SEQUENCE OF OPERATIONS 

THERMOSTAT CONTROL

FAN SPEED CONTROL

These units are equipped with variable speed supply fan 

control.   There is a cooling and heating fan speed set 

point.  In this application, both the cooling and heating fan 

speed set point should be the same.  This should be set by 

the test and balance contractor to provide and correct CFM 

for the unit.  Once the supply fan speed is initially set, it will 

not modulate.

NORMAL HOURS (not night set back)

Cooling Mode(humidistat on cooling) –When the 

temperature gets above the set point temperature by more 

than 2 degrees, the compressor will come on and start 

cooling the air.  Once the temperature reaches the set-

point, the compressor will turn off and the air will continue 

to circulate in the space without heating or cooling.

Heating Mode (humidistat on heating) – When the 

temperature gets below the set point temperature by 

more than 2 degrees, the heat pump will come and begin 

heating the air.  Once the temperature reaches the set  

point temperature, the heat pump will turn off and the air 

will continue to circulate in the space without heating or 

cooling.

Humidity mode – When the unit is not running in cooling 

or heating and the humidity sensor on the humidistat 

registers a humidity higher than the set point humidity, the 

compressor will come on for cooling and the hot gas on/off 

valves will open to raise the discharge temperature of the 

air entering the building after cooling.  This will help reduce 

the humidity without cooling the building off too much.  

Once the humidity is below the set point humidity, the unit 

compressor and hot gas on/off valves will shut off and the 

air will continue to circulate in the space without heating or 

cooling.

NIGHT SET BACK HOURS

Allows the occupant to set a schedule across the 7 day, 24 

hour week to schedule set back temperatures at night to 

conserve energy.

UNOCCUPIED HOURS 

Allows the occupant to set a schedule across the 7 day, 24 

hour week to schedule the unit off to conserve energy.

1

1

iAIRE 

OM manual

iAIRE, LLC

Содержание ultraDRY Series

Страница 1: ...PD 05 18 2022 v 1 04 PN IOM 0034 O M manual outside air solutions Thermostat Control...

Страница 2: ...THERMOSTAT DEFAULT SETTINGS TABLE 13 18 WIRING DIAGRAMS 20 23 BACNET POINTS LIST 24 PLUMBING PIPING DIAGRAM 25 26 OPTIONS WIRING DIAGRAMS 27 36 NOTES 37 38 TROUBLESHOOTING 10 Contact iAIRE At www myia...

Страница 3: ...50A Fuse 31 600V 30A Switch 32 600V 60A Switch 33 600V 100A Switch 34 600V 150A Switch Configuration 13 A Down Supply Down Return B Horizontal Supply Down Return C Down Supply Horizontal Return D Hori...

Страница 4: ...rflow Capability 17 L Low H High Options 18 0 No Options A 2 Position Outside Air Damper B 2 Position Exhaust Air C Building Pressure D Outside Airflow Monitoring H Supply Air FIlter Status J Exhaust...

Страница 5: ...TRUCTIONS Asterisk All part numbers and part number references will use an asterisk to designate all characters which do not apply to the part number for the information being provided in that section...

Страница 6: ...ave an authorized factory start up and the start up paperwork on file For Questions Contact iAIRE At www myiaire com Email sales myiaire com Phone 844 348 9168 Fill out Start Up request form here http...

Страница 7: ...ystem should Ensure proper refrigerant feed to evaporators Provide practical refrigerant line sizes without excessive pressure drop Prevent excessive amounts of lubricating oil from being trapped in a...

Страница 8: ...nsure it is what was ordered Verify voltage phases match 1 Verify condition of unit and note any installation or shipping damage to coils or cabinets 2 Verify installation of condensate drain trap 3 V...

Страница 9: ...emperature of the Liquid Line leaving the condenser Condensing temperature should be 100 110 degrees minimum d Calculate Sub cooling Saturation Temp Liquid line Temp Sub cooling e Charge systems for 1...

Страница 10: ...pins make sure there is not a short or the unit will not turn on This is the location for remote start stop d Check to make sure the circuit breaker or the 24V power supply is not tripped 2 Fan speed...

Страница 11: ...mp will come and begin heating the air Once the temperature reaches the set point temperature the heat pump will turn off and the air will continue to circulate in the space without heating or cooling...

Страница 12: ...oor Temperature Occupancy Status Help Language Selection Temperature Units Fan Mode System Mode Date Touch and hold this point for 3 seconds to enter setup mode Note If a configuration installer passw...

Страница 13: ...ABLE Return to previous menu 1 2 Setup Network Configuration Setpoints Display Service view Test Outputs Discover Mode shows wireless ZigBee network Icon not shown if ZigBee communication module not i...

Страница 14: ...DEFAULT SETTINGS TABLE CONT 14 iAIRE OM manual iAIRE LLC...

Страница 15: ...DEFAULT SETTINGS TABLE CONT 15 iAIRE OM manual iAIRE LLC...

Страница 16: ...DEFAULT SETTINGS TABLE CONT 16 iAIRE OM manual iAIRE LLC...

Страница 17: ...DEFAULT SETTINGS TABLE CONT 17 iAIRE OM manual iAIRE LLC...

Страница 18: ...DEFAULT SETTINGS TABLE CONT Custom Menu containing VFD speed setpoint and HGRH min and max 18 iAIRE OM manual iAIRE LLC...

Страница 19: ...N PLACE OF INDOOR FAN POWER DISTRIBUTION BLOCK EXISTING EXISTING SOLID CORE SENSOR 1 2 BB WHITE GRAY AA RED BLACK GREEN MOTOR INCOMING POWER DD P CC 3 1 2 VFD LOW VOLTAGE TERMINAL STRIP SCR AI 1 AGND...

Страница 20: ...K7 S5 OAHSENSOR ECON CO2SENSOR ECON ACTUATOR OPTIONALSENSORS H1 WHT SEEFIGURE 3 H3 S2 YEL BLUE YEL ORG GRAY T18 See Terminal Strip T3 See Terminal Strip T2 See Terminal Strip T2 RED GRN L1 BLK K1 T13...

Страница 21: ...T10 T14 T11 T12 RED R BLK C WHT PURP H2 2 1 4 3 5 6 BRN WHT BLUE YEL T10 T14 T11 T12 RED R BLK C CONDENSER SEE TERMINAL STRIP 3 IN AIR HANDLER FACTORY AIR HANDLER TERMINAL STRIP W2 W1 Y2 Y1 R C FIGUR...

Страница 22: ...PNK T2 YEL T4 BLUE S3 YEL S2 BLUE S1 YEL T5 ORG S4 ORG T16 GRAY S5 GRAY TERMINAL STRIP T1 T1 1 TERMINAL STRIP T2 GRAY GRAY WHT 12 AA GRAY WHT 9 H2 CENTRAL TERMINAL BOARD R Y1 Y2 W1 W2 G C X EXISTING...

Страница 23: ...2 3 4 1 2 3 4 7 8 VALVE 6386 STEPS 5 8 VALVE 3193 STEPS RED BLK RED GRN TERMINAL STRIP T1 WHT BLK H3 FIGURE4 PACKAGE RTU 6 2 3 1 4 5 FIGURE 3 A FIGURE 3 B OPTIONAL MODULATING HEAT MAXITROL GAS VALVE N...

Страница 24: ...THERMOSTAT CONTROL BACNET POINTS LIST 24 iAIRE OM manual iAIRE LLC...

Страница 25: ...USE FOR 2 STAGE UNITS J K P G M H FANCOIL ENTERING AIR EAT REHEAT COIL T DISCHARGE AIR DAH H LEAVING AIR LAT NOT INSTALLED IN SPACE CONTROL UNITS T DISCHARGE AIR DAT T Y1 Y2 W1 W2 W3 HEATING ELECTRIC...

Страница 26: ...NG CONDENSING VALVE 1 FANCOIL E MODULATING HOT GAS VALVE 1 G RAWAL APR VALVE H SUCTION ACCUMULATOR J LIQUD LINE BULB NOT ON APR 410 5 K EXTERNAL EQUALIZER APR 410 2 AND UP L HOT GAS BULB NOT ON APR 41...

Страница 27: ...ON OPTION WIRING REVISION V3 2 0 0 SCH 0001 O C Co on nn ne ec ctt tto o G G S Siig gn na all C Co on nn ne ec ctt tto o C Co om mm mo on n DEVIC IONIZATION COMMON BLACK 24VAC RED 27 iAIRE OM manual i...

Страница 28: ...POWERED SERVICE OUTLET OPTION WIRING REVISION V5 0 0 1 SCH 0010 O 6 7 8 8 7 6 5 4 3 2 1 5 4 3 2 1 Incoming Power from RTU SPLIT 460 V 208 230 V 28 iAIRE OM manual iAIRE LLC...

Страница 29: ...24 VAC COMMON 16 6 17 9 10 GREEN GREEN BLUE WHITE RED WHITE ORANGE BLACK BLACK RED RED WHITE BLACK NOTE Make sure to cut the jumper on the Carrier control board for smoke EXISTING C MAIN CONTROL BOARD...

Страница 30: ...tat provided by other vendors Translator provided as an optional device TO RTU ECON SIG TO ACTUATOR ECONOMIZER CONTROL SCHEMATIC COMM Split Only 2 05 2014 v 1 0 SCH 0014 O J17 J18 J19 J20 COMP 1 COMP...

Страница 31: ...THERMOSTAT CONTROL ECONOMIZER BACNET POINTS LIST 31 iAIRE OM manual iAIRE LLC...

Страница 32: ...AL LO ON NE E IONIZATION WIRING REVISION V3 2 0 0 SCH 001 15 5 O DEVIC IONIZAETION COMMON BLACK 24VAC RED COMMON 120VAC 208VAC 240VAC 480VAC TRANSFORMER BLACK WHITE RED ORANGE BLACK RED 32 iAIRE OM m...

Страница 33: ...R L1 L2 L3 PE 3 COM 1 2 3 JJ 4 Ain1 4 DAT PROCESS CONTROLS O O RING RING GROUND TERM GROUND TERM X C G W2 W1 Y2 Y1 R CENTRAL TERMINAL BOARD existing C BLK R RED L3 L1 L2 L3 L1 L2 GND MAIN POWER FROM R...

Страница 34: ...Sensor 16 High Outside vs Building Space CO2 Alarm 17 High Outside vs Building Space CO2 Alarm 18 19 20 Terminal Strip 1 Occupied 2 Occupied 3 Airflow Low CFM Alarm 5 Airflow Low CFM Alarm 6 Output CF...

Страница 35: ...N N A A L L B B R R O O W W N N B B L L A A C C K K B BL LA AC CK R RE ED B BL LA AC CK B BR RO OW WN E E X X I I S S I I T T I I N N G G F F A A C C T T O O R R Y Y O O D D F F W W I I R R I I N N G...

Страница 36: ...1 DEFAULT SETPOINT 35 psig 465 psig 395 psig N N O O T T E E 1 1 WIRE CONNECTED TO W1 O ONLY INSTALLED WHEN CONNECTING TO HEAT PUMP UNIT N N O O T T E E 2 2 BE SURE TO SELECT N C or N O TO MATCH UNIT...

Страница 37: ...37 iAIRE OM manual iAIRE LLC NOTES...

Страница 38: ...38 iAIRE OM manual iAIRE LLC NOTES...

Отзывы: