w

ire

 S

izinG

 

and

 r

unS

Supplying a gate operator with the correct electrical service is crucial to the performance of the operator and 

the life of its electrical components.  If the wire size used is too small, the voltage loss, especially during motor 
startup, will prevent the motor from attaining its rated horsepower. The percentage of horsepower lost is far 

greater than the percentage of voltage loss.  

A voltage loss can also cause the control components to chatter while the motor is starting, substantially 

reducing their life due to the resultant arcing. There is no way to restore lost performance resulting from 

undersized wires, except to replace them. To avoid costly rewiring, be sure to choose a sufficient wire size 

during site planning phases and at initial installation.

The tables on the following page are based on copper wire and allow for a 5% voltage drop. The ampere 

values shown are the service factor ampere rating of the motor (maximum full load at continuous duty). At 
minimum, a 20A circuit (protected with a 20A Inverse Time Breaker) should be provided.

Always connect electrical power and ground the operator in accordance with the NFPA 780 & NEC, Article 430 

and Article 250. Research and adhere to other local codes that may apply.

Low Voltage Control Wiring

The Smart Touch Controller has very sensitive control inputs. The following is a chart of maximum distances for 
wire size:

Wire Size 

Maximum Distance

   18 ga  

7.0 miles (11 km)

   20 ga  

3.5 miles (5.6 km)

   22 ga  

2.7 miles (4.3 km)

   24 ga  

2.0 miles (3.2 km)

   26 ga  

1.0 mile (1.6 km)

   28 ga  

3700 feet (1.1 km) 

  © 2018 

Power 

MX3636-01 Rev. D 

17  

Содержание HSG80F

Страница 1: ...HydraSwing 40 40F 40 Twin 40F Twin 80F 150 Swing gate linear actuator with Smart Touch Controller Programming and Operations Manual www SecureOpeners com 800 878 7829 Sales SecureOpeners com...

Страница 2: ...www SecureOpeners com 800 878 7829 Sales SecureOpeners com...

Страница 3: ...user and installer menu options designing vehicle loop layouts troubleshooting and maintaining the gate operator Programming Operations Manual with HySecurity Smart Touch Controller MX3636 01 Revision...

Страница 4: ...and UPS models Build Year UL 325 2016 set at the factory UL 325 Entrapment Protection Sensor Monitoring Required Normally Closed NC sensors tested approved Three SENSOR Inputs on Controller Installer...

Страница 5: ...pment protection sensors available for NC monitoring of automatic gate operators All HySecurity gate operators manufactured after January 1 2016 using software versions h4 50 or h5 50 or later comply...

Страница 6: ...te HydraSwing 40 cover off Cylinder Gate mount welded to gate Bearing 2x Base of cylinder Rod end clevis end Brake manifold assembly Manual release Hoses with Quick Disconnects Brake valves Chassis wi...

Страница 7: ...nduit Grade level Smart Touch Controller display and keypad Smart Touch Controller Variable Speed Drive Motor Pump pack assembly Earth ground location in cabinet Control box Power board Hand pump loca...

Страница 8: ...Components Breather cap Vent plug Quick Disconnects Open valve Filler plug Pressure gauge Reservoir Pressure relief valve Inherent Entrapment Sensor IES Solenoid viii MX3636 01 Rev D HydraSwing Progra...

Страница 9: ...nal Installer s Responsibility continued 5 Safety Owner User Responsibility 6 Hazardous Materials and Proper Disposal 6 Identifying Gate Operator Category and Usage Class 7 Breather Cap Installation a...

Страница 10: ...30 How Software Handles Monitoring External Entrapment Protection Sensors 31 Table 3 Changes to Sensor Inputs on the Controller 31 External Entrapment Protection Sensors What the Installer Needs to D...

Страница 11: ...ting an Interlocked Pair Dual Gate 67 Dual Gate Wiring Connections 68 Dual or Sequenced Gates Power Software Accessory Requirements 69 Programming a Dual Gate Interlocked Pair 69 Connecting Sequenced...

Страница 12: ...u 97 Electrical Issues 98 AC Powered Gate Operators 98 HydraSwing Wiring Diagram Pre May 2017 99 Mechanical Issues 100 Hydraulic Issues 100 Typical Problems and Troubleshooting Procedures 101 General...

Страница 13: ...14 Smart Touch Photo Eye Thru Beam EMX IRB MON 115 Smart Touch Photo Eye Reflective E3K R10K4 116 Smart Touch The Solution MIM 62 Multi input Module 117 Smart Touch Photo Eye Reflecti Guard RG R 118 S...

Страница 14: ...Page intentionally left blank xiv MX3636 01 Rev D HydraSwing Programming Operations 2018...

Страница 15: ...rket Slide swing traffic barrier fortified crash barrier gate wedge and vertical lift operators have all received rigorous testing and certification Security low maintenance flexible configuration and...

Страница 16: ...lowing The gate safety section of the HySecurity website contains published materials regarding industry changes due to UL 325 2016 requirements involving external entrapment protection sensors Links...

Страница 17: ...Security product manuals and review all the literature that accompanies the product It is important that only qualified installers handle the installation of the HySecurity equipment and gate operator...

Страница 18: ...esignated and signs direct pedestrians to the walk through gate 8 Install the supplied WARNING signs on the inside and outside of the gate or barrier gate operator so they are clearly visible from bot...

Страница 19: ...unted beyond 6 feet 183 cm of the gate to prevent users from touching or accessing the gate while operating the controls People attempting to access the controls by reaching through or around the gate...

Страница 20: ...signs are required to maintain UL 325 compliance Do not physically disable the warning buzzer and NEVER disconnect or cut its wires The buzzer provides compliance with the Manual on Uniform Traffic Co...

Страница 21: ...uch as a multi family housing unit five or more single family units hotels garages retail stores or other buildings accessible by or servicing the general public Class III Class III Intended for use i...

Страница 22: ...e to perform the following procedure will cause premature pump shaft failure and void the Limited Warranty 1 Remove the vent plug and discard it 2 Replace the vent plug with the breather cap Refer to...

Страница 23: ...and power is disconnected turned OFF The manual release option can be found on the brake manifold To move the gate manually turn OFF the power switch on the control box in the HydraSupply cabinet and...

Страница 24: ...it remains in the open position NOTE If the valve re seats itself repeat the pull and twist in the opposite direction until the valve remains open 5 Begin pumping the handle up and down As hydraulic f...

Страница 25: ...IES Check gate operator specifications If the gate is heavy and near the weight capacity of what the gate operator can handle make sure the gate has an open design that allows wind to flow through it...

Страница 26: ...ry could occur if the hazardous situation is not avoided NOTICE Indicates damage to equipment is probable if the hazardous situation in not avoided Common Industrial Symbols The following internationa...

Страница 27: ...efer to the National Fire Protection Association NFPA 780 Standard for the Installation of Lightning Protection Systems Highlights of the standard include The ground rod must be UL listed copper clad...

Страница 28: ...for all AC power connections Verify that the operator is electrically grounded per NFPA 780 and NEC Article 250 and local codes Wiring AC Power The HydraSwing has separate Installation Instructions t...

Страница 29: ...INSIDE OBSTRUCTION VEHICLE DETECTOR OUTSIDE OBSTRUCTION VEHICLE DETECTOR SHADOW RESET VEHICLE DETECTOR EDGE SENSOR PHOTO EYE POWER 24 VOLTS COMMON PHOTO EYE POWER DO NOT USE PHOTO EYE OPEN DIRECTION D...

Страница 30: ...DIO CONTROL OPEN CLOSE 1 OPEN PARTIAL INTERLOCK OPEN TIME CLOCK OPEN FREE EXIT DETECTOR DISABLE EXIT DETECTOR DISABLE CLOSE TIMER INSIDE OBSTRUCTION VEHICLE DETECTOR OUTSIDE OBSTRUCTION VEHICLE DETECT...

Страница 31: ...o choose a sufficient wire size during site planning phases and at initial installation The tables on the following page are based on copper wire and allow for a 5 voltage drop The ampere values shown...

Страница 32: ...2 2 2 2 2 VFD Rating Amps 17 4 17 4 8 7 8 7 5 2 5 2 Wire Gauge Distance Distance Distance Distance Distance Distance 12 90 27m 100 30m 220 67m 240 73m 680 207m 830 253m 10 150 46m 170 52m 350 107m 390...

Страница 33: ...oltage frequency is converted to DC to begin with there is absolutely no relationship between the input frequency phase and frequency phase of the power supplied to the motor The input could be 1 or 3...

Страница 34: ...overview wiring and conduit considerations DC Power Supply UPS Connections If you have a gate operator with a DC Power Supply unit you will need to connect the primary AC input power to the DC Power...

Страница 35: ...system continues to move the gate System features are covered in the HyInverterAC Installation and Reference Manual shipped with the product and available online NOTICE The AC Power Supply with HyInv...

Страница 36: ...Page intentionally left blank 22 MX3636 01 Rev D HydraSwing Programming Operations 2018...

Страница 37: ...ller Menu Mode Navigation Buttons To change that data appearing in the display To navigate through the Selections To choose what appears on the display To navigate between menu items Press Select Two...

Страница 38: ...the gate a few times LEARN CLOSE INCHES XXX X Learn Close Limits Choose one of the following bullet procedures depending on the gate location The gate is in the desired closed position press Stop twi...

Страница 39: ...sure the gate is properly installed and aligned before performing the following steps Take precautionary measures to keep the gate s travel path clear The gate will be moving while you adjust the pres...

Страница 40: ...s SS 0 OFF IES STOP ONLY 0 stop revers for 2s 1 stop only In a Usage Class 4 environment the operator can be set to stop the gate and not reverse gate travel after an IES trip NOTE This menu option ap...

Страница 41: ...he site power are controlled better which results in less intermittent operator problems Smoother operator acceleration and deceleration enhances gate travel All HydraSwing gate operators include ModB...

Страница 42: ...of gate travel To operate properly a device must be connected between Terminal 23 on the Smart Touch Controller and a 24VDC terminal on the Power Module When the connections are made a constant hold s...

Страница 43: ...serial number Replacement controller boards for existing sites allow for a Build Year setting of 1 BY 1 pre 2016 Independent Sensor Inputs The edge photo eye and photo eye COM inputs on the Smart Tou...

Страница 44: ...ensor function SR IES reverse to open Smart Touch Controller Installer Menu Functions for IES Installer Menu Display Code Setting Options Bold Factory Settings Description SE 2 IES SENSITIVITY 1 max s...

Страница 45: ...tor controller New silk screen controller boards are on order but until they are ready for shipment labels will be overlaid on the board to indicate terminology adaptations Table 3 indicates how the e...

Страница 46: ...other conditions may dictate the use of additional safety designs components It is up to the gate system designer and installer to assess appropriate safety design and components above and beyond mini...

Страница 47: ...splay To navigate between menu items Press Select Two left characters blink Press Next or Previous Continue pressing Next to view all selections Press Select Blinking characters become static Press Ne...

Страница 48: ...nsors press NEXT so PE 1 ON appears 5 Press SELECT PE stops blinking 6 Press MENU to exit Menu Mode and return to Run Mode NOTE The Photo Eye Align mode turns OFF with the next limit contact For more...

Страница 49: ...ir function Each call out explains where to find more information about the component Smart Touch Controller Provides inputs for peripherals accessories 2 electromechanical user relays 250VAC 10A one...

Страница 50: ...4 Smart Touch Controller LIMIT DUAL GATE RADIO OPTIONS DRIVE POWER RS485 MOTOR USER 1 USER 2 USER 3 VEHICLE DETECTOR VEHICLE DETECTOR VEHICLE DETECTOR STOP BUZZER FREE EXIT INSIDE OBSTR OUTSIDE OBSTR...

Страница 51: ...different operational modes exist Run Mode gate is operational awaiting commands Menu Mode motor disengages and operator commands are ignored Data entry menu navigation and menu selection can be accom...

Страница 52: ...325 Information about the classes can be found online through DASMA Technical Data Sheets www dasma com or UL 325 www ul com OP Open Position E Extended cylinder and R Retracted cylinder Refer to Ope...

Страница 53: ...RLOCK OPEN TIME CLOCK OPEN FREE EXIT DETECTOR DISABLE EXIT DETECTOR DISABLE CLOSE TIMER INSIDE OBSTRUCTION VEHICLE DETECTOR OUTSIDE OBSTRUCTION VEHICLE DETECTOR SHADOW RESET VEHICLE DETECTOR SENSOR 1...

Страница 54: ...Select Blinking characters become static Press Next or Previous Advance press Next Previous press Previous CT 0 OFF CLOSE TIMER Pressing Select causes the left most two characters to blink CT in the e...

Страница 55: ...character display identifies operator status Pressing Menu scrolls through operator status displays and accesses the User Menu NOTE Pressing the Menu button twice bypasses the operator status displays...

Страница 56: ...G all models except 50VF series 2 SwingRiser HRG 3 HydraLift HVG 4 StrongArm HTG 5 SlideWinder 24 6 SlideWinder 38 7 SlideDriver 50VF 8 StrongArm CRASH 9 HydraSwing 10 HydraSupply XL Indicates and ide...

Страница 57: ...your operator is set for the correct date and time zone can be accomplished by taking the following steps 1 While in Run mode gate status appears in the display press and hold the STOP button The dat...

Страница 58: ...ld to Close but configures the Open inputs for a constant hold function 0 Momentary open signal 1 Constant hold open push button required To comply with UL 325 Type D protection you must set HO to 1 C...

Страница 59: ...lect and change the date and time When your selections are complete press Menu to return to User Menu mode N A LD 5 LCD CONTRAST 5 0 through 9 Adjusts the contrast of the display Available settings fr...

Страница 60: ...f a laptop computer and S T A R T software See Smart Touch Analyze and Retrieve Tool information found on the HySecurity website Table 6 describes the Installer Menu items and supplies the factory def...

Страница 61: ...325 Usage Class UC The installer sets the usage class for the operator to function NOTE The usage class setting does not appear on Crash products N A SH 0 GATE HANDING 0 gate disabled R viewed from th...

Страница 62: ...is required before the gate can be closed 24V Fire Dept Open 24 OC 0 DISABLED EMERGENCY CLOSE 0 disabled 1 enabled Enables the Emergency Close input When set to 1 the constant hold close overrides ve...

Страница 63: ...Sensor 1 2 or 3 Sensor COM COM 24V EO 0 STOP ONLY EYE OPEN LOGIC 0 Open eye stops only 1 Two second reverse to close If the open photo eye is triggered the default setting is non reversal while the g...

Страница 64: ...ing disables the free exit detector NOTE When set to 0 the free exit is disabled while the gate rests on it s closed limit If the closed limit is not tripped the free exit continues to work normally D...

Страница 65: ...d can be used for high voltage and or high current loads Connect devices directly to the top of the relay COM and either NO and or NC contacts Multiple logic function options exist Refer to User Relay...

Страница 66: ...eared when the 13 User Relay function Rx 13 LOITERING was configured Now even without the User Relay option 13 being utilized LT is a standard Installer Menu item User Relay 13 OS 1 30 SEC OPEN SPEED...

Страница 67: ...it loop detector Hy5B ILD0 RUN MODE IND OBS LOOP SET 0 Run mode 1 Show frequency 2 Show call level 0 7 3 Set Frequency Controls the Hy5B Inside Obstruction Loop detector Hy5B OLD0 RUN MODE OUT OBS LOO...

Страница 68: ...the full close stop is retained in memory NOTE During this process you can press and hold Open to reverse direction and adjust the gate position Learn Open Limits 1 When the Learn Open display appear...

Страница 69: ...navailable 2 Use the Select and then Next or Previous buttons to navigate and change the number of seconds appearing on the display Refer to Menu Mode Navigation on page 40 3 To exit the User Menu pre...

Страница 70: ...erator Cycle the gate a few times by pressing the Close and Open buttons If installed for emergency fast operation test the EMERGENCY CLOSE using the constant hold device Observe the travel speed of t...

Страница 71: ...585 VERSION S N RS232 DISPLAY VEHICLE DETECTOR COM COM A B RPM COM OPEN S1 24V 24V STATUS LED Stop Button 1 Open Button 2 Close Button 3 Remote Open and Radio Control 4 Open Close 5 Open Partial 6 Int...

Страница 72: ...HICLE DETECTOR SENSOR 1 SENSOR COM DO NOT USE SENSOR 2 DO NOT USE SENSOR 3 DO NOT USE CHARGER AC LOSS LOCK INTERLOCK EMERG CLOSE FIRE DEPT OPEN 2 3 4 5 6 7 8 9 10 11 12 14 15 16 17 18 19 20 21 22 23 2...

Страница 73: ...LOSE 1 OPEN PARTIAL INTERLOCK OPEN TIME CLOCK OPEN FREE EXIT DETECTOR DISABLE EXIT DETECTOR DISABLE CLOSE TIMER INSIDE OBSTRUCTION VEHICLE DETECTOR OUTSIDE OBSTRUCTION VEHICLE DETECTOR SHADOW RESET VE...

Страница 74: ...Inputs 4 5 6 and 7 for external control devices DO NOT connect an external control device to Input Terminals 1 2 or 3 unless the controls are located in clear view of the entire gate area and are bein...

Страница 75: ...toring External Entrapment Protection Sensors on page 31 Connection to external entrapment protection sensors 18 DO NOT USE DO NOT USE 19 SENSOR 3 Photo Eye Close direction Refer to How Software Handl...

Страница 76: ...BSTRUCTION VEHICLE DETECTOR OUTSIDE OBSTRUCTION VEHICLE DETECTOR SHADOW RESET VEHICLE DETECTOR SENSOR 1 DO NOT USE DO NOT USE DO NOT USE CHARGER AC LOSS LOCK INTERLOCK EMERG CLOSE FIRE DEPT OPEN 2 3 4...

Страница 77: ...an be used as an interlock signal to another operator s interlock input or simply to indicate that the gate is secure The relay is off when the gate is closed The relay energizes when the fully closed...

Страница 78: ...etector output Interlocks an entry device to prevent pedestrian use This output is active whenever the Outside Obstruction Loop Detector is tripped Relay 1 2 or 3 13 Loitering Alert Indicates a vehicl...

Страница 79: ...ware detects a low battery voltage below 21VDC but greater than 18VDC for a duration of 2 seconds or more To slow battery drain accessory power loads are shed Relay 3 26 Free Exit Vehicle Detector Pul...

Страница 80: ...AY 4 LOGIC through RB RELAY 11 LOGIC can be accessed through the Installer Menu Set the number for the relay based on the information found in Table 7 Programmable User Relays Wire communication cable...

Страница 81: ...systems not dual gate systems Connecting an Interlocked Pair Dual Gate The Smart Touch Controller provides dual gate connections two swing gates run by two separate HydraSupply control units The STC...

Страница 82: ...CHARGER AC LOSS SPARE INPUT EMERG CLOSE FIRE DEPT OPEN 2 3 4 5 6 7 8 9 10 11 12 14 15 16 17 18 19 20 21 22 23 24 Smart Touch Controller LIMIT DUAL GATE RADIO OPTIONS DRIVE POWER RS485 MOTOR USER 1 USE...

Страница 83: ...to designate Sally Port A in the dual gate menu item as 3 DG 3 and Sally Port B as 4 DG 4 NOTE If using the Hy8Relay connect it to the dual gate spades on the Primary controller Programming a Dual Ga...

Страница 84: ...l information To connect a sequenced pair of gate operators follow the steps on the next page STOP BUTTON OPEN BUTTON CLOSE BUTTON REMOTE OPEN AND RADIO CONTROL OPEN CLOSE 1 OPEN PARTIAL INTERLOCK OPE...

Страница 85: ...ccessory Requirements To review the installation site requirements refer to Bi Parting Dual Gate Systems on page 67 SG 0 SEQUENTIAL GATE Status Display User Menu Installer Menu Sequence Gate Status Di...

Страница 86: ...gs A hydraulic splitter is used in twin HydraSwing models since only one HydraSupply controls two gates Gate Open ports Gate Close ports Conduit HydraSupply cabinet showing hose connections for Twin H...

Страница 87: ...ft minimum to 8 ft max Reset Loop can be offset from C L gate 1 to 5 ft 31 to 152 cm Dimension F 10 to 15 ft 3 to 3 6 m NOTICE For sequenced gates to operate properly all vehicle detectors must be wir...

Страница 88: ...Dimension A 6 to 16 ft minimum to 16 ft maximum 183 to 488 cm Dimension B 6 to 8 ft minimum to 4 ft maximum 91 to 122 cm Dimension C 3 ft minimum to 4 ft maximum Distance from edge of Reset Loop to C...

Страница 89: ...t down only after all vehicle detectors are clear and no other open command is present Mode 2 The close timer does not wait for vehicle detectors to clear but instead it starts counting down as soon a...

Страница 90: ...ly eliminates crosstalk and the need to set frequency levels Vehicle Counting Hy5B detects passenger vehicles and motorcycles Automatic Lightning Suppression Where lightning strikes occur often connec...

Страница 91: ...urated insulation Be sure to use wire with a direct burial jacket such as XLPE or XHHW wire Do NOT use THHN wire Check the Version of Software 1 In the field open the gate operator s Control Box 2 To...

Страница 92: ...EHICLE DETECTOR VEHICLE DETECTOR VEHICLE DETECTOR STOP BUZZER FREE EXIT INSIDE OBSTR OUTSIDE OBSTR SHADOW RESET WIEGAND HySecurity COM NO MX000585 VERSION S N RS232 DISPLAY VEHICLE DETECTOR COM COM A...

Страница 93: ...ate operator functions as if the Hy5B is triggered NOTE Best Practice When re tuning Hy5B vehicle detectors verify that the loops are clear before pressing the Reset button CAUTION Do not connect Free...

Страница 94: ...the area of the loop The lead in portion sealed in a saw cut does not need to be twisted so long as the wires are encapsulated in loop sealant and cannot move 24V AC Accessory power 24V DC COMMON VEH...

Страница 95: ...tion Dimension E 4 ft maximum 122 cm Vehicles must be able to pass from one loop to the next without loss of detection Dimension F Distance from gate to free exit loop is gate panel length plus 4 ft 1...

Страница 96: ...e of roadway No vehicle can pass through such a small area and escape detection Dimension E 4 ft maximum 122 cm Vehicles must be able to pass from one loop to the next without loss of detection Dimens...

Страница 97: ...the use of additional safety designs components It is up to the gate system designer and installer to assess appropriate safety design and components above and beyond minimum UL 325 and ASTM F2200 St...

Страница 98: ...eliable in inclement weather or low visibility provides convenience due to minimal wiring NOTE In an outdoor environment because of reduced performance avoid using a retro reflective sensor to span a...

Страница 99: ...Smart Touch Smart DC Controllers CAUTION All external entrapment protection sensors must be NC sensor outputs and wired to the SENSOR COM terminal for monitoring and powering purposes The sensor becom...

Страница 100: ...f the PVC conduit at a 45 degree angle to act as a drip shield Hold the reflector against the backside of the PVC conduit by attaching a 3 inch male connector DO NOT cement the connector as doing so m...

Страница 101: ...0 11 12 14 USER 3 Photo eye connections for Free Exit detection Photo eye connections for Inside Obstruction detection reversing loop Photo eye connections for Outside Obstruction detection reversing...

Страница 102: ...ice indicating the photo eyes are aligned set the next photo eye if the site has one and continue the process until all photo eyes are aligned 8 Press MENU to exit Menu Mode and return to Run Mode 9 M...

Страница 103: ...ss your gate site for the most appropriate placement of edge sensors Plan to integrate contact gate edge and non contact photo eyes sensors in your site plan Sensors are wired to the Controller and re...

Страница 104: ...nterface module with an NC output Miller Edge has marked UL 325 2016 compliant edge sensors with blue electrical tape on the output wire These edge sensors have a 10k resistor that connects to an inte...

Страница 105: ...me approximate installation date and service records of any recently performed maintenance work TIP On AC powered gate operators the active status of each input on the Smart Touch Controller is indica...

Страница 106: ...ead Battery DC BUSS 21V 3 chirps upon any operating command entry DC operators only Appears when the 24 VDC power drops too low disabling the operator which helps prevent damage to the batteries from...

Страница 107: ...3 EXCESS DRIFT Gate drift in transit Advisory only The alert appears and is being prevented from re opening Will self clear after an open or close input ALERT ALERT 4 THERMAL Overload 2 chirps per sec...

Страница 108: ...Y 2 chirps per second every 15 seconds Turn off AC power and replace the 3V coin battery that controls the internal clock Use a CR2032 coin battery ALERT ALERT 18 CHANGE BATTERY 1 chirp a minute Batte...

Страница 109: ...the accumulator While ALERT 27 appears on the display a renewed close command will attempt to run the barrier but the alert will not clear unless the close limit is reached or a reset is pressed ELD...

Страница 110: ...oftware version should be h4 50 or h5 50 or later If necessary update the software using a PC laptop and S T A R T ERROR ERROR 3 HY5 COMM ERROR 3 chirps per second once per minute One or more detector...

Страница 111: ...User Menu NOTE While you are viewing the event log the gate operator is in Menu mode and cannot run open or close 1 To enter the User Menu press the Menu key twice 2 Press Next and scroll until LG 0...

Страница 112: ...ps do not exist on battery operators 4 Verify the 24VAC is present at the Red and Green wires from the control transformer to the Power Supply Board by measuring the bottom of the power supply board a...

Страница 113: ...to L1 Black Trans Lead to L3 Green Red 24VDC COMMON 2 2K Blue White Blue HySecurity MX002440 Display Keypad Wiring Not Shown For Single Phase 1 T1 For 3 L1 and T3 L3 T1 L1 T2 L2 T3 L3 Transformer Powe...

Страница 114: ...e NOTE If the gate speed must be changed contact your HySecurity distributor or HySecurity Tech Support Extremely cold weather is unlikely to seriously affect the gate speed because HySecurity employs...

Страница 115: ...t be pushed If the power is three phase verify counter clockwise electric motor rotation To reverse rotational direction switch any two AC lines NOTE The VFD Motor Controller displays trip and fault c...

Страница 116: ...e panels from synchronizing PROBLEM 7 The gate panels move very slowly and seem to shudder throughout gate travel 1 Follow steps on page 23 Verify the Open Position and Hydraulic Hose Swap 2 Verify se...

Страница 117: ...er Laptop computer with Windows PC operating system XP Vista Win7 Win8 or Win 10 Minimum 128MB of RAM Minimum 5MB of hard drive disk space VGA graphics card minimum resolution of 800 x 600 Installing...

Страница 118: ...oard diagnostic tools Be sure to check the HySecurity website for the latest version of software and operator code before heading out for field maintenance Electrical Controls NOTICE Before servicing...

Страница 119: ...ore adding any fluid If fluid needs to be added 1 Move the gate so the cylinder is retracted 2 Remove the metal plug from the tank 3 Use HySecurity Uniflow hydraulic fluid part number MX000970 Gallon...

Страница 120: ...40 F and 158 F 40 C and 70 C The biodegradable fluid has a temperature rating between 10 F and 158 F 23 C and 70 C Brake Valve Adjustments WARNING The contents of the hydraulic cylinder are under pre...

Страница 121: ...lve on page 25 and follow the instructions For HySecurity Technical Support contact 800 321 9947 Open Valve The open valve is solenoid operate d and when energized directs the hydraulic flow to open t...

Страница 122: ...slow or erratic operation and will result in excess drive wheel wear Lubricate gate hardware more frequently and check for smooth operation by opening the toggle clamping mechanism and then pushing t...

Страница 123: ...l Box Visually look inside Control Box Check for worn wires Repair wires remove debris X Clock Battery Replace 7 X Motor Brushes DC Only Replace 8 X Special Notes 5 Fluid Level Check fluid level weekl...

Страница 124: ...110 MX3636 01 Rev D HydraSwing Programming Operations 2018 Page intentionally left blank...

Страница 125: ...USE CHARGER AC LOSS LOCK INTERLOCK EMERG CLOSE FIRE DEPT OPEN 2 3 4 5 6 7 8 9 10 11 12 14 15 16 17 18 19 20 21 22 23 24 Smart Touch Controller LIMIT DUAL GATE RADIO OPTIONS DRIVE POWER RS485 MOTOR USE...

Страница 126: ...u Mode Navigational Tips Press the Menu button twice to access Menu mode The gate will not run while in Menu mode The buttons on the display keypad perform certain functions while in Menu Mode Refer t...

Страница 127: ...y2NC NOTE Turn OFF AC power before connecting sensor wires to the Smart Touch Controller CAUTION Connect all contact and non contact sensors to same power source Example Do NOT connect photo eyes to 2...

Страница 128: ...Turn OFF power 2 Connect the Green NC relay wire from GEM 10 to Sensor 1 2 or 3 3 Connect Red Green wires from GEM 104 to SENSOR COM on Controller or Power Supply Board STC 4 Connect Red wire from GE...

Страница 129: ...Accessory power 24V DC EMX IRB MON Photo Eye Receiver EMX IRB MON Photo Eye Transmitter 24V 24V NC Relay COMMON NEG to SENSOR COM Jumper POWER INPUT 24V to COM COMMON NEG to SENSOR COM CAUTION Set DIP...

Страница 130: ...ct photo eye wiring NOTE Run a jumper between photo eye 24V and Relay COM C2 terminals See photo 3 Turn ON power 4 Access the Installer Menu and configure SENSOR setting according to the entrapment ar...

Страница 131: ...OBSTRUCTION VEHICLE DETECTOR SHADOW RESET VEHICLE DETECTOR SENSOR 1 SENSOR COM DO NOT USE SENSOR 2 DO NOT USE SENSOR 3 DO NOT USE CHARGER AC LOSS LOCK INTERLOCK EMERG CLOSE FIRE DEPT OPEN 2 3 4 5 6 7...

Страница 132: ...12 14 15 16 17 18 19 20 21 22 23 24 Smart Touch Controller LIMIT DUAL GATE RADIO OPTIONS DRIVE POWER RS485 MOTOR USER 1 USER 2 USER 3 VEHICLE DETECTOR VEHICLE DETECTOR VEHICLE DETECTOR STOP BUZZER FRE...

Страница 133: ...OM COM A B RPM COM OPEN S 1 24V 24V STATUS LED 24V AC Accessory power 24V DC COMMON Wireless Edge Link Receiver MGL RX20 Signal received from battery powered Transmitter MGL TX20 Connect either channe...

Страница 134: ...IONS DRIVE POWER RS485 MOTOR USER 1 USER 2 USER 3 VEHICLE DETECTOR VEHICLE DETECTOR VEHICLE DETECTOR STOP BUZZER FREE EXIT INSIDE OBSTR OUTSIDE OBSTR SHADOW RESET WIEGAND HySecurity COM NO MX000585 VE...

Страница 135: ...SENSOR COM Sensor wire P NC can attach to any SENSOR input MGL RX20 24V NOTE DIP switches must be set as shown otherwise the photo eye will not operate correctly CAUTION Set DIP Switches 1 OFF 2 OFF...

Страница 136: ...122 MX3636 01 Rev D HydraSwing Programming Operations 2018...

Страница 137: ...fire terrorism or war or 3 damaged through improper operation maintenance storage or abnormal or extraordinary use or abuse Any modification made to products will void the warranty unless the modific...

Страница 138: ...HyInverter HydraSwing 150 with HyInverter Actual open close time dependent on gate weight length percentage of open area on panel and anticipated wind speed The operator s normal duty cycle and the a...

Отзывы: