PUTTING THE EQUIPMENT INTO OPERATION

 

Should be done in sequence. 

Check that

the motor rotates in the right direction in relation to the rotor's direction 
of rotation. 
In the event of a fault, switch two phases to the motor.

Setting max speed

Set the “High speed” DIP switch to the ON position. 
Adjust "Max rpm" so that the rotor rotates at 10-12 rpm 
(or as per rotor manufacturer directions). 
After a test run, set the DIP switch to OFF.

Setting min speed

Set the “Low Speed” DIP switch in the ON position.  
Adjust "Min rpm" so that the rotor rotates at 0.2-1 rpm 
(or as per rotor manufacturer directions).
After a test run, set the DIP switch to OFF.

Checking the cleaning
function

Switch off the voltage.
Make sure the cleaning DIP switch is set to ON 
and the input signal is disconnected. 
When power is switched on, the rotor will rotate at minimum rpm for  
10 seconds.

Checking the
rotation monitor

The yellow Rotation LED will flash when the magnet passes 
the magnetic sensor, regardless of DIP switch position.

Setting the threshold 
value

Make sure the control centre is connected. Jump "Run" 5-6.  
Set the minimum output signal on the control centre.  
If the rotor continues to turn, increase the threshold value until it stops.

Finish by

having the control unit drive the rotor at maximum and minimum  
rpm and checking that the rotor speed is correct.  

13

Check that

the DIP switch is set for the type of signal the control equipment outputs.
See “DIP switch” setting, page 7.

Check that

the cleaning function and rotation sensor DIP switch are set to ON.

Continued from previous page

Содержание F21037601

Страница 1: ...IBCcontrol MANUAL CONTROL UNIT FOR ROTARY HEAT EXCHANGER MiniMax Article no F21037601 Set of EMC glands as an option M ade in S w ed en Since 1983 Since 1983 Ska vara 25 mm i diameter p h jden...

Страница 2: ......

Страница 3: ...functions 5 Technical data 6 Functions 6 DIP switch 7 Operational indications 8 Alarms 8 9 Settings via potentiometer 10 Reset 10 Connection diagram 11 Connections 11 12 Checks before powering up the...

Страница 4: ...Disposal and recycling When replacing components or when the control unit in its entirety need replacing please follow the advice below The aim should always be maximum possible recycling of raw mate...

Страница 5: ...power before removing the cover Never touch electrical components or contacts while main current is switched on Risk of electric shock resulting in serious injury or death Connected terminals contain...

Страница 6: ...The Electromagnetic Compatibility Regulations 2016 The Electrical Equipment Safety Regulations 2016 The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Re...

Страница 7: ...has an adjustable threshold of 20 of the input signal s maximum value MiniMax has adjustable boost function The rotation monitor a magnet fitted to the rotor with an associated magnetic sensor stops...

Страница 8: ...0 60 Hz Power input max 650 W Input current max 2 8 A External fuse max 10 A Output voltage 3x0 230 V Min frequency 5 20 Hz Max frequency 40 100 Hz Motor output max 370 W Motor current max 1 9 A Exact...

Страница 9: ...4 20 mA 0 0 1 0 1 0 Cleaning function 1 Cleaning function connected in ON position When the rotor has stopped for 30 minutes the cleaning function is activated and the rotor rotates at minimum speed...

Страница 10: ...every 5 minutes Magnet turned the wrong way Rotation monitor incorrectly connected refer to Connections on pages 11 12 Too wide a gap between the magnetic sensor and magnet max 15 mm Broken belt Belt...

Страница 11: ...e motor resistance it should be identical on all phases Short circuit between phases in the cable Earth fault in the motor or cable Overcurrent MiniMax limits thr current at 4 A and trips then after 4...

Страница 12: ...eased if necessary but motor temperature will increase Acc Acceleration time 0 30 s Factory set to max does not need adjustment Ret Retardation time 0 30 s Factory set to max does not need adjustment...

Страница 13: ...tion monitor A1 A2 A3 1 2 6 10 12 w S br Manual high low speed Input signal Run 3 5 9 11 Reset 1 2 3 Pot 10 k Potentiometer input L N V W 1 x 230 V U Max 2 A 250 V AC 3 x 230 V Max 370 W 13 14 15 T T...

Страница 14: ...Remote reset in the event of alarm connection between terminals 11 12 The control unit is reset automatically in the event of voltage drop out See also Reset page 10 Control relay 16 17 Closes circui...

Страница 15: ...e voltage Make sure the cleaning DIP switch is set to ON and the input signal is disconnected When power is switched on the rotor will rotate at minimum rpm for 10 seconds Checking the rotation monito...

Страница 16: ...GLAND Motor Connection voltage 3G1 5 Not shielded lflex Classic 110 CY 7G0 5 Shielded EMC glands must be used for shielded cables The above cables or equivalent must be used to comply with the EMC Dir...

Страница 17: ...PERSONAL NOTES 15...

Страница 18: ...16 PERSONAL NOTES...

Страница 19: ...17 PERSONAL NOTES...

Страница 20: ...IBC control AB Br nnerigatan 5 A 263 37 H gan s Sverige Tel 46 42 33 00 10 www ibccontrol se info ibccontrol se IBCcontrol F21037906GB Version 1 0 1 2021 10 01...

Отзывы: