 valve
combines simplicity with reinforced NORYL *
construction to provide an uncommonly reliable
appliance. The inherent quality of the system means
a long life of efficient, trouble-free soft water. If
maintenance becomes necessary, the Series 255/940
Control offers a unique separation capability
illustrated in the Service section of this manual.

Superior design

 

Single synchronous electric motor 

provides all

the power for the clock and the operation of the
control.

 

Electrical wiring is factory assembled. 

System

cannot be connected incor

rectly.

 

Program clock 940 (timer) and 960 Demand
system are interchangeable. 

Both units provide

guest regeneration capability.

 

System may be indexed manually with or
without power 

to any one of its service or

regeneration positions. Legend on timer faceplate
indicates control valve position.

 

No moving parts in water stream 

means no

close tolerance parts subject to fouling. Thus, the
system is especially effective on iron-bearing
water.

 

No dynamic seals 

that could cause leakage

through wear or fatigue.

 

Control accepts NORYL* or brass manifold or
modular bypass valve without modification,

offering complete versatility and easy plumbing
for any installation.

 

Brining control valve built into system

eliminates need for any brine valve.

 

Drain flow control 

is built into the valve to

control backwash and fast rinse flow rates.

 

NORYL is a trademark of GE Plastics.

Superior Operation

 

Direct acting system 

functions independently of

water pressure. No pistons or diaphragms that
require a minimum water pressure to operate.

 

Five-cycle operation 

provides for down flow

service, up flow backwash, down flow brining,
down flow slow and fast rinse. A sixth position is
included for timed refill of the brine tank.

 

Valve discs are held closed by water pressure

and therefore, are leak tight. The sealing forces
are increased as the water pressure is increased.
Valve seats are in a vertical position, which is
design position least vulnerable to plugging.

 

System operation cannot get out of phase 

or

sequence. The control always returns to a fixed
service position of regeneration regardless of
where in the regeneration cycle it was started.

 

Bypass (unconditioned) water is automatically
available 

during regeneration.

Installation

All plumbing and electrical connections must conform
to local codes. Inspect the unit carefully for carrier
shortage or shipping damage.

Location Selection

 

Locate unit as close to a drain as possible

 

If supplementary water treating equipment is
required, make sure that adequate additional
space is available. Locate the brine tank in an
accessible place so that salt can easily be added.

 

Do not install any unit closer than 10ft (3m) of
piping between the outlet of the water conditioner
and the inlet of the water heater. Water heaters
can transmit heat back down the cold water pipe
into the control valve. Hot water can severely
damage the controller.

A 10ft (3m) total pipe run (including bends, elbows
etc) is a reasonable distance to prevent hot water
damage. A positive way to prevent hot water from
flowing from a heat source to the conditioner is to
install a check valve in the soft water piping from the
conditioner. If a check valve is installed, make sure
that the water-heating unit is equipped with a properly
rated temperature and pressure safety relief valve.
Always conform to local codes.

 

Do not locate the unit in an area where the temp
ever falls below 34ºF (1ºC) or over 120ºF (49ºC).

 

Do not install the unit near acid or acid fumes.

 

Do not expose the unit to petroleum products.

Содержание AST1052T-940

Страница 1: ...TION OPERATING INSTRUCTIONS Model AST1052T 940 Serial No Telephone 07 3219 2233 Facsimile 07 3219 2266 Email sales ibcwater com au Website www ibcwater com au FILTRATION WATER TREATMENT PRODUCTS for commercial industrial and residential application Manufacturer and Supplier of ...

Страница 2: ...roximately 20ppm based on a sample volume of 10mls Other hardness test kits are available for more accurate testing eg Hardness Tablets Directions Take a 50ml sample of water in a screw capped bottle Add one 1 tablet to sample shake or crush to disintegrate Repeat until last trace of reddish tinge disappears The final colour is usually blue but with some water a greyish coloured end point is obtai...

Страница 3: ...ge in litres call ð D For household situations allow 250 litres per person per day CALCULATION N 1000 x C D x H Select nearest lower whole number If necessary consult your dealer or IBC Water Treatment for advice on setting up the softener EXAMPLE Household use for 5 people on 220 mg l hard water using Model AST1041 at 1350 grams capacity N 1000 x 3000 1250 x 220 10 9 days 10 days Note Maximum num...

Страница 4: ... Per Kg metres AST1052T 940 1820 3 3640 12 37 52 25 12 52 70 0 70 0 60 1 58 CABINET BRINE CHAMBER POLY MOULDED Operating Pressure 300 690 kPa Temperature 5o x 50o C Electrical 240V 50Hz 3 watts maximum WARNING A pressure reduction valve should be installed in areas of high water pressure above 690kPa A water hammer arrestor should be installed if water hammer prevails Caution Do not use where wate...

Страница 5: ...f the top The resin must not be allowed to be spilled on the floor as it is very slippery and dangerous to walk on STEP 5 Clean top of neck and threads of all traces of resin Remove the plastic cap fitted in Step 3 taking care not to raise the distributor pipe NEVER shorten the length of the distributor pipe STEP 6 Unpack control valve check that tank O ring is in place Clip in top strainer if not...

Страница 6: ... TOP STRAINER SUPPLIED LOOSE IT IS IMPORTANT THAT THIS STRAINER IS ASSEMBLED TO THE VALVE DURING INSTALLATION THE LENGTH OF THE INTERNAL RISER PIPE IS FACTORY ADJUSTED FOR THE TANK SIZE PROVIDED DO NOT SHORTEN THIS PIPE UNDER ANY CIRCUMSTANCES ASSEMBLE TOP STRAINER TO VALVE BODY PUSH AND TWIST INTERNAL RISER PIPE ...

Страница 7: ... the timer at the left hand side The Transformer is only suitable for indoor mounting When ordering spare parts Advise that the Timer is the low voltage model Salt Dial Indicator Knob Clock Dial Calendar Cap Day Pins Do not rotate by hand Low Voltage Transformer Only use the included transformer for powering the Timer Connect the plug of the transformer cable to the mating socket at the rear of th...

Страница 8: ...AST1052T 940 Page 8 Water Conditioning Control System Installation Operating and Maintenance Manual Series 255 Valve 940 Control ...

Страница 9: ...lacing Conditioner into Operation 13 Adjustment of Timer 14 Special Features of Timer Adjustment of Brine Control 14 How to Set the Salt Dial Service 15 Removing the Timer Assembly Removing the Valve Assembly Preventative Maintenance 17 Injector Screen and Injector Specifications 18 Pressure Graphs 19 Control Valving identification 20 Valve Disc Operation 20 Flow Diagrams 21 Replacement Parts 22 T...

Страница 10: ...ive cycle operation provides for down flow service up flow backwash down flow brining down flow slow and fast rinse A sixth position is included for timed refill of the brine tank Valve discs are held closed by water pressure and therefore are leak tight The sealing forces are increased as the water pressure is increased Valve seats are in a vertical position which is design position least vulnera...

Страница 11: ...ntrol Bypass Valve optional Air Check Brine Tube Fitting Connection 1 4 Figure 2 Tank Adaptor Tank Tread 2 1 2 8 male NPSM Drain Connection 3 8 or 1 2 NPT or BSPT Outlet Connection 3 4 or 1 NPT or Inlet Connection 3 4 or 1 NPT or BSPT ...

Страница 12: ...ater pressure at the conditioner is not less than 40psi 280kPa You may elevate an additional 2ft 61cm for each additional 10psi 70kPa of water pressure When the drain line is elevated and empties into a drain which is below the level of the control valve form a 7 inch 17cm loop at the drain end of the line so that the bottom of the loop is level with the drain line connection This provides an adeq...

Страница 13: ...alve s into the not in bypass position Open the water supply valve very slowly to approximately the 1 4 open position Caution If the water supply valve is opened too rapidly or too far resin may be lost In the BACKWASH position you should hear air escaping slowly from the drain line 3 When all the air is purged from the tank water begins to flow steadily from the drain slowly open the main supply ...

Страница 14: ... indicator knob counterclockwise to START Figure 8 It will take a few minutes for regen eration to begin The normal regeneration schedule will not be disrupted Manual Regeneration Electricity is used only to run the timer and to rotate the camshaft All other functions are operated by water pressure Therefore in the event of a power outage all the various regeneration positions may be dialled manua...

Страница 15: ...e the timer assembly for servicing 1 Unplug the power cord 2 Remove the rear cover by pushing back on the tab provided on the cover with your thumb Figure 10 Next lift the cover off the valve 3 To remove the camshaft or reinstall it the rib on the shaft must be pointing straight up This occurs when the indicator knob is rotated to the refill position Press down on the back of the camshaft to disen...

Страница 16: ...he camshaft Slide the camshaft into the timer It may be necessary to rock the timer slightly to key the camshaft into the timer When the camshaft is slid into place lift he back of the camshaft up while rotating the indicator knob to seat the camshaft in the top plate hoop Removing the Valve Assembly Complete the following steps to remove the valve assembly 1 Unplug the power cord 2 Shut off the w...

Страница 17: ...steps to clean the injector screen and injector 1 Unplug the power cord 2 Shut off the water supply or put the bypass valve s into the bypass position and remove the rear cover Figure 10 3 Relieve system pressure by opening the rinse drain valve the fifth valve back from the control with a screwdriver Figure 11 4 Using a blade screwdriver unscrew and remove the injector screen and injector cap 5 C...

Страница 18: ... Pressure 300 psi 2069kPa Working Pressure 20 to 127 psi 138 to 876 kPa 100 psi max in Canada Voltage 24V 50 Hz 24V 60 Hz 100V 50 Hz 100V 60 Hz 230V 50 Hz 115V 60 Hz Current 50 mA Operating Temperature 34 F 1 C to 120 F 49 C Humidity 10 to 100 condensing allowed Pressure Tank Thread 2 1 2 in 8 NPSM Brine Line Thread 1 4 in NPT male Distributor Tube Diameter Required 13 16 in O D 20 6 mm ...

Страница 19: ...e 1 2 in NPT male drain Valve Module Tank Adaptor Optional Bypass Valve Reinforced NORYL Inlet Outlet Manifold Brass or reinforced NORYL Rubber Parts Compounded for cold water service Injector size A White Nozzle 0 042 in 1 1 mm diameter Throat 0 089 in 2 3 mm diameter Injector size B Blue Nozzle 0 052 in 1 3 mm diameter Throat 0 099 in 2 5 mm diameter Injector size C Red Nozzle 0 059 in 1 51 mm d...

Страница 20: ...AST1052T 940 Page 20 Control Valving Identification Valve Disc Operation ...

Страница 21: ...AST1052T 940 Page 21 Flow Diagrams ...

Страница 22: ...AST1052T 940 Page 22 ...

Страница 23: ...le 1000904 Adj Backwash Extra Salt Long Rinse Long Cycle 1000905 3 Cycle Adj Backwash 11 Motor Option 1 1000802 24V 50 Hz 1000803 24V 60 Hz 1000804 110V 50 Hz 1000805 100V 60 Hz 1000806 230V 50 Hz 1000807 115V 60 Hz Code Part No Description Qty 12 1000841 Clutch Gear 1 13 1007483 Wire Nut 1 14 1000833 Gear 1 15 1000832 Gear 1 16 1000858 Geneva Clock 1 17 1000844 Geneva Drive Gear 1 18 Power Cord 1...

Страница 24: ...AST1052T 940 Page 24 ...

Страница 25: ...AST1052T 940 Page 25 Valve Body and Tank Adaptor Module ...

Страница 26: ...5 No 14 for 14 in Diameter Tank 7 1030502 Ball Flow Control 1 8 Injector Assy With O rings 1 1032970 A Injector White 1032971 B Injector Blue 1032972 C Injector Red 9 Injector Cap With O rings 1 1000217 A Cap 1000218 B Cap 1000219 C Cap Code Part No Description Qty 10 1033784 Tank Adaptor Assy 1 11 1032416 Air Check Ass 1 12 1010429 O ring 3 1 8x3 1 2x3 16 BN 1 13 1010428 O ring 3 4x1x1 8 EP 1 14 ...

Страница 27: ...stic Pipe Adaptor Kit 1 1001605 1 in BSPT Plastic Pipe Adaptor Kit 1 1001611 3 4 in BSPT Brass Pipe Adaptor Kit 1 1001610 1 in NPT Brass Pipe Adaptor Kit 1 1001612 1 in BSPT Brass Pipe Adaptor Kit 1 Code Part No Description Qty Piping Boss 4 Kit Piping Boss Includes Hardware 1040277 3 4 in NPT Brass 3 8 in NPT Drain 1040278 1 in NPT Brass 1 2 in NPT Drain 1040281 3 4 in BSPT Brass 3 8 in BSPT Drai...

Страница 28: ... b Restricted drain line c Injector plugged d Defective injector e Valve disc 2 and or 3 not closed f Air check prematurely closed a Water pressure must be 20 psi minimum b Remove restriction c Clean injector and screen d Replace injector cap e Flush out foreign matter holding disc s open by manually operating valve stem s Replace if needed f Put control momentarily into brine refill replace or re...

Страница 29: ...AST1052T 940 Page 29 ...

Страница 30: ...an be used directly without dissolving before application The recommended dosage for Calcium Hypochlorite is two grains approx 0 1 ounce per cubic foot Complete the following steps to disinfect the conditioner Add the Calcium Hypochlorite to the brine well of the brine tank Make sure that he brine tank has water in it so the solution is carried into the conditioner Proceed with normal regeneration...