SS-IOM (05/14)
Page 4
Installation
1. Before installling the Sure-Start on the EarthLinked® Compressor Unit, turn all power to the
system OFF.
2. Remove the approporate compressor unit cabinet panels to access the electric box.
3. Prior to installation of the Sure-Start, be sure all start capacitors, start relays, hard start (start
assist) and/or other related devices are removed.
4.
Install the Sure-Start module mounting bracket as shown in Figure 3. The mounting bracket is
to be fastened to the outside of the electric box with two self-tapping screws.
BE SURE NOT
TO DRILL INTO ELECTRICAL COMPONENTS INSIDE THE ELECTRIC BOX. REMOVE ALL
METAL SHAVINGS.
Figure 3. Mounting Bracket Installation
5. Wire as shown in Figure 4 and Figure 5, as appropriate. All wiring to and from the components
inside the electric box can be channeled through an access hole in the bottom of the electric
box.
6.
Wiring is field supplied
. All field wiring shall be rated at 167°F (75°C). Wire gage shall be as
follows:
a. 8 to 12 AWG Cu, stranded, for terminals [Run Winding (R) and active T2]
b. 12 to 16 AWG Cu, stranded, for terminals [Run Capacitor (RC), Start Winding (S)
and Compressor/Motor Common (C)]
IMPORTANT!
DO NOT SWAP THE RUN AND START WINDINGS!
BE SURE THE CONNECTOR TERMINATIONS ARE TIGHT!