6.   The  FC20  and  FC20.WM  can  switch  the  live  supply  of  up  to 

two  external  pumps  (220/240V  AC,  maximum  10  amps). 
Connections  are  provided  for  this  on  the  220/240V  terminal 
block as shown in the wiring details diagram.  The FC20.4 and 
FC20.WM.4  can  switch  the  live  supply  of  up  to  two  external 
pumps. 

 
7.   Connect  the  external  pulse  supply,  from  up  to  two  pumps, 

inside  the  pulse  connections  junction  box  as  shown  in  the 
wiring  details  diagram.  In  the  case  of  the  FC20.WM  the  pulse 
connection terminal block is located in the base of the cabinet.  
An extra junction box/terminal block is provided for the FC20.4 
and FC20.WM.4.  

 
8.   Ensure  all  the  terminal  screws  are  tight  and  replace  the 

junction box covers. 

 
 

 

 

FC20 ELECTRICAL CONNECTION DETAILS 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FC20 POWER

SUPPLY

(CONSTANT)

220 / 240V AC

FUSE - 16A

220 / 240 V AC

POWER

SUPPLY IN

E

L

N

1

3

2

5

E

4

7

6

8

FC20 & FC20.WM (2 PUMP) 220/240V TERMINAL BLOCK CONNECTIONS

EXTERNAL

PUMP

CONTROL

10

9

L

N

E

PUMP 2 LIVE
SUPPLY IN

PUMP 2 SWITCHED
LIVE SUPPLY OUT

PUMP 1 SWITCHED
LIVE SUPPLY OUT

PUMP 1 LIVE
SUPPLY IN

L

N

L

L

L

L

Содержание FC20 Series

Страница 1: ...ls only FC20 FC20 4 FC20 WM FC20 WM 4 Please read carefully before commencing installation Registered Office HYTEK GB LIMITED Delta House Green Street Elsenham Bishop s Stortford CM22 6DS UK Registered in England No 1915382 Tel 44 0 1279 815 600 Fax 44 0 1279 812 978 email info hytekgb com Web www hytekgb com ...

Страница 2: ...aste streams It is your responsibility to dispose of this and other electric and electronic equipment via designated collection facilities appointed by the government or local authorities IMPORTANT WARNING NOTES 1 This system must not be sited adjacent to a petrol dispenser or in any other hazardous zone 2 Installation of this equipment should only be carried out by qualified fuel installation eng...

Страница 3: ...s of the four 12 mm diameter mounting holes provided For the FC20 WM use the mounting plate provided to mount to a suitable wall ELECTRICAL 4 Remove the covers from the 220 240V supply and the pulse input connection junction boxes For the FC20 WM the 220 240V terminal block is located behind the override fuse panel which can be removed by removing the four screws in its face 5 Connect a constant 2...

Страница 4: ... details diagram In the case of the FC20 WM the pulse connection terminal block is located in the base of the cabinet An extra junction box terminal block is provided for the FC20 4 and FC20 WM 4 8 Ensure all the terminal screws are tight and replace the junction box covers FC20 ELECTRICAL CONNECTION DETAILS FC20 POWER SUPPLY CONSTANT 220 240V AC FUSE 16A 220 240 V AC POWER SUPPLY IN E L N 1 3 2 5...

Страница 5: ...1 2 0V PUMP 1 PULSES IN FC20 POWER SUPPLY CONSTANT 220 240V AC FUSE 16A 220 240 V AC POWER SUPPLY IN E L N 1 3 2 5 E 4 7 6 8 FC20 4 FC20 WM 4 4 PUMP 220 240V TERMINAL BLOCK CONNECTIONS EXTERNAL PUMP CONTROL 10 9 L N E PUMP 2 LIVE SUPPLY IN PUMP 2 SWITCHED LIVE SUPPLY OUT PUMP 1 SWITCHED LIVE SUPPLY OUT PUMP 1 LIVE SUPPLY IN L N L L L L PUMP 4 LIVE SUPPLY IN PUMP 4 SWITCHED LIVE SUPPLY OUT PUMP 3 S...

Страница 6: ...S419 8 ...

Страница 7: ...S419 8 ...

Страница 8: ...ssions EN61000 3 2 1995 A12 Emissions EN61000 3 3 1995 2006 95 EC Electrical Equipment Low Voltage S I 1992 3037 S I 1994 2063 Amendment Entry Into Force 1 January 1993 Primary Legislation The European Communities Act 1972 Machinery Directive 98 37 EC 2006 42 EC Waste Electrical and Electronic Equipment Regulations 2006 2002 96 EC 2003 108 EC Authorized By Clive Wellings Declaration Number EC042 ...

Отзывы: