ML-IoT/C and /N Operation Manual © Copyright
Page -
18
Issue 1.2 28 Jun, 2021
3.7
New Password
SDI-12 Terminal
Allows individual commands to be formed and sent
to the SDI-12 sensors. This is useful for :
- Checking the address of the sensor connected
using the ?! command – note this should only be
used when a single sensor is connected as all
sensors will respond with their address.
- Checking the actual sensors connected at each
address using the I command – eg. 1I! as shown in
this example.
- Changing the address of the sensor using the A
command – eg. 0A1! To change the SDI-12 address
from 0 to 1
- Doing SDI-12 sensor configuration or calibration
changes.
NOTE:
In recent F/W versions the 12V Boost
power will remain on – as indicated in the red note.
The
default
Administrator Password when the ML-
IoT is first powered on is “
admin
”.
This should be changed here as soon as possible.
The password should be 4 to 8 characters long.
It is case sensitive.
Alpha, numeric and special characters can be used.
Enter the same password twice for it to be accepted.
NOTE :
Touch on the checkbox after the password
to view the password entered.
----------------------------------------------------------------
Entering the password **** is a special case and
disables the password access.
Do not leave the ML-IoT in this state when deployed.