iAIRE ultraDRY Series Скачать руководство пользователя страница 7

7

LINE SIZING

In sizing refrigerant lines, cost considerations favor keeping 

the  line  size  as  small  as  possible.  However,  suction  and 

discharge  line  pressure  drops  cause  loss  of  compressor 

capacity and increased power usage.

Excessive  liquid  line  pressure  drops  can  cause  the  liquid 

refrigerant  to  flash,  resulting  in  faulty  expansion  valve 

operation.  Refrigeration  systems  are  designed  so  that 

friction pressure losses do not exceed a pressure differential 

equivalent  to  a  corresponding  change  in  the  saturation 

boiling temperature.

The  primary  measure  for  determining  pressure  drop  is 

a  change  in  saturation  temperature.  Pressure  drop  in  a 

refrigerant  line  causes  a  reduction  in  system  efficiency. 

Correct  sizing  must  be  based  on  minimizing  cost  and 

maximizing efficiency.

Pressure  drop  calculations  are  determined  as  normal 

pressure  loss  associated  with  a  change  in  saturation 

temperature  of  the  refrigerant.  Typically,  the  refrigeration 

system will be sized for pressure losses of 2°F differential or 

less for each segment of the discharge, suction, and liquid 

lines.  An  HFC  refrigerant  liquid  line  is  sized  for  pressure 

losses of 1° differential or less.

IMPORTANT: 

The information above is intended for general 

information  on  refrigerant  piping  only.  Reference  specific 

AHU  and  condensing  units  manuals  for  specific  piping 

details.

REFRIGERANT PIPING GUIDELINES

IMPORTANT: 

The information below is intended for general 

information  on  refrigerant  piping  only.  Reference  specific 

AHU  and  condensing  units  manuals  for  specific  piping 

details.

The design of a refrigerant piping system should:

Ensure  proper  refrigerant  feed  to  evaporators;  Provide 

practical  refrigerant  line  sizes  without  excessive  pressure 

drop; Prevent excessive amounts of lubricating oil from being 

trapped in any part of the system; Protect the compressor at 

all times from loss of lubricating oil; Prevent liquid refrigerant 

or oil slugs from entering the compressor during operating 

and idle time; and Maintain a clean and dry system.

REFRIGERANT LINE VELOCITIES

Economics,  pressure  drop,  noise,  and  oil  entrapment 

establish feasible design velocities in refrigerant lines. These 

are:

Suction line - 700 to 4,000 fpm

Discharge line - 500 to 3,500 fpm

Condenser drain line - 100 fpm or less

Liquid line - 125 to 450 fpm

Higher gas velocities are sometimes found in relatively short 

suction lines on comfort air conditioning or other applications 

where the operating time is only 2,000 to 4,000 hrs per year 

and where the low initial cost of the system may be more 

significant than low operating cost.

Industrial  or  commercial  refrigeration  applications,  where 

equipment runs almost continuously, should be designed with 

low refrigerant velocities for the most efficient compressor 

performance and low equipment operating cost.

The liquid line from the condenser to the receivers should 

be sized for 100 fpm or less to ensure positive gravity flow 

without incurring a backup of liquid flow. Liquid lines from 

the receivers to the evaporator should be sized to maintain 

velocities  below  300  fpm,  thus  minimizing  or  preventing 

liquid hammer when solenoids or other electrically operated 

valves are used.

Minimum Discharge- Line Velocities

Refrigerant Velocity, fpm

Nominal Pipe 

Size, in.

Riser

Horizontal

7/8

375

285

1-1/8

430

325

1-3/8

480

360

1-5/8

520

390

2-1/8

600

450

iAIRE 

OM manual

iAIRE, LLC

Содержание ultraDRY Series

Страница 1: ...PD 05 18 2022 v 1 04 PN IOM 0034 O M manual outside air solutions Thermostat Control...

Страница 2: ...THERMOSTAT DEFAULT SETTINGS TABLE 13 18 WIRING DIAGRAMS 20 23 BACNET POINTS LIST 24 PLUMBING PIPING DIAGRAM 25 26 OPTIONS WIRING DIAGRAMS 27 36 NOTES 37 38 TROUBLESHOOTING 10 Contact iAIRE At www myia...

Страница 3: ...50A Fuse 31 600V 30A Switch 32 600V 60A Switch 33 600V 100A Switch 34 600V 150A Switch Configuration 13 A Down Supply Down Return B Horizontal Supply Down Return C Down Supply Horizontal Return D Hori...

Страница 4: ...rflow Capability 17 L Low H High Options 18 0 No Options A 2 Position Outside Air Damper B 2 Position Exhaust Air C Building Pressure D Outside Airflow Monitoring H Supply Air FIlter Status J Exhaust...

Страница 5: ...TRUCTIONS Asterisk All part numbers and part number references will use an asterisk to designate all characters which do not apply to the part number for the information being provided in that section...

Страница 6: ...ave an authorized factory start up and the start up paperwork on file For Questions Contact iAIRE At www myiaire com Email sales myiaire com Phone 844 348 9168 Fill out Start Up request form here http...

Страница 7: ...ystem should Ensure proper refrigerant feed to evaporators Provide practical refrigerant line sizes without excessive pressure drop Prevent excessive amounts of lubricating oil from being trapped in a...

Страница 8: ...nsure it is what was ordered Verify voltage phases match 1 Verify condition of unit and note any installation or shipping damage to coils or cabinets 2 Verify installation of condensate drain trap 3 V...

Страница 9: ...emperature of the Liquid Line leaving the condenser Condensing temperature should be 100 110 degrees minimum d Calculate Sub cooling Saturation Temp Liquid line Temp Sub cooling e Charge systems for 1...

Страница 10: ...pins make sure there is not a short or the unit will not turn on This is the location for remote start stop d Check to make sure the circuit breaker or the 24V power supply is not tripped 2 Fan speed...

Страница 11: ...mp will come and begin heating the air Once the temperature reaches the set point temperature the heat pump will turn off and the air will continue to circulate in the space without heating or cooling...

Страница 12: ...oor Temperature Occupancy Status Help Language Selection Temperature Units Fan Mode System Mode Date Touch and hold this point for 3 seconds to enter setup mode Note If a configuration installer passw...

Страница 13: ...ABLE Return to previous menu 1 2 Setup Network Configuration Setpoints Display Service view Test Outputs Discover Mode shows wireless ZigBee network Icon not shown if ZigBee communication module not i...

Страница 14: ...DEFAULT SETTINGS TABLE CONT 14 iAIRE OM manual iAIRE LLC...

Страница 15: ...DEFAULT SETTINGS TABLE CONT 15 iAIRE OM manual iAIRE LLC...

Страница 16: ...DEFAULT SETTINGS TABLE CONT 16 iAIRE OM manual iAIRE LLC...

Страница 17: ...DEFAULT SETTINGS TABLE CONT 17 iAIRE OM manual iAIRE LLC...

Страница 18: ...DEFAULT SETTINGS TABLE CONT Custom Menu containing VFD speed setpoint and HGRH min and max 18 iAIRE OM manual iAIRE LLC...

Страница 19: ...N PLACE OF INDOOR FAN POWER DISTRIBUTION BLOCK EXISTING EXISTING SOLID CORE SENSOR 1 2 BB WHITE GRAY AA RED BLACK GREEN MOTOR INCOMING POWER DD P CC 3 1 2 VFD LOW VOLTAGE TERMINAL STRIP SCR AI 1 AGND...

Страница 20: ...K7 S5 OAHSENSOR ECON CO2SENSOR ECON ACTUATOR OPTIONALSENSORS H1 WHT SEEFIGURE 3 H3 S2 YEL BLUE YEL ORG GRAY T18 See Terminal Strip T3 See Terminal Strip T2 See Terminal Strip T2 RED GRN L1 BLK K1 T13...

Страница 21: ...T10 T14 T11 T12 RED R BLK C WHT PURP H2 2 1 4 3 5 6 BRN WHT BLUE YEL T10 T14 T11 T12 RED R BLK C CONDENSER SEE TERMINAL STRIP 3 IN AIR HANDLER FACTORY AIR HANDLER TERMINAL STRIP W2 W1 Y2 Y1 R C FIGUR...

Страница 22: ...PNK T2 YEL T4 BLUE S3 YEL S2 BLUE S1 YEL T5 ORG S4 ORG T16 GRAY S5 GRAY TERMINAL STRIP T1 T1 1 TERMINAL STRIP T2 GRAY GRAY WHT 12 AA GRAY WHT 9 H2 CENTRAL TERMINAL BOARD R Y1 Y2 W1 W2 G C X EXISTING...

Страница 23: ...2 3 4 1 2 3 4 7 8 VALVE 6386 STEPS 5 8 VALVE 3193 STEPS RED BLK RED GRN TERMINAL STRIP T1 WHT BLK H3 FIGURE4 PACKAGE RTU 6 2 3 1 4 5 FIGURE 3 A FIGURE 3 B OPTIONAL MODULATING HEAT MAXITROL GAS VALVE N...

Страница 24: ...THERMOSTAT CONTROL BACNET POINTS LIST 24 iAIRE OM manual iAIRE LLC...

Страница 25: ...USE FOR 2 STAGE UNITS J K P G M H FANCOIL ENTERING AIR EAT REHEAT COIL T DISCHARGE AIR DAH H LEAVING AIR LAT NOT INSTALLED IN SPACE CONTROL UNITS T DISCHARGE AIR DAT T Y1 Y2 W1 W2 W3 HEATING ELECTRIC...

Страница 26: ...NG CONDENSING VALVE 1 FANCOIL E MODULATING HOT GAS VALVE 1 G RAWAL APR VALVE H SUCTION ACCUMULATOR J LIQUD LINE BULB NOT ON APR 410 5 K EXTERNAL EQUALIZER APR 410 2 AND UP L HOT GAS BULB NOT ON APR 41...

Страница 27: ...ON OPTION WIRING REVISION V3 2 0 0 SCH 0001 O C Co on nn ne ec ctt tto o G G S Siig gn na all C Co on nn ne ec ctt tto o C Co om mm mo on n DEVIC IONIZATION COMMON BLACK 24VAC RED 27 iAIRE OM manual i...

Страница 28: ...POWERED SERVICE OUTLET OPTION WIRING REVISION V5 0 0 1 SCH 0010 O 6 7 8 8 7 6 5 4 3 2 1 5 4 3 2 1 Incoming Power from RTU SPLIT 460 V 208 230 V 28 iAIRE OM manual iAIRE LLC...

Страница 29: ...24 VAC COMMON 16 6 17 9 10 GREEN GREEN BLUE WHITE RED WHITE ORANGE BLACK BLACK RED RED WHITE BLACK NOTE Make sure to cut the jumper on the Carrier control board for smoke EXISTING C MAIN CONTROL BOARD...

Страница 30: ...tat provided by other vendors Translator provided as an optional device TO RTU ECON SIG TO ACTUATOR ECONOMIZER CONTROL SCHEMATIC COMM Split Only 2 05 2014 v 1 0 SCH 0014 O J17 J18 J19 J20 COMP 1 COMP...

Страница 31: ...THERMOSTAT CONTROL ECONOMIZER BACNET POINTS LIST 31 iAIRE OM manual iAIRE LLC...

Страница 32: ...AL LO ON NE E IONIZATION WIRING REVISION V3 2 0 0 SCH 001 15 5 O DEVIC IONIZAETION COMMON BLACK 24VAC RED COMMON 120VAC 208VAC 240VAC 480VAC TRANSFORMER BLACK WHITE RED ORANGE BLACK RED 32 iAIRE OM m...

Страница 33: ...R L1 L2 L3 PE 3 COM 1 2 3 JJ 4 Ain1 4 DAT PROCESS CONTROLS O O RING RING GROUND TERM GROUND TERM X C G W2 W1 Y2 Y1 R CENTRAL TERMINAL BOARD existing C BLK R RED L3 L1 L2 L3 L1 L2 GND MAIN POWER FROM R...

Страница 34: ...Sensor 16 High Outside vs Building Space CO2 Alarm 17 High Outside vs Building Space CO2 Alarm 18 19 20 Terminal Strip 1 Occupied 2 Occupied 3 Airflow Low CFM Alarm 5 Airflow Low CFM Alarm 6 Output CF...

Страница 35: ...N N A A L L B B R R O O W W N N B B L L A A C C K K B BL LA AC CK R RE ED B BL LA AC CK B BR RO OW WN E E X X I I S S I I T T I I N N G G F F A A C C T T O O R R Y Y O O D D F F W W I I R R I I N N G...

Страница 36: ...1 DEFAULT SETPOINT 35 psig 465 psig 395 psig N N O O T T E E 1 1 WIRE CONNECTED TO W1 O ONLY INSTALLED WHEN CONNECTING TO HEAT PUMP UNIT N N O O T T E E 2 2 BE SURE TO SELECT N C or N O TO MATCH UNIT...

Страница 37: ...37 iAIRE OM manual iAIRE LLC NOTES...

Страница 38: ...38 iAIRE OM manual iAIRE LLC NOTES...

Отзывы: