PCON Specifications (Controller for RCA3/RCP2 Series)
Specification Item
PCON-C
(Internal drive-power
cutoff relay type)
PCON-CG
(External drive-power
cutoff relay type)
PCON-CF
(Internal drive-power
cutoff relay type)
Number of controlled axes
1 axis/unit
Supply voltage
24VDC
10%
Actuator
Peak *2
Peak *2
Peak *3
20/28P motor
35/42/56P motor
2.0A
2.0A
Power-s
ou
rc
e
capacity *1
86P motor
6.0A
Heating value
9.6W
9.6W
26.4W
Control method
Weak field-magnet vector control
Encoder resolution
Incremental specification 800 P/rev
Positioning command
Position number specification 64 points (standard), 512 points (maximum)
*The position number varies depending on the selection of the PIO pattern.
Backup memory
Position data and parameters are saved in nonvolatile memory.
Serial EEPROM can be rewritten 100,000 times. (NOTE 1)
PIO interface
24VDC, input/output
LED indicators
SV (Green) – Servo ON, ALM (Red) – Alarm present
Serial communication
RS485, 1 channel (conforming to the Modbus protocol)
Forced release of
electromagnetic brake
NOM/BK RLS switch (on the front panel)
Cable length
Actuator cable: 20m or less
I/O flat cable: 10m or less
Insulation strength
500VDC, 10M
Surrounding air
temperature
0 to 40
C
Surrounding humidity 85%RH or less (non-condensing)
Surrounding
environment
Refer to Installation Environment
Surrounding storage
temperature
-10 to 65
C
Surrounding storage
humidity
90%RH or less (non-condensing)
Environment
Vibration Durability
10 to 57Hz in XYZ directions/Pulsating amplitude 0.035mm (continuous),
0.075mm (intermittent)
57 to 150Hz/4.9m/s
2
(continuous), 9.8m/s
2
(intermittent)
Protection class
IP20
Cooling method
Natural air-cooling
Forced air-cooling
Weight
300g or less
300g or less
320g or less
External dimensions
35W x 178.5H x 68.1D (mm)
*1: The rush current, which is approx. 5 to 12 times the
rated current, flows for approx. 1 to 2msec after
power-on. Please note that the rush current value
varies depending on the impedance of the power
line.
*2: Excitation phase detection is performed after
power-on. In such a case, the current becomes
maximum (normally 100msec).
However, a current of approx. 6.0A flows (for
approx. 1 to 2msec) if the motor driving power is
turned on again after its shutdown.
*3: Excitation phase detection is performed after
power-on. In such a case, the current becomes
maximum (normally 100msec).
However, a current of approx. 10.0A flows (for
approx. 1 to 2msec) if the motor driving power is
turned on again after its shutdown.
As a +24V DC power supply,
select the power supply of the
“peak load support” specification
or one with sufficient capacity.
In particular, in the case of the
unit with the remote sensing
function, the greatest care is
required.
NOTE 1: Position data and parameters are written to EEPROM.
Please note that the rewrite limit is around 100,000 times.
External Dimensions
Installation Environment
This product is capable for use in the environment of pollution degree 2
*1
or equivalent.
*1 Pollution Degree 2 : Environment that may cause non-conductive pollution or transient
conductive pollution by frost. (IEC60664-1)
1.
Installation Environment
Do not use this product in the following environment.
Location where the surrounding air temperature exceeds the range of 0 to 40
C
Location where condensation occurs due to abrupt temperature changes
Location where relative humidity exceeds 85%RH
Location exposed to corrosive gases or combustible gases
Location exposed to significant amount of dust, salt or iron powder
Location subject to direct vibration or impact
Location exposed to direct sunlight
Location where the product may come in contact with water, oil or chemical droplets
Environment that blocks the air vent [Refer to Installation and Noise Elimination
Section]
When using the product in any of the locations specified below, provide a sufficient
shield.
Location subject to electrostatic noise
Location where high electrical or magnetic field is present
Location with the mains or power lines passing nearby
2.
Storage and Preservation Environment
The storage and preservation environment should comply with the same standards as
those for the installation environment. In particular, when the machine is to be stored
for a long time, pay close attention to environmental conditions so that no condensation
forms. Unless specially specified, moisture absorbency protection is not included in the
package when the machine is delivered. In the case that the machine is to be stored
and preserved in an environment where condensation is anticipated, take the
condensation preventive measures from outside of the entire package, or directly after
opening the package.
Installation and Noise Elimination
1.
Noise Elimination Grounding (Frame Ground)
2.
Precautions Regarding Wiring Method
(1) Use a twisted cable for connection to the 24V DC power supply.
(2) Separate signal lines and encoder cables from high-power lines such as the power
wire.
3.
Noise Sources and Elimination
Carry out noise elimination measures for
power devices on the same power path
and in the same equipment.
The following are examples of measures
to eliminate noise sources:
(1) AC solenoid valves, magnet
switches and relays
[Measure]
Install a surge killer parallel with
the coil.
(2) DC solenoid valves, magnet
switches and relays
[Measure]
Install a diode parallel with the
coil. Use a DC relay with a built-in
diode.
4.
Heat Radiation and Installation
Conduct design and manufacture in consideration of the control box size, controller
layout and cooling in such a way that the temperature around the controller will be 40
C
or less.
Do not share the ground wire with
or connect to other equipment.
Ground each controller.
Class D grounding
(Formerly Class-III grounding:
Grounding resistance at 100
or less)
178.
5
170.
5 (
M
o
un
ting
di
m
en
si
on)
5
68.1
5
35
50mm or more
Fan
50mm or more
95mm
or more
Airflow
Controller
Ground Terminal
Annealed copper wire:
Connect a ground wire
with a diameter of 1.6mm
or larger.
Connect the ground wire
to the mounting screw of
the controller.
Surge Killer
Relay coil
+
-
Relay
coil
Controller
Controller
Other
equipment
Other
equipment
Other
equipment