G7
Hysteresis Temp.
max
0 - 10 K
factory setting =
10 K
determines t he t emperature threshold f or t he
„Temp. max“ alarm based on (G2 + G7)
Steam bath/
Temperature/
Hysteresis
Temp. Max
G8
Follow-on time
0 - 255 min
factory setting =
0 min
additional supply fan operating time for drying
of the steam cabin
Steam bath/
Fans/Follow-on
time
G13
Hysteresis supply
fan
0 - 10 K
factory setting =
1 K
the supply fan is powered until the steam bath
temperature r eaches ( G2 + G13), with
G2 =
steam ba th
°C t emperature se t value
an d
G13 = hys teresis supply fan.
Be yond th at
temperature the fan remains off
Steam bath/
Fans/Supply
fan/Hysteresis
H1/
H11
Partial blow-down 0 - 255
0 - 999 kg
number of filling cycles before partial blow-
down is initiated (electrode humidifier only)
amount of steam produced before partial blow-
down is initiated (heater humidifier)
Operator menu/
Blow-down/Par-
tial blow-down
counter
H2/12 Partial blow-down
time
1 - 255 s
pump operating time during partial blow-down
(applies to both types of humidifiers)
Operator menu/
Blow-down/Par-
tial blow-down
time
H7/
H17
Full blow-down
counter
0 - 9999 (ELDB)
0 - 9999 kg
(HKDB)
number of filling cycles before full blow-down is
initiated (electrode humidifier only)
amount of steam produced before full blow-
down is initiated (heater humidifier)
Operator menu/
Blow-down/Fulll
blow-down
counter
H8/
H18
Full blow-down
time
0 - 999 s
0 - 255 s
pump operating time during full blow-down
(applies to both types of humidifiers)
Operator menu/
Blow-down/Fulll
blow-down time
H10
Steam-down time 0 - 9999 min
(HKDB)
steam-down time as a criterion for the correct
operation of a heater steam humidifier (HKDB).
Within the time set a defined level variation of
the cylinder filling must be observable
Operator menu/
Blow-down/
Steam-down
time
L0
Amount of steam
produced
Reading
reading
[t]
Operator menu/
Service
L1
Power output
Reading
reading [kg/h]
Operator menu/
Service
L2
Current drawn
Reading
reading [A]
Operator menu/
Service
L3
Control signal
Reading
reading [%]
Operator menu/
Service
L4
Demand
Reading
reading [%]
Operator menu/
Service
L5
Output limitation Reading
reading [%]
Operator menu/
Service
Para-
meter
Designation
Range
Description of parameter
Menu/Sub-
menü