i
6
LOWER
DISPLAY
UPPER
DISPLAY
PARA
METER
DESCRIPTION
DEFAULT
OUTPUT 2
MODE
Disable
This parameter will appear only if Control logic is Heat-Cool.
If Enabled, User can set Diff. mode for OUTPUT 2 in USER list.
If disabled, User can not set Diff. mode for OUTPUT 2 in USER list.
OUTPUT 2
CONTROL
15.0
OP2 will be OFF at A OP2C value irrespective of output 2 mode.
This parameter will appear only if Control logic is Heat-Cool.
15
Default USER LOCK CODE is 15 to access Control & Configuration List.
User has a choice to set its own USER LOCK CODE between 1 to 9999, this is to
prevent unauthorized access of Control & Configuration List.
USER
LOCK
CODE
SET
POINT 1
Enable
If Enabled, User can View & edit the Set point (SP1) in USER list.
If disabled, User can only View the Set Point (SP1) but Can not edit it in USER
list.
This parameter allows the user to select output 2 as an ‘Auxiliary’ control.
For options refer Table 3.
For options refer Table 4.
This parameter allows the user to select output 2 as an ‘Alarm’ control.
This parameter allows the user to select output 2 as a ‘Soak’ mode.
For options refer Table 5.
This parameter allows the user to select output 2 to function as both ‘Alarm’ &
‘Soak’. For options refer Table 4 & 5.
OUTPUT 2
FUNCTION
Auxiliary
When NONE is selected, Output 2 will be permanently de-activated.
By pressing DOWN key, Lower display will Toggle between SP1-value, SP2-
value, Alarm SP-Value(AL.SP) & Timer-value(SOAK).
By this parameter Lower display will only show the SP1-value.
By this parameter Lower display will only show the Timer value(SOAK TIME).
This parameter will appear only if Output 2 is set as SOAK/ AL.ST
By this parameter Lower display will show Setpoint till soak timer has not started
and afterwards, it will display the Timer value(SOAK TIME).
LOWER
DISPLAY
MESSAGE
SP1
LOWER
DISPLAY
RAMPING
SETPOINT
This parameter will appear only if Ramp rate is enabled.
If Enabled, User can View ramping setpoint.
If disabled, User can View target setpoint.
This parameter will appear only if Ramp rate is enabled.
Enable
TABLE 3 :
Below listed options will appear only if OP2 is selected as an Auxiliary Control Mode .
OUTPUT 2
LOGIC
HEAT
User can select Heat logic for control Output 2 in which OP2 will remain ON till
PV<SP2 (PV increases when output is ON).
User can select Cool logic for control Output 2 in which OP2 will remain ON till
PV> SP2 (PV decreases when output is ON).
LOWER
DISPLAY
UPPER
DISPLAY
PARA
METER
DESCRIPTION
DEFAULT
If selected, User can set SP2 value independently, irrespective of SP1.
In this mode SP2 is always related with SP1.
User can set SP2 value with deviation of ± 99°C w.r.t SP1.
ABS
SET
POINT
2
SET
POINT
2
Enable
If Enabled, User can View & edit the Set point (SP2) in USER list.
If disabled, User can not View or edit Set Point (SP2) in USER list.
OIM Px-X28 V2.0 Page 6 of 9