HygroMatik Spa Touch Control Скачать руководство пользователя страница 31

                                                                                                                    

SPA

                                                                                                                                               Page 31

G7

Hysteresis Temp. 

max

0 - 10 K
factory setting = 

10 K

determines t he t emperature  threshold f or t he

„Temp. max“ alarm based on  (G2 + G7) 

Steam bath/

Temperature/

Hysteresis 

Temp. Max

G8

Follow-on time

0 - 255 min
factory setting = 

0 min

additional supply fan operating time  for drying

of the steam cabin

Steam bath/

Fans/Follow-on 

time

G13

Hysteresis supply 

fan

0 - 10 K
factory setting = 

1 K

the supply fan is powered until the steam bath

temperature r eaches ( G2  +  G13), with 

G2 =

steam ba th

 

°C t emperature se t  value

 an d

G13 = hys teresis  supply  fan.

 Be yond th at

temperature the fan remains off

Steam bath/

Fans/Supply 

fan/Hysteresis

H1/

H11

Partial blow-down 0 - 255

0 - 999 kg

number of filling cycles before partial blow-

down is initiated (electrode humidifier only)

amount of steam produced before partial blow-

down is initiated (heater humidifier)

Operator menu/

Blow-down/Par-

tial blow-down 

counter

H2/12 Partial blow-down 

time

1 - 255 s

pump operating time during partial blow-down 

(applies to both types of humidifiers)

Operator menu/

Blow-down/Par-

tial blow-down 

time

H7/

H17

Full blow-down 

counter

0 - 9999 (ELDB)

0 - 9999 kg 

(HKDB)

number of filling cycles before full blow-down is 

initiated (electrode humidifier only)

amount of steam produced before full blow-

down is initiated (heater humidifier)

Operator menu/

Blow-down/Fulll 

blow-down 

counter

H8/

H18

Full blow-down 

time

0 - 999 s 
0 - 255 s 

pump operating time during full blow-down 

(applies to both types of humidifiers)

Operator menu/

Blow-down/Fulll 

blow-down time

H10

Steam-down time 0 - 9999 min 

(HKDB)

steam-down time as a criterion for the correct 

operation of a heater steam humidifier (HKDB).  

Within the time set a defined level variation of 

the cylinder filling must be observable

Operator menu/

Blow-down/

Steam-down 

time

L0

Amount of steam 

produced

Reading

reading

 

[t]

Operator menu/

Service

L1

Power output

Reading

reading [kg/h]

Operator menu/

Service

L2

Current drawn

Reading

reading [A]

Operator menu/

Service

L3

Control signal

Reading

reading  [%]

Operator menu/

Service

L4

Demand

Reading

reading  [%]

Operator menu/

Service

L5

Output limitation Reading

reading [%]

Operator menu/

Service

Para-

meter

Designation

Range

Description of parameter

Menu/Sub-

menü

Содержание Spa Touch Control

Страница 1: ...SPA Manual Spa Remote Touch READ AND SAVE THESE INSTRUCTIONS SPART ENo SPART EN...

Страница 2: ...11 2014 SPART EN All Rights reserved HygroMatik GmbH grants the legal user of this product or device the right to use the Work s solely within the scope of the legitimate operation of the product or...

Страница 3: ...9 3 3 Quick Access Functions Overview 10 4 Operating the Spa Remote Touch on User and Operator Levels 11 4 1 Accessing the Main Menu 11 4 2 Overview on Submenus 11 4 3 Access to Operator Level 12 4 4...

Страница 4: ...cs Terms used with graphics or drawings 1 2 Documentation Scope of Supply HygroMatic steam ge nerators a re always a ccompanied by two operating manuals one for the unit itself and one for the control...

Страница 5: ...atic discharges In order to safeguard these components during installation and servicing steps must be taken to protect against ESD Reminder Materials and c onsumables must be handled and or dis posed...

Страница 6: ...ust be p rovided in th e ro om to e nsure closur e of the h umidifier s water supply in the event of a leak Electrical Work on the electrical system must be performed by qualified person nel Disconnec...

Страница 7: ...e cradle the Spa Remote Touch can be run for up to thr ee hours on the b atteries inegrated in the remote control The charging cradle is per man antly connected to the steam generator through a commun...

Страница 8: ...quently used functions Menu Enable steam production Essence injection Timer function ECO function Light function Symbol Status Description perma nently on preset Timer mode is activated blinking steam...

Страница 9: ...ith water white Ready for Use the safety chain clamp 1 2 is open the device is not enabled for steam production dark blue ECO device operates in ECO mode orange No Demand the requirement is below the...

Страница 10: ...timer mode Hourly daily or weekly timer functions can be set on operator level Menu function Tapping on the key MENU takes youto the main menu with the submenus Steam bath Timer ECO Device configurat...

Страница 11: ...l temperature and switching the essence dosing on and off From guest lev el t he re turn to us er lev el r equires a 5 ch aracter n umeric password that can be set on operator level Note The fu nction...

Страница 12: ...ser level as shown by the User indication in white in the appropri ate display field After typing in 010 as an access code the character colour changes to grey Instead of Password entry Operator is di...

Страница 13: ...SPA Page 13 4 4 Menu Scheme...

Страница 14: ...essence submenu and select On Intensity Select Intensity to set the intensity of the essence The intensity grade selected is shown in a 11 stage diagram Touch the diagram in order to change the intens...

Страница 15: ...rating the Error C Max alarm message Select Hysteresis Temp max this parameter determines at which temperature with respect to the temperature set value steam generation is cut and the alarm Error C...

Страница 16: ...an for permanent operation Quit the menu with Changing the switch off temperature hysteresis of the fan Select Automatic Select Hysteresis to set the temperature hysteresis set temperature minus hyste...

Страница 17: ...timer function Quit the menu with 4 4 2 3 Modes The following timer modes are available Hourly Daily Weekly Setting of the relevant times ca n be made in Settings The program selected is shown in the...

Страница 18: ...ng allows for the definiti on of th e stea m p roduction pe riod After timer start the remaining period is displayed in the button field Steam production period Select Steam production period after pr...

Страница 19: ...reselection of Weekly program Type in the times for start and stop of steam production Confirm by pressing OK or discard by using the ESC button Quit the menu with 4 4 3 ECO Mode The steam generator s...

Страница 20: ...point temperature lower than the standard value Please note Standby Heating and temperature preservation can not be active at the same time Selection of the ECO function intended Select ECO Settings...

Страница 21: ...el also provides expanded access to all parameters Only password entry activates the operator level If there has not been an entry for a period of 15 minutes control automatically switches back to use...

Страница 22: ...hile the charging cradle is connected to the turned on steam generator In the next step the charging cradle must be prepared To do so the two pins on jumper JP1 on the board of the charging cradle hav...

Страница 23: ...correct password is typed in The password set is dis played in the Set password button field The submenu allows for the following actions Activate Set password Activate guest mode Select Activate ente...

Страница 24: ...4 7 Name Plate The nameplate holds the following information concerning the steam humidifier connected Serial number Software version of control unit Year of production Deutsch English Fran ais ESpa...

Страница 25: ...arameters Select Mode of operation Use arrows to select 1 step or PI controller Confirm by pressing OK or discard the input using the ESC button Quit the menu with 4 4 8 2 Service In this submenu the...

Страница 26: ...ng criteria have to be considered for the start of the blow down o peration device type recognition is automatic b y the r emote control Additionally and not depending on the type of humidifier stand...

Страница 27: ...blow down is initiated Partial full blow down These parameters define the operating time of the pump in s during blow down with respect to the mode chosen Setting up of partial blow down counter Selec...

Страница 28: ...t using ESC but ton Quit the menu with Setting up of full blow down time Select Operator menu Select blow down Select full blow down time Type in a value in the range from 0 255 s for heater humidi fi...

Страница 29: ...parameter C16 and so on Standby heating is only operational in ECO mode when A17 on On A17 off tempera ture preservation is operational i e the steam bath temperature is held on a lower set value as d...

Страница 30: ...e set value and G1 Hys teresis 1 step controller Example G2 is set to 45 C and G1 is set to 1K t The s team generator will be switched of at 46 C and will be switched on again at 45 C Steam bath tempe...

Страница 31: ...oth types of humidifiers Operator menu Blow down Par tial blow down time H7 H17 Full blow down counter 0 9999 ELDB 0 9999 kg HKDB number of filling cycles before full blow down is initiated electrode...

Страница 32: ...eplate S4 Unit type Reading automatically read Main menu Nameplate S5 Year of produc tion Reading automatically read Main menu Nameplate S6 Serial number Reading automatically read Main menu Nameplate...

Страница 33: ...ctronics is ma de through a st andard RJ45 p atch cable to be pro vided by the customer The photos below show the cabling on the bot tom side of the control unit housing and inside the charging cradle...

Страница 34: ...Page 34 The pho tos below sho w the inter nal cab ling of the contro l un it for connecting the Spa Remote Touch charging cradle Internal cabling of control unit Internal cabling of control unit deta...

Страница 35: ...O HLFKQXQJ 1U HQHQQXQJ DWHL 63 7RXFK 5HPRWH 6 6 520 7 LVH 0HLWQHU 6WU HQVWHGW 8O EXUJ HUPDQ 7HOHID 3KRQH bQGHUXQJ DWXP 1DPH HDUE HSU 1RUP DWXP XVW D UHLJDEH XH 5W 237 21 9RUEHUHLWXQJ 63 7RXFK 5HPRWH 2...

Страница 36: ......

Отзывы: