I-CON Systems, Inc., for product support call 1-866-730-7192 or visit us online at support.i-con.com
Continued Next Column
Continued on Next Page
Hand tighten the vacuum breaker nut to the flushometer. Once
everything is properly aligned, tighten the tailpiece lock nut,
spud nut, & vacuum breaker nut with a smooth jawed wrench.
Step 3
Flush Supply Installation Continued
FLUSHING THE
SUPPLY LINE
Before the water is turned on, unscrew the control stop cap
from the control stop and turn the adjustment screw all the
way
CLOCKWISE
to ensure that the control stop is closed.
Remove the flushometer cap using a strap wrench. Then remove
the trip mechanism & ProLAST
®
.
Step 1
Step 2
Reinstall the flushometer cap
WITHOUT
the trip mechanism
and ProLAST
®
.
Step 3
I-CON COBALT
™
Manual Exposed Flush Valve
powered by ProLAST
®
Installation Instructions
VLV-FVL-MN3000 Series
Rev 022719