DIP SWITCH
6
7
Input signal
1 2 3 4 5 6 7 8 9 10
Potentiometer
0 0 0 0 0 0
0-5 V
0 0 0 0 0 0
0-10 V
1 0 0 0 0 0
0-20 V
0 1 0 0 0 0
1-5 V
0 0 1 0 0 0
2-10 V
1 0 1 0 0 0
5-10 V
1 0 0 1 0 0
10-0 V
1 0 0 0 0 1
10-2 V
1 0 1 0 0 1
10-5 V
1 0 0 1 0 1
0-20 mA
0 0 0 0 1 0
4-20 mA
0 0 1 0 1 0
Cleaning
function
1
Cleaning function connected in ON
position. When the rotor has stopped
for 30 minutes, the cleaning function
is activated and the rotor rotates at
minimum speed for 10 seconds.
Rotation monitor
1
Rotation monitor set to ON position.
High speed *)
1
The rotor rotates at the set maximum
rpm when the switch is set to ON.
Low speed *)
1
The rotor rotates at the set minimum
rpm when the switch is set to ON.