OIM AI-7X41 V2.1 Page 3 of 5

(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values / options)

CONTROL LIST :

 

 SET & DOWN key simultaneously  

To enter in this mode press 

for 3 sec. User can set the control parameters.

 PARA

METER

RANGE

DESCRIPTION

DEFAULT

DISPLAY

PRORTIONAL

BAND

INTEGRAL

TIME

DERIVATIVE

TIME

CYCLE

TIME

CONTROL

HYS.

0.5 

to 

99.9°C

o

1 to 100  C

to 

3600 Sec.

to 

300 Sec.

1.0

 to 

100 Sec.

50 %

 to 

100 %

This  parameter  will  be  prompted  only  if  selected  control  action  is  PID.  It  sets 
bandwidth  over  which  the  output  power  is  adjusted  depending  upon  the  error  (SV-
PV). The value of this parameter is automatically set by Auto tune function.

This parameter will be prompted only if selected control action is PID. It defines how 
strongly the Controller will react to the rate of change of PV. Value of this parameter 
is automatically set by Auto Tune function. If set to ‘0’, this function will be disabled.

This  parameter  will  be  prompted  only  if  selected  control  action  is  PID.  User  can  set 
this  value  based  on  process  being  controlled  &  type  of  Output  being  selected.  For 
Relay  O/P,  cycle  time  should  be  more  than  12sec  &  for  SSR  O/P,  cycle  time  should   
be less than 5 Sec.

This parameter will be prompted only if selected control action is ON-OFF. It sets the 
dead  band  between  ON  &  OFF  switching  of  the  Output.  Larger  value  of  hysterisis 
minimize  the  number  of  ON-OFF  operation  of  load.  This  increases  life  of  actuators 
like contactors but also produces large errors (between PV & SV).

This parameter will be prompted only if selected control action is PID. It sets the time 
taken  by  PID  algorithm  to  remove  steady  state  error.  Value  of  this  parameter  is 
automatically set by Auto Tune function. If set to ‘0’, this function will be disabled.

o

5.0 C

  240

   60

16.0 Sec.

100 %.

100 %.

2°C

DELAY 

0

 to

500 Sec.

This parameter will be prompted only if selected control action is ON-OFF. It sets the 
output  restart  time  where  O/P  once  turned  OFF  will  turn  ON  only  after  restart  time, 
regardless difference between PV & SP in Heat or Cool mode. If set to '0', O/P will be 
switched without delay. Also, Delay will be applicable at every power ON.

0 Sec.

0

LOCK
CODE

1 ~ 9999

Set this parameter to 15 (Default LOCK CODE) to access Control List.
User has a choice to set different Lock Code via USER LOCK CODE in Config. List.

OUTPUT
 POWER

LIMIT

TUNE 

OFFSET

  0.0 %

TO

100.0 %

This parameter will be prompted only if selected control action is PID. This parameter 
will decide the maximum output power in % applied to the load

This parameter will be promted only if selected control action is PID.This parameter  
allows the user to carry out Auto Tuning function below the set point. (If tune offset is 
set to 50 %, tuning will be carried out at 50 % of the set point and If set to 100 %, 
tuning will be carried out at 100 % of the set point.)

OUTPUT

OFF

This parameter will be prompted only if selected control action is PID. With this 
parameter  O/P will be Completely OFF after the Set Point + Offset Value. If 
Disable, O/P will act Depending upon the PID Value after Set Point achieved.

Disable

1  to 10 

MODEL

VERSION

INPUT

HOME

PV

POWER UP :

At power-on, following sequence will be prompted on the display for 1 sec. till it reaches to Home display mode.

PROGRAMMING :

USER LIST :

 

To access the user list, Press & Release SET key once.

(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values/options).

 PARA
METER

DISPLAY

RANGE

DESCRIPTION

DEFAULT

 Control
Set Point

LSPL~HSPL

User can change SP value using UP/ DOWN keys. Holding the key, will change the value 
at a faster rate. Press SET key to store the value & move on to the next parameter.

0°C