Hytronik HIR27 Скачать руководство пользователя страница 7

1

Functions and Features

Daylight Harvest

Light will not switch on 
when natural light is 
sufficient, even there is 
motion detected.

The light switches on 
automatically with 
presence when natural 
light is insufficient.

The light turns on at full or dims to maintain the lux level. The light output 
regulates accroding to the level of natural light available.

The light dims to stand-by 
period after hold-time and 
stays on selected minimum 
dimming level.

The light switches off when 
the ambient natural light is 
sufficient.

The light switches off 
completely after the 
stand-by period.

3

Selecting this mode will activate the following logic:

Manual on - The lights will not switch on until they have manually been switched on at the wall switch.  The occupancy sensor is
                  inactive whilst the lights are off.

Auto off - When the lights are on, the sensor becomes active and monitors the space for activity.  Once the area is vacated
              (absence setection), the sensor will automatically switch off the lights if the last person out  forgets to switch off the light
              manually.

Note: The wall switch can be assigned to function      or      , but not both. The default function is manual override.

2

3

Semi-auto Mode (Absence Detection)

Manual Override

2

* Short Push (<1s): on/off function;   
   On 

 Off: the light turns off immediately and cannot be triggered ON by motion until the expiration of pre-set hold-time. After this 

                    period, the sensor goes back to normal sensor mode.
   Off 

 On: the light turns on and goes to sensor mode, no matter if ambient Lux level exceeds the daylight threshold or not.

* Long Push (>1s): adjust the target lux level by turning the light up or down. Both the adjustment on remote control and push switch 
                            can overwrite each other. The last adjustment remains in memory. 

Note: if end-user do not want this manual override function, just leave the “push” terminal unconnected to any wire.

   

With the help of push-switch, this sensor can be over-ridden by the end-user to manually switch on/off the light, or adjust the target lux 
level by push-switch, which makes the product more user-friendly and offers more options to fit some extra-ordinary demands:

3

4

Synchronisation Function

By connecting the “SYNC” terminals in parallel (see wiring diagram), no matter which sensor detects motion, all HIR27 in the group 
will turn on the lights when surrounding natural light is below the daylight threshold. The detection area could be widely enlarged in 
this way. 

Subject to change without notice.

Edition: 30 Jun. 2021      Ver. A0      Page 7/9

Содержание HIR27

Страница 1: ...eded natural light has proirity synchronization control TX T X T X RX Synchronisation terminal for grouping of sensors Input Characteristics Stand by power Model No HIR27 Operating voltage 0 5W Appr 20s Warming up 220 240VAC 50 60Hz Switched power Max 40pcs devices 80mA EMC standard EMC Safety standard LVD Certification EN55015 EN61000 EN61547 CB CE EMC LVD RCM ROHS compliance Safety and EMC EN606...

Страница 2: ...lens 6 Clip fascia to body 7 Bend back springs and insert into ceiling 4 5 2 3 1 65mm Install lens as required 7 2 1 Install blind as required A B 6 3 2 1 Wire Preparation 0 75 2 5mm 8mm min 6mm max 11mm Pluggable screw terminal It is recommended to make connections to the terminal before fitting to the sensor Subject to change without notice Edition 30 Jun 2021 Ver A0 Page 2 9 Note We recommend t...

Страница 3: ...rn for single person Ta 20 O C Recommended ceiling mount installation height 2 5m 6m max 64m2 Ø 9m max 13m2 Ø 4m max 13m2 Ø 4m max 13m2 Ø 4m max 13m2 Ø 4m max 13m2 Ø 4m max 50m2 Ø 8m max 38m2 Ø 7m max 38m2 Ø 7m max 38m2 Ø 7m Blind Option 1 Aisle Detection Optional Accessory Ceiling Surface Mount Box HA03 Optional Accessory Blind Insert for Blocking Certain Detection Angles 75 Ø 94 Blind Option 2 1...

Страница 4: ...0m2 Ø 5m max 20m2 Ø 5m max 20m2 Ø 5m 2 HIR27 R Reinforced Low bay A Tangential movement Tangential max 10m h max 6m A B Radial movement Radial max 5m h max 6m B Optional Accessory Ceiling Surface Mount Box HA03 Optional Accessory Blind Insert for Blocking Certain Detection Angles 75 Ø 94 Valid Range Blind Option 1 Aisle Detection Blind Option 2 180 O Detection Valid Range insensitive sensitive ins...

Страница 5: ...essory Ceiling Surface Mount Box HA03 Optional Accessory Blind Insert for Blocking Certain Detection Angles 75 Ø 94 Valid Range Blind Option 1 Aisle Detection Blind Option 2 180 O Detection Valid Range Radial B Tangential A 2 5m Mount height 11m 12m 10m 8m 6m max 104m2 Ø 11 5m max 50m2 Ø 8m max 154m2 Ø 14m max 227m2 Ø 17m max 269m2 Ø 18 5m max 314m2 Ø 20m max 7m2 Ø 3m max 7m2 Ø 3m max 7m2 Ø 3m max...

Страница 6: ...eiling Surface Mount Box HA03 75 Ø 94 4 HIR27 RH Reinforced High bay with 3 Pyro Tangential max 30m h max 12m A Radial max 4m h max 12m B Radial B Tangential A 2 5m Mount height 11m 12m 10m 8m 6m max 154m2 Ø 14m max 38m2 Ø 7m max 314m2 Ø 20m max 531m2 Ø 26m max 615m2 Ø 28m max 707m2 Ø 30m max 7m2 Ø 3m max 7m2 Ø 3m max 7m2 Ø 3m max 13m2 Ø 4m max 13m2 Ø 4m max 13m2 Ø 4m A Tangential movement B Radia...

Страница 7: ... is manual override 2 3 Semi auto Mode Absence Detection Manual Override 2 Short Push 1s on off function On Off the light turns off immediately and cannot be triggered ON by motion until the expiration of pre set hold time After this period the sensor goes back to normal sensor mode Off On the light turns on and goes to sensor mode no matter if ambient Lux level exceeds the daylight threshold or n...

Страница 8: ...d Scene program 1 key commissioning Detection range All buttons in this zone are disabled 1 Press button Start to program 2 Select the buttons in Detection range Daylight threshold Hold time Stand by time Stand by dimming level to set all parameters 3 Press button Memory to save all the settings programmed in the remote control 4 Press button Apply to set the settings to each sensor unit s For exa...

Страница 9: ...dimming level to set the stand by dimming level at 10 20 30 50 All buttons are disabled Auto configuration function 1 Press button Shift the red LED starts to flash 2 Select a time period and the sensor will do light level measurement and determine save the lowest light level commission line with 100 light on so as to set the target lux level automatically Note 1 Make sure the light level measurem...

Отзывы: