background image

i

5

OIM BL-886 V1.0 Page 5 of 6

Configuration Mode

(1) To enter in this mode, Press and hold SET & UP key simultaneously for 3 sec. 
(2) Press UP or DOWN key to scroll between parameter options. 
(3) Press SET key to store the current parameter & move on to the next parameter.

Input 
Freq.

Medium

Lock
Code

0

Default

Display

Parameter

Type

Batch

OP2F

Batch

Mode

Mode 

1

Front

Reset

Enable

10.00

mm

Diameter

Very High Frequency:- 

If selected; Count Input Frequency up to 2.5KHz.

High Frequency:- 

If selected; Count Input Frequency up to 1KHz.

Medium Frequency:- 

If selected; Count Input Frequency up to 100Hz.

Low Frequency:- 

If selected; Count Input Frequency up to 30Hz.

Very Low Frequency:- 

If selected; Count Input Frequency up to 3Hz.

User  can  select  an  option  from  Very  Low/Low/Med/High/Very  High  according  to  the 
frequency  of  count  pulse  at  the  input  terminal.  This  feature  is  useful  in  avoiding  noise 
signal.

Set this parameter to 15 (Default LOCK CODE) to access Configuration List.
User has a choice to set different Lock Code in the range 1 ~ 9999 via USER LOCK 
CODE in Configuration List.

Description

User can select an option between Batch Type, Length Type & Preset Type.

Batch Type :

 If Selected Instrument will Work as Batch Counter.

Length Type :

 If Selected Instrument will Work as Length Counter.

Preset Type :

 If Selected Instrument will Work as Preset Counter.

Batch:-

  If  selected,  Output2  used  as  Batch  Output.  When  Batch  Count  Equal  to  Set 

Batch Output2 will Turn on. Output 2 will turn off by pressing Down/Reset Key for 3Sec. 
in View Mode.

Set Count 2:-

 If selected, Output2 used as independent Set Point. When Running Count 

Equal  to  Set  Count  2  Output2  will  Turn  on.  Output  2  will  turn  off,  depending  on  Time 
Parameter or by pressing Down/Reset Key.
Note:- This parameter will appears only if Mode as Mode 1 Selected. 

Auxiliary:-

 If selected, Output2 have same function as Output 1. 

Off:-

 If selected, Output2 is not used & cab be kept reserve for future use.

This parameter will occurs only if Batch type is selected.

Mode - 1: 

In this mode Relay1 & Buzzer will Turn Off simultaneously depending on “Time 

parameter” value in Set mode.

Mode  -  2: 

In  this  mode  Relay1  &  Buzzer  will  Turn  Off  depending  on  “Set  Count  -  Off” 

Value in Set mode.

ENABLE:

  If  selected;  user  can  reset  the  Running  Count  &  Total  Count  by  pressing 

Down/Reset key located at front panel.

DISABLE:

  If  selected;  user  can  not  reset  the  counter  by  pressing  down  key  located  at 

front panel. Only remote reset at back terminal is allowed. This feature is useful to avoid 
unauthorized attempt to reset the counter during run mode.

User can set desired Diameter value. 'dIA' will be displayed on lower display 
&  last  stored/default  value  of  ‘Dia  Meter'  will  be  displayed  on  upper  display. 
User  can  change  this  value  by  using  Up/Down/Shift  key.  Press  'set'  key  to 
store the desired value & move to next parameter.

0.01 to

9999.99

mm

Отзывы: