8. Parameter
Fieldbus Communication
203
RCP6S
[29] Home position check sensor input polarit
(Parameter No.43)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
43 Home Position Check Sensor
Input Polarity
HMC
-
0: Sensor not used
1: a contact
2: b contact
In accordance
with actuator
Set the input signal polarity of the home position check sensor (option).
Since the home position check sensor is installed just below the mechanical end, if the actuator
reverses without reaching the mechanical end because of a reason such as interference, an
alarm will be generated because it will be identified as off the position and causes 0BA “Home
sensor non-detection” error.
It is generally unnecessary to change the setting.
Set Value
Description
0
Home position check sensor not used
1
Sensor polarity: Contact a
2
Sensor polarity: Contact b
[30] Silent interval magnification (Parameter
No.45)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
45 Silent interval magnification
SIVM
times
0 to 10
0
Use this parameter to set the silent interval (no communication) time by the time taken for
communication of 3.5 characters or longer before command data transmission when the
controller is operated via serial communication (RTU).
This parameter need not be changed when a teaching tool such as PC software is used.
If “0” is set, no multiplier is applied.
[31] Velocity override (Parameter No.46)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
46 Velocity Override
OVRD
%
1 to 100
100
When move commands are issued from the PLC, the moving speed set in the “Velocity” field of
the position table can be overridden by the value set by this parameter.
Actual movement velocity = [Velocity set in the position table] × [setting value in Parameter
No.46]
Example) Value in the “Velocity” field of the position table: 500mm/s
Setting in Parameter No.46 20%
In this case, the actual movement speed becomes 100mm/s.
The minimum setting unit is 1% and the input range is 1 to 100%.
(Note) This parameter is ignored for move commands from a teaching tool such as PC
software.
For RCP6S, RCM-P6PC
and RCM-P6AC only
ME0349-4B
Содержание RCM-P6AC
Страница 2: ......
Страница 9: ...Fieldbus Communication RCP6S ME0349 4B ...
Страница 32: ...Fieldbus Communication 20 RCP6S ME0349 4B ...
Страница 86: ...2 Wiring Fieldbus Communication 74 RCP6S ME0349 4B ...
Страница 178: ...3 Operation Fieldbus Communication 166 RCP6S ME0349 4B ...
Страница 184: ...4 Vibration Suppress Control Function Fieldbus Communication 172 RCP6S ME0349 4B ...
Страница 192: ...6 Power saving Function Fieldbus Communication 180 RCP6S ME0349 4B ...
Страница 196: ...7 Absolute Reset Fieldbus Communication 184 RCP6S ME0349 4B ...
Страница 284: ......
Страница 285: ......