Important! 
 
The reverse current rating of the modules depends on the type and is 20 A for IBC 
PolySol TX modules. If the reverse current can exceed the maximum fuse rating 
specified on the module rear, a properly approved and certified over current blocking 
device (fuse or circuit breaker) must be installed in series with each module or each 
module string. The fuse rating of the IBC PolySol TX module types is 15 A. 
 
 
Grounding 
System Bonding 

 

The module frames do not require grounding according to the regulations of IBC SOLAR 
AG. Regional or national regulations, however, may require that the module frames be 
grounded. In addition, the module frames may require grounding for lighting/overvoltage 
protection. 

 
Functional Grounding 

 

In case modules are installed within 500 m of the coastline, a functional grounding of the 
photovoltaic generator has to be installed. 

 

DANGER! Incorrect grounding causes risk of fire hazard! 
The direct grounding of the positive or negative conductor is only permitted if any hazards 
for persons can be excluded. Comply to all valid regulations for personal safety and fire 
prevention. 

 

For the installation of a functional grounding: 

 

Only use galvanic isolated inverters (inverters with transformers). 

 

Only ground the negative conductor of the PV-generator. 

 

Only unse grounding kits which are compliant with the inverter. 

 

Meet all earthing instructions of the inverter manufacturer. 

 
 

Mechanical installation 

 

The modules should be mounted so that they are exposed as directly to sunlight as 
possible and to as little shading as possible. 

 

Even partial shading can significantly reduce the output power of the modules and system. 

 

The modules must be securely fastened. To do this, use special mounting frames or 
mounting kits designed for photovoltaic applications. 

 

The tilt angle of the PV modules measured between the PV modules and the horizontal 
must be 5° at minimum. Ensure that the drainage ope nings of the frame are left open 
following installation to allow water runoff. This prevents frost damage. 

 

Make sure to avoid an insufficient inclination angle (i.e. <15°), since otherwise, dirt can 
accumulate on the glass surface and be retained by the frame. 

 

Dirt accumulations on the module surface can cause shading on active solar cells, thus 
reducing the electrical output. 

 

For roof-mounted systems, make sure that there is sufficient room for ventilation below the 
module in order to cool the rear (at least 100 mm). 

 

Always make sure that the module rear does not come into contact with foreign objects or 
building elements, especially if the module is subjected to a mechanical load. 

 

The modules may be installed in landscape or portrait format. Install the module in such a 
way that the junction box is positioned in the upper area of the module. 

 

IBC SOLAR AG allows several mounting methods. You can obtain detailed information on 
the permissible mounting methods along with the permissible clamping areas in the drawing 
found in the appendix. 

Содержание PolySol TX Series

Страница 1: ...aling as little as 5 of full sunlight The current and power output increase with the light intensity The output power generated by the modules may exceed the specified rated power The rated values are...

Страница 2: ...tective equipment Safety precautions during installation Make sure that no children or other persons are near the systems or modules during installation Do not perform installation work under severe w...

Страница 3: ...n connectors The PV module s plug connection can also be protected using the pluggable PV SSH4 safety lock clip available from Multi Contact The PV SSH4 clip is not supplied by IBC SOLAR AG and must b...

Страница 4: ...he inverter manufacturer Mechanical installation The modules should be mounted so that they are exposed as directly to sunlight as possible and to as little shading as possible Even partial shading ca...

Страница 5: ...r to take into account the thermal linear expansion of the module frame the distance between 2 modules should be 20 mm However it has to be at least 10 mm For mounting with clamps the surface pressure...

Страница 6: ...Commission a specialist company for this purpose IBC SOLAR AG is a member of the European PV Cycle Association and accepts our product responsibility You can give back modules of IBC SOLAR AG and all...

Страница 7: ...Appendix 1 Clamping range long side...

Страница 8: ...Appendix 2 Clamping range short side Attention For using clamps at the short side the max load must not exceed 2400 Pa...

Отзывы: