OIM AI-7X41 V2.1 Page 3 of 5
(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values / options)
CONTROL LIST :
SET & DOWN key simultaneously
To enter in this mode press
for 3 sec. User can set the control parameters.
PARA
METER
RANGE
DESCRIPTION
DEFAULT
DISPLAY
PRORTIONAL
BAND
INTEGRAL
TIME
DERIVATIVE
TIME
CYCLE
TIME
CONTROL
HYS.
0.5
to
99.9°C
o
1 to 100 C
0
to
3600 Sec.
0
to
300 Sec.
1.0
to
100 Sec.
50 %
to
100 %
This parameter will be prompted only if selected control action is PID. It sets
bandwidth over which the output power is adjusted depending upon the error (SV-
PV). The value of this parameter is automatically set by Auto tune function.
This parameter will be prompted only if selected control action is PID. It defines how
strongly the Controller will react to the rate of change of PV. Value of this parameter
is automatically set by Auto Tune function. If set to ‘0’, this function will be disabled.
This parameter will be prompted only if selected control action is PID. User can set
this value based on process being controlled & type of Output being selected. For
Relay O/P, cycle time should be more than 12sec & for SSR O/P, cycle time should
be less than 5 Sec.
This parameter will be prompted only if selected control action is ON-OFF. It sets the
dead band between ON & OFF switching of the Output. Larger value of hysterisis
minimize the number of ON-OFF operation of load. This increases life of actuators
like contactors but also produces large errors (between PV & SV).
This parameter will be prompted only if selected control action is PID. It sets the time
taken by PID algorithm to remove steady state error. Value of this parameter is
automatically set by Auto Tune function. If set to ‘0’, this function will be disabled.
o
5.0 C
240
60
16.0 Sec.
100 %.
100 %.
2°C
DELAY
0
to
500 Sec.
This parameter will be prompted only if selected control action is ON-OFF. It sets the
output restart time where O/P once turned OFF will turn ON only after restart time,
regardless difference between PV & SP in Heat or Cool mode. If set to '0', O/P will be
switched without delay. Also, Delay will be applicable at every power ON.
0 Sec.
0
LOCK
CODE
1 ~ 9999
Set this parameter to 15 (Default LOCK CODE) to access Control List.
User has a choice to set different Lock Code via USER LOCK CODE in Config. List.
OUTPUT
POWER
LIMIT
TUNE
OFFSET
0.0 %
TO
100.0 %
This parameter will be prompted only if selected control action is PID. This parameter
will decide the maximum output power in % applied to the load
This parameter will be promted only if selected control action is PID.This parameter
allows the user to carry out Auto Tuning function below the set point. (If tune offset is
set to 50 %, tuning will be carried out at 50 % of the set point and If set to 100 %,
tuning will be carried out at 100 % of the set point.)
OUTPUT
OFF
This parameter will be prompted only if selected control action is PID. With this
parameter O/P will be Completely OFF after the Set Point + Offset Value. If
Disable, O/P will act Depending upon the PID Value after Set Point achieved.
Disable
1 to 10
MODEL
VERSION
INPUT
HOME
PV
POWER UP :
At power-on, following sequence will be prompted on the display for 1 sec. till it reaches to Home display mode.
PROGRAMMING :
USER LIST :
To access the user list, Press & Release SET key once.
(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values/options).
PARA
METER
DISPLAY
RANGE
DESCRIPTION
DEFAULT
Control
Set Point
LSPL~HSPL
User can change SP value using UP/ DOWN keys. Holding the key, will change the value
at a faster rate. Press SET key to store the value & move on to the next parameter.
0°C