background image

Table 3.1 mGARD-100 Trip Levels vs. Turns through ZSCS.

30mA (L, L, L, L)

30mA

15mA

10mA

2.5mA

2mA

40mA (L, L, L, R)

40mA

20mA

14.3mA

5mA

4mA

60mA (L, L, R, L)

60mA

30mA

20mA

7.5mA

6mA

90mA (L, L, R, R)

90mA

45mA

30mA

12.5mA

10mA

150mA (L, R, L, L)

150mA

75mA

50mA

25mA

20mA

250mA (L, R, L, R)

250mA

125mA

83.3mA

30mA

24mA

400mA (L, R, R, L)

400mA

200mA

133.3mA

37.5mA

30mA

600mA (L, R, R, R)

600mA

300mA

200mA

52.5mA

42mA

900mA (R, L, L, L)

900mA

450mA

300mA

75mA

60mA

1500mA (R, L, L, R)

1500mA

750mA

500mA

125mA

100mA

2500mA (R, L, R, L)

2500mA

1250mA

833.3mA

150mA

120mA

4A (R, L, R, R)

4A

2A

1.33A

250mA

200mA

6A (R, R, L, L)

6A

3A

2A

600mA

480mA

9A (R, R, L, R)

9A

4.5A

3A

750mA

600mA

10A (R, R, R, L)

10A

5A

3.33A

1.05A

840mA

12A (R, R, R, R)

12A

6A

4A

1.5A

1.2A

dip setting

1 turn

2 turns

3 turns

4 turns

-Applies to both internal and external CT

5 turns

3.3 INDICATION

There is one green LED on the front of the mGARD-100:

LED Off:

 No control voltage or mGARD-100 defective

LED Slow Flashing:

 Normal, control voltage on

LED Fast Blinking:

 Ground Fault Trip

LED Steady On:

 Control voltage too low or mGARD-100 defective

MGARD-SYM REMOTE INDICATOR

The mGARD-SYM is a remote display indicator that is used in conjunction with I-Gard relays. The indicator has the 

capability to interconnect and work with up to 50 relays including the mGARD-100 relay in a bus network topology 
and provides detailed device status information.

As shown in Figure 3.0, the display has a 4-line screen that shows a list of connected devices. A device can be 
selected and viewed in detail. The relay mode, delay and trip level settings can be viewed (but not altered). The reset 
and test functions can also be performed directly from the display. 

Fault levels are displayed as a percentage of the selected pickup (trip) current level. If the trip level is 1 Amp 
and there is a 500 mA fault current, the reading on the display will appear as 50%. Screen navigation is done 

using a 4-button interface. The menus are displayed on the right side of the LCD; the left side is reserved for 

viewing relay information.

To properly display current levels on the mGARD-SYM, the trip levels can be set to match to a 100:1 or 1000:1 
interposing ZSCS using the mGARD-SYM interface.

Содержание mGARD-100

Страница 1: ...C 419EM Instruction Manual March 2015 Ground fault relay microprocessor based relay mGARD 100...

Страница 2: ...mer service and technical leadership We build on this foundation by investing in developing new products in electrical safety education including EFC scholarship program by actively participating in t...

Страница 3: ...safe 4 Manual Rreset 4 3 2 Dipswitch Settings 4 3 3 Indication 6 mGard Sym Remote Indicator 6 3 4 Reset 7 3 5 Ground Fault Test 7 4 Installation Instructions 8 4 1 Mounting 8 4 2 Built In Current Tran...

Страница 4: ...nate false tripping when using the relay on systems with variable frequency drives With the harmonic filter disabled the relay will accurately respond to AC currents between 25 and 400Hz By using an i...

Страница 5: ...mpere for all relays and coordinating between upstream and downstream relays by selecting different time delays 3 operation 3 1 Operation and Glossary of Terms Auto Reset After a trip the relay will a...

Страница 6: ...s set to trip the relay contacts change their state Time Delay Intentional period of time programmed to elapse before the tripping operation of the relay It should not be confused with the breaking op...

Страница 7: ...L R R R R L L R R L R R R R L R R R R 30 40 60 90 150 250 400 600 900 1500 2500 4 6 9 10 12 3 4 6 9 15 25 40 60 90 150 250 400 600 900 1000 1200 30 40 60 90 150 250 400 600 900 150 250 4000 6000 9000...

Страница 8: ...t Trip LED Steady On Control voltage too low or mGARD 100 defective MGARD SYM REMOTE INDICATOR The mGARD SYM is a remote display indicator that is used in conjunction with I Gard relays The indicator...

Страница 9: ...t is NOT necessary to press the remote test reset button after the ground fault has been cleared when the mGARD 100 is set in the pulsed trip auto reset mode In this mode the relay will reset automati...

Страница 10: ...ing current sensor keep the distance between the relay and the sensor as short as possible Use twisted cable and increase the gauge of the conductor as per the table below Table 4 0 ZSCS secondary wir...

Страница 11: ...4 Cables in form factor 2 42 mm 0 3 0 34 0 43 0 59 0 75 0 87 1 02 7 74 8 7 11 15 19 22 26 6 7 Cables in form factor 3 0 mm 0 37 0 43 0 54 0 73 0 93 1 07 1 26 9 6 10 8 14 18 24 27 32 9 10 Cablse in fo...

Страница 12: ...phase and neutral conductors through the window of the interposing zero sequence current sensor Note that the relay is located downstream from the neutral ground point Position the cable in the centre...

Страница 13: ...shows an mGARD 100 relay operating in non failsafe mode The relay is monitoring the neutral conductor in a resistance grounded system Figure 4 3 shows a system with several mGARD 100 relays monitoring...

Страница 14: ...listed below in Table 5 1 Table 5 1 mGARD 100 DC control voltage options 12V 9 18 VDC 12DCV mGARD 100 12DCV 24V 18 36 VDC 24DCV mGARD 100 24DCV dc voltage range catalogue number suffix example 6 serv...

Страница 15: ...ts Main Trip Relay Type Form Z N O and N C pair Rating 10A 250V AC resistive 10A 30V DC resistive Terminal Contact Material Clamping screw nickel plated brass Plug contacts tin plated bronze Physical...

Страница 16: ...I GARD RESERVES THE RIGHT TO CHANGE SPECIFICATIONS OF ITS PRODUCTS WITHOUT NOTICE 8 dimensional drawings Figure 8 0 mGARD 100 dimensions in millimetres inches...

Страница 17: ...Notes...

Страница 18: ...www i gard com Phone 905 673 1553 Toll Free 1 888 737 4787 Fax 905 673 8472 sales i gard com...

Отзывы: