1-31
INSTALLATION
SL 20-115 MODULATING GAS BOILER
1.8.6 Thermostat Heat Anticipator
iBC “therm.” contacts draw no power, so an anticipator setting for the thermostat
is not applicable with the sl modulating series boilers. in the case of a single
temperature / heat load where zone valves are used to manage individual
thermostatically controlled zones, each room thermostat’s heat anticipator should
be adjusted to the current draw of its associated zone valve.
Figure 36: Electrical Wiring Connections (full page ladder diagram at back of this manual)
A 2.5 mm Slot screwdriver is
required for the bottom terminal
strip. Broader or narrower blades
may damage the terminal screws.