CONNECTION DIAGRAM

CONNECTIONS

Switch off power before starting work on the equipment.
Recommended tightening torque on terminals 0.5 Nm; max tightening torque 0.8 Nm.

Input voltage
(L-N-PE)

1x230-240 V +/-15%, 50/60 Hz.
NOTE! Protective earth must always be connected.

Motor
(U-V-W)

Three-phase induction motor wired for 3x230 V (Delta).
Max 370 W.
Direction of rotation is changed by switching two of the phases.

Continued on next page

+

Rotation

monitor

A1 A2 A3

1 2

6

10

12

w   

S

   br

Manual

high / low speed

Input

signal

Run

3 5

9

11

Reset

1 2 3

Pot. 10 k

Potentiometer input

+

Rotations-

vakt

A1 A2 A3

1 2

6

10

12

w   

S

   br

Manuell

hög / låg hastighet

Insignal

Drift

3 5

9

11

Åter-

ställning

1 2 3

Pot. 10 k

Potentiometer ingång

L N

V W

1 x 230 V

U

(Max 2 A / 250 V AC)

3 x 230 V

Max 370 W

13 14 15

T T

Alarm relay

 

Thermal

contact

1

M

2

3

4

5

3 ~

L N

V W

1 x 230 V

U

(Max 2 A / 250 V AC)

3 x 230 V

Max 370 W

13 14 15

T T

Larmrelä

 

Termo-

kontakt

1

M

2

3

4

5

3 ~

+

Rotation

monitor

A1 A2 A3

1 2

6

10

12

w   

S

   br

Manual

high / low speed

Input

signal

Run

3 5

9

11

Reset

1 2 3

Pot. 10 k

Potentiometer input

+

Rotations-

vakt

A1 A2 A3

1 2

6

10

12

w   

S

   br

Manuell

hög / låg hastighet

Insignal

Drift

3 5

9

11

Åter-

ställning

1 2 3

Pot. 10 k

Potentiometer ingång

L N

V W

1 x 230 V

U

(Max 2 A / 250 V AC)

3 x 230 V

Max 370 W

13 14 15

T T

Alarm relay

 

Thermal

contact

1

M

2

3

4

5

3 ~

L N

V W

1 x 230 V

U

(Max 2 A / 250 V AC)

3 x 230 V

Max 370 W

13 14 15

T T

Larmrelä

 

Termo-

kontakt

1

M

2

3

4

5

3 ~

+

Rotation

monitor

A1 A2 A3

1 2

6

10

12

w   

S

   br

Manual

high / low speed

Input

signal

Run

3 5

9

11

Reset

1 2 3

Pot. 10 k

Potentiometer input

+

Rotations-

vakt

A1 A2 A3

1 2

6

10

12

w   

S

   br

Manuell

hög / låg hastighet

Insignal

Drift

3 5

9

11

Åter-

ställning

1 2 3

Pot. 10 k

Potentiometer ingång

L N

V W

1 x 230 V

U

(Max 2 A / 250 V AC)

3 x 230 V

Max 370 W

13 14 15

T T

Alarm relay

 

Thermal

contact

1

M

2

3

4

5

3 ~

L N

V W

1 x 230 V

U

(Max 2 A / 250 V AC)

3 x 230 V

Max 370 W

13 14 15

T T

Larmrelä

 

Termo-

kontakt

1

M

2

3

4

5

3 ~

Содержание MiniMax

Страница 1: ...IBCcontrol Made in Sweden MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGER MiniMax Article no F21037501 Set of EMC glands as an option...

Страница 2: ......

Страница 3: ...nical data 6 Functions 6 DIP switch 7 Operational indications 8 Alarms 8 9 Settings via potentiometer 10 Push button 10 Connection diagram 11 Connections 11 12 Checks before powering up the control un...

Страница 4: ...emented Disposal and recycling When replacing components or when the control unit in its entirety need replacing please follow the advice below The aim should always be maximum possible recycling of r...

Страница 5: ...in power before removing the cover Never touch electrical components or contacts while main current is switched on Risk of electric shock resulting in serious injury or death Residual voltage remains...

Страница 6: ...on of conformity with the requirements of the EMC Directive 2004 108 EC The control unit is approved according to the requirements of the EMC Directive 2004 108 EC and is tested according to standard...

Страница 7: ...ning begins and the rotor turns for 10 seconds at minimum rpm The rotation monitor a magnet fitted to the rotor with an associated magnetic sensor stops the converter and generates an alarm in the cas...

Страница 8: ...0 W Input current max 2 8 A Incoming fuse max 10 A Output voltage 3x0 230 V Min frequency 1 20 Hz Max frequency 40 100 Hz Motor output max 370 W Motor current max 1 9 A Exact value cannot be obtained...

Страница 9: ...0 0 1 0 4 20 mA 0 0 1 0 1 0 Cleaning 1 Cleaning function set to ON position When the wheel has stopped for 30 minutes the cleaning function is activated and the wheel rotates at minimum speed for 10...

Страница 10: ...received every 5 minutes Magnet facing the wrong way Magnetic sensor incorrectly connected see Connections on pages 11 12 Too wide a gap between the magnetic sensor and magnet max 15 mm Broken belt Be...

Страница 11: ...asure motor resistance it should be identical on all phases Short circuit between phases in the cable Earth fault in motor or cable Overcurrent MiniMax limits current at 4 A and trips then after 4 5 s...

Страница 12: ...tor temperature will increase Acc Acceleration time 0 30 s Factory set to max does not need adjustment Ret Retardation time 0 30 s Factory set to max does not need adjustment Threshold value The contr...

Страница 13: ...ax 2 A 250 V AC 3 x 230 V Max 370 W 13 14 15 T T Larmrel Termo kontakt 1 M 2 3 4 5 3 Rotation monitor A1 A2 A3 1 2 6 10 12 w S br Manual high low speed Input signal Run 3 5 9 11 Reset 1 2 3 Pot 10 k P...

Страница 14: ...t be jumped if external start not used Rotation monitor 9 10 White cable connected to terminal 9 brown to terminal 10 The magnet is installed with south side S towards the transmitter Max gap 15 mm Re...

Страница 15: ...ltage Make sure the cleaning DIP switch is set to ON and the input signal is disconnected When power is switched on the wheel will rotate at minimum rpm for 10 seconds Checking the rotation monitor Th...

Страница 16: ...GLAND Motor cable Incoming EKK 3G1 5 Not shielded lflex Classic 110 CY 7G0 5 Shielded EMC glands must be used for shielded cables The above cables or equivalent must be used to comply with the EMC Dir...

Страница 17: ...PERSONAL NOTES 15...

Страница 18: ...16 PERSONAL NOTES...

Страница 19: ...17 PERSONAL NOTES...

Страница 20: ...IBC control AB Br nnerigatan 5 A 263 37 H gan s Sverige Tel 46 0 42 33 00 10 Fax 46 0 42 33 03 75 www ibccontrol se info ibccontrol se IBCcontrol F21037905GB Version 1 0 2016 03 01...

Отзывы: