Hytronik HIR27 Скачать руководство пользователя страница 8

Settings (Remote Control HRC-11)

Press button “RESET”, all settings go back to default:
Hold-time 5min, Daylight sensor 100Lux, Stand-by time: 10min, Stand-by dimming 
level: 20%

Reset Settings

Permanent ON/OFF function

Press button “ON/OFF” to select permanent ON or permanent OFF mode.
* Press button “AUTO”, “RESET” to quit this mode.

AUTO mode

Press button “AUTO” to initiate automatic mode. The sensor starts working and all 
settings remain as before the light is switched ON/OFF.

Note: the function of Semi-auto is disabled.

ON/

OFF

& A

4

4h

h

h

HRC-11

Press button “Shift”, the LED on the top left corner is on to indicate mode selection. 
All values / settings in RED are valid for 20 seconds. 

Shift Button

Press buttons in zone “ Daylight threshold” to set daylight sensor at 2Lux/ 10Lux / 50Lux / 100Lux / 300Lux / Disable.

Daylight threshold

1. Press button “Shift”, the red LED starts to flash. 
2. Press button “Ambient”, the surrounding lux level is sampled and set as the new daylight threshold.

Ambient daylight threshold

Scene program - 

1-key commissioning

Detection range

All buttons in this zone are disabled.

1. Press button “Start” to program.
2. Select the buttons in “Detection range”, “Daylight threshold”, “Hold-time”, “Stand-by time”, “Stand-by dimming level” to set all 
parameters.
3. Press button “Memory” to save all the settings programmed in the remote control.
4. Press button “Apply” to set the settings to each sensor unit(s).     
    

For example, to set detection range 100%, daylight threshold Disable, hold-time 5min, stand-by time +∞, stand-by dimming level 30%, the steps should be:  

    Press button “Start”, button ”100%”, “Disable”, “Shift”, “5min”, “Shift”, “+∞”, “30%”, “Memory”. By pointing to the sensor unit(s) and pressing “Apply”, all 
    settings are passed on the sensor(s).

Brig/-

Press these two buttons to adjust the light output brightness and set a new target lux level. The daylight sensor can measure ambient 
daylight level and ignore the LED light, so as to calculate how much artificial light is needed to maintain the target lux level.

Press the buttons to select light output at 80% (atinitial 10,000 hours) or 100%.

Note: “Sensor off” and “Twilight” functions are disabled.

Power output

Subject to change without notice.

Edition: 30 Jun. 2021      Ver. A0      Page 8/9

Содержание HIR27

Страница 1: ...eded natural light has proirity synchronization control TX T X T X RX Synchronisation terminal for grouping of sensors Input Characteristics Stand by power Model No HIR27 Operating voltage 0 5W Appr 20s Warming up 220 240VAC 50 60Hz Switched power Max 40pcs devices 80mA EMC standard EMC Safety standard LVD Certification EN55015 EN61000 EN61547 CB CE EMC LVD RCM ROHS compliance Safety and EMC EN606...

Страница 2: ...lens 6 Clip fascia to body 7 Bend back springs and insert into ceiling 4 5 2 3 1 65mm Install lens as required 7 2 1 Install blind as required A B 6 3 2 1 Wire Preparation 0 75 2 5mm 8mm min 6mm max 11mm Pluggable screw terminal It is recommended to make connections to the terminal before fitting to the sensor Subject to change without notice Edition 30 Jun 2021 Ver A0 Page 2 9 Note We recommend t...

Страница 3: ...rn for single person Ta 20 O C Recommended ceiling mount installation height 2 5m 6m max 64m2 Ø 9m max 13m2 Ø 4m max 13m2 Ø 4m max 13m2 Ø 4m max 13m2 Ø 4m max 13m2 Ø 4m max 50m2 Ø 8m max 38m2 Ø 7m max 38m2 Ø 7m max 38m2 Ø 7m Blind Option 1 Aisle Detection Optional Accessory Ceiling Surface Mount Box HA03 Optional Accessory Blind Insert for Blocking Certain Detection Angles 75 Ø 94 Blind Option 2 1...

Страница 4: ...0m2 Ø 5m max 20m2 Ø 5m max 20m2 Ø 5m 2 HIR27 R Reinforced Low bay A Tangential movement Tangential max 10m h max 6m A B Radial movement Radial max 5m h max 6m B Optional Accessory Ceiling Surface Mount Box HA03 Optional Accessory Blind Insert for Blocking Certain Detection Angles 75 Ø 94 Valid Range Blind Option 1 Aisle Detection Blind Option 2 180 O Detection Valid Range insensitive sensitive ins...

Страница 5: ...essory Ceiling Surface Mount Box HA03 Optional Accessory Blind Insert for Blocking Certain Detection Angles 75 Ø 94 Valid Range Blind Option 1 Aisle Detection Blind Option 2 180 O Detection Valid Range Radial B Tangential A 2 5m Mount height 11m 12m 10m 8m 6m max 104m2 Ø 11 5m max 50m2 Ø 8m max 154m2 Ø 14m max 227m2 Ø 17m max 269m2 Ø 18 5m max 314m2 Ø 20m max 7m2 Ø 3m max 7m2 Ø 3m max 7m2 Ø 3m max...

Страница 6: ...eiling Surface Mount Box HA03 75 Ø 94 4 HIR27 RH Reinforced High bay with 3 Pyro Tangential max 30m h max 12m A Radial max 4m h max 12m B Radial B Tangential A 2 5m Mount height 11m 12m 10m 8m 6m max 154m2 Ø 14m max 38m2 Ø 7m max 314m2 Ø 20m max 531m2 Ø 26m max 615m2 Ø 28m max 707m2 Ø 30m max 7m2 Ø 3m max 7m2 Ø 3m max 7m2 Ø 3m max 13m2 Ø 4m max 13m2 Ø 4m max 13m2 Ø 4m A Tangential movement B Radia...

Страница 7: ... is manual override 2 3 Semi auto Mode Absence Detection Manual Override 2 Short Push 1s on off function On Off the light turns off immediately and cannot be triggered ON by motion until the expiration of pre set hold time After this period the sensor goes back to normal sensor mode Off On the light turns on and goes to sensor mode no matter if ambient Lux level exceeds the daylight threshold or n...

Страница 8: ...d Scene program 1 key commissioning Detection range All buttons in this zone are disabled 1 Press button Start to program 2 Select the buttons in Detection range Daylight threshold Hold time Stand by time Stand by dimming level to set all parameters 3 Press button Memory to save all the settings programmed in the remote control 4 Press button Apply to set the settings to each sensor unit s For exa...

Страница 9: ...dimming level to set the stand by dimming level at 10 20 30 50 All buttons are disabled Auto configuration function 1 Press button Shift the red LED starts to flash 2 Select a time period and the sensor will do light level measurement and determine save the lowest light level commission line with 100 light on so as to set the target lux level automatically Note 1 Make sure the light level measurem...

Отзывы: