HydraSwing Programming & Operations
© 2018
S
mart
t
OucH
c
OntrOLLer
i
nputS
When using AC power, an LED lights next to any active input.
1. Test the open and close function of the gate before wiring to accessory devices (external control
inputs). This makes it easier to troubleshoot if an unexpected functionality arises.
NOTE:
If you are using the operator strictly in a DC capacity, the Smart Touch Controller has a tact button you
can push which lights an LED next to the active inputs. This button is in the bottom left corner of the STC board.
Press the SHOW LEDs push button switch to verify the status of the terminal inputs.
2. All the Smart Touch Controller inputs listed below are shown as a single input. The second wire is
connected to the Common Terminal Bus on the Power Supply Board.
NOTE:
The Emergency Close and Fire Dept. Open inputs are an exception and require a +24V input.
The +24V is located on Power Supply Board next to the Common Bus. See drawing on previous page.
Stc t
erminaL
i
nputS
WARNING
Use Terminal Inputs 4, 5, 6, and 7 for external control devices. DO NOT connect an external control device to
Input Terminals, 1, 2, or 3 unless the controls are located in clear view of the entire gate area and are being
constantly monitored and supervised.
NOTE:
UL 325 2016 sensor input label changes shown in
Bold
.
Smart Touch Controller Inputs Chart
1
Stop Button
Stop Button
Normally Closed input. Jumper
to Common if input is not being
used.
Line of sight, external
stop button or 3-button
station.
2
Open Button
Open Button
Do not use for radio or remote
access controls.
Normally Open Input
Line of sight, external
open button or 3-button
station.
3
Close Button
Close Button
Do not use for radio or remote
access controls.
Normally Open Input
Line of sight, external
close button or 3-button
station.
4
Remote Open
& Radio Control
Remote Open
& Radio
Control
For radio/remote open device:
Access the RO from the User
Menu and set to 1. NO Input
Remote access control or
radio controls
5
Open/Close
Button
Open/Close
Button
Connection for push button or
radio controls.
Singular button device
(multi-function)
6
Open Partial
Open Partial
NOTE:
Terminal is only used in
slide gates. Adjustable through
the Installer Menu from 7 to 99.
Monitored access
controls
Содержание HSG80F
Страница 2: ...www SecureOpeners com 800 878 7829 Sales SecureOpeners com...
Страница 14: ...Page intentionally left blank xiv MX3636 01 Rev D HydraSwing Programming Operations 2018...
Страница 36: ...Page intentionally left blank 22 MX3636 01 Rev D HydraSwing Programming Operations 2018...
Страница 124: ...110 MX3636 01 Rev D HydraSwing Programming Operations 2018 Page intentionally left blank...
Страница 136: ...122 MX3636 01 Rev D HydraSwing Programming Operations 2018...