i2O
|
www.i2owater.com
|
|
+44 (0) 2380 111 420
Page 7
To consider before start the Calibration Process:
All APVs are factory set to
provide
approx.
18m
minimum
downstream
pressure.
Rotating the APV end cap
by “1-slot” is equivalent to
1m water pressure in both
directions. Use a C-
spanner to adjust the APV
where required.
Always ensure the APV is
depressurized
(hoses
disconnected)
when
performing calibrations.
When end cap contact is
made with the internal
spring, the equivalent
pressure is approximately
10m