Electronic Motor Protection Relays
Classification
Normal Type – Earth Leakage
HGMP N60 Z
Normal Type - Instantaneous
HGMP N60 I
Advanced Type
HGMP A60
Panel Installation Type
Separated/Integrated
Separated
Connection Type
Screw type/Tunnel type
Rated Current
60 : 0.5 ~ 60 A
1)
Current Configuration Range
Minimum rated current ~ maximum rated current
Control Voltage (50/60 Hz)
A/DC 100 ~ 240 V
Function
Overcurrent
Over 112.5 % ± 5 % – Definite time, inverse time (thermal, non-thermal)
Undercurrent
User set (30 to 90 % of rated current)
1)
Phase Failure
Over 70 ± 10 % of phase current deviation
Phase Unbalance
Over user set ± 10 % of phase current deviation
Rotor
Stall
User set after startup (Over 150 ~ 700 % of rated current) – Definite time only
Lock
User set after startup (Over 200 ~ 1,000 % of rated current) – Definite time only
Reverse Phase
Detection during startup
Earth Leakage
User set (100 ~ 2,500 mA)
-
User set (100 ~ 2,500 mA)
Ground Fault
0.5 ~ 60 A
Instantaneous
-
User set (600 ~ 1,500 % of rated current)
Time Settings
Overcurrent
Inverse
Operation time: 1 ~ 60 class (for 600 %)
Definite
Delay time : 0, 1 ~ 200 sec, operation time : 0.2 ~ 60 sec
Undercurrent
User set (0.5 ~ 30 sec)
Phase Failure
Less than 2 sec
User set (0.5 ~ 10 sec)
Phase Unbalance
Less than 5 sec
User set (0.5 ~ 10 sec)
Rotor
Stall
Less than 5 sec
User set (0.5 ~ 10 sec)
Lock
Less than 500 msec
User set (0.5 ~ 10 sec)
Reverse Phase
Less than 100 msec
Earth Leakage
User set (0.1 ~ 10 sec)
3)
-
User set (0.1 ~ 10 sec)
3)
Ground Fault
User set (0.1 ~ 10 sec)
3)
Instantaneous
-
Less than 50 msec – Operation delay during startup can be set
Overload Warning Function Setting
60 ~ 110 % of rated current
1)
Runtime Alert Function
OFF/1 ~ 9,999 Hour
Accuracy
Current
±5 % (or 100 mA)
2)
Time
±10 % (or 0.5 sec)
Contact
No. of Contacts
Main contact : 2SPST
Main contact : 2SPST, Auxiliary contact : 1SPST
Capacity
3 A/250 VAC (Resistive load)
Environment
Operation
-20 ~ 60 ℃
Storage
-30 ~ 85 ℃
Relative Humidity
35 ~ 85 % RH (No freezing)
Withstand Voltage
Between Main Circuit And Enclosure
2,000 VAC/1 min
Between Main Circuits
2,000 VAC/1 min
Between Contacts
1,000 VAC/1 min
The Others
Insulation Resistance
over 100 MΩ at 500 VDC
Standard
IEC 60947-4-1
ZCT input
200 mA/100 mV
Cable Spec.
1.5 m, 2 m, 3 m
Power Consumption
under 2 W
※
1)
Minimum operational current is over 70 % of minimum rated current
2)
50 % for earth leakage
3)
Operation delay during startup can be set. (For HGMP N60 Z, earth leakage and ground fault share the operation time configuration)
21