Page 77
Water leaks from
steam cylinder
upper part
•
Hose clamps on steam and/or conden-
sate hose not tightened
•
Tighten clamps
•
Steam hose adapter not properly fit or
o-ring not replaced
•
Replace O-ring (if required) and
ensure proper adapter installa-
tion
No steam produc-
tion despite the
steam humidifier
being switched
on. Display not
illuminated.
•
•
•
Defective F1 and/or F2 fuses (1.6 A each)
L3 phase failure (ext. circuit breaker has
tripped or is defective)
device load circuit breaker has tripped
•
•
•
Check micro fuses and replace,
if required
Replace breaker and investi-
gate possible causes
Switch on breaker. If problem
persists, check for reason
Blow-down pump
works but not wa-
ter is drained
•
Steam cylinder and/or drainage system
blocked
•
Clean cylinder base and/or
drainage system, respectively
Cylinder is fully
drained after par-
tial blow-down
despite switched-
off pump
•
Vent pipe is blocked
•
Clean venting bore or replace
vent pipe adapter
No steam exit
from steam mani-
fold
Water exits peri-
odically from
drain hose with-
out pump
switched on
•
•
Steam pipe improperly laid (water bag).
Excess pressure in duct system (max.
overpressure is 1200 Pa/.17 psi)
•
•
Rerun steam hose according to
guide lines
Consult your expert dealer if
problem persists
Problem
Possible cause for faulty situation
Counter measure
Содержание StandardLine Series
Страница 16: ...Seite 16 Device connections cable entries waste water connection water inlet steam outlet device front...
Страница 78: ...Page 78 13 Declaration of conformity...
Страница 82: ...Page 82 This page intentionally left blank...
Страница 83: ...Page 83 This page intentionally left blank...
Страница 85: ...Page 85 17 View of housing 70 56 57...