10
PUSH BUTTON
Reset
Reset button for resetting the control unit.
The control unit also resets in the event of voltage drop-out.
In both cases, all alarms reset.
Also see “Reset”, page 12.
SETTINGS VIA POTENTIOMETER
Boost
Torque boost at low rpm. Factory set.
May be increased if necessary, but motor temperature will increase.
Acc
Acceleration time (0-30 s).
Factory set to max; does not need adjustment.
Ret
Retardation time (0-30 s).
Factory set to max; does not need adjustment.
Threshold value
The control unit will start when the input signal exceeds the threshold
value; adjustable between 0-20 % of max input signal.
E.g. selecting 0-10 V input signal will mean an adjustable threshold value
of 0-2 V.
Min rpm
Min rpm (1-20 Hz).
Factory set to 4 Hz.
Max rpm
Max rpm (40-100 Hz).
Factory set to 50 Hz.