COBALT Pro
™
Wall Sensor Retrofit Kit for
Concealed Flush Valve Installation Instructions
I-CON Systems, Inc., for product support call 1-866-730-7192 or visit us online at support.i-con.com
One or more products contained herein are protected by U.S. Patent with other undergoing the patent process www.i-con.com/patents
Part No. 101674
page 6
Rev 080323
ADJUSTING CONTROL STOP
Step 1
Turn adjustment wheel
COUNTERCLOCKWISE
1/2 turn from
closed position. Activate flush valve.
Step 2
To adjust flush valve, turn adjustment wheel in small increments.
Activate flush valve after each adjustment. The proper flow rate
should completely cleanse fixture without splashing water
outside of fixture.
NOTE:
The flow from the valve must never exceed the flow
capacity of the fixture. If a valve failure should occur, the fixture
must be able to accommodate a continuous flow from the valve.
CONTROL MODULE AND INTERFACE SETUP
NOTE:
When powered and face plate is removed, control
module automatically enters maintenance mode. While
maintenance mode is active, a solid green light indicates that
a user is detected. Control module exits maintenance mode
when face plate is replaced or after 30 minutes. To re-enter
maintenance mode, press any quick action button.
QUICK ACTION BUTTON DIAGRAM
Full Flush
Half Flush
Full
Flush
Count
Reset