SPA
Page 30
E1
Xp-PI controller
0.1 - 100 %
factory setting =
5 %
gain of PI contoller (Xp=100/E1)
(only relevant when U6 = „PI controller“)
Operator menu/
Operating para-
meters/XP
E2
Tn-PI controller
0 -255 sec
factory setting =
60 sec
integral time of PI controller
(only relevant when U6 = „PI controller“)
Operator menu/
Operating
parameters/TN
E11
ECO temperature 0 - 49 °C
factory setting =
35 °C
determines th e set va lue of the s team b ath
temperature whe n ECO mod e „ Temperature
preservation“ is selected
ECO/Eco set-
tings/Tempera-
ture preser-
vation
E14
Intensity
11-stage bar dia-
gram
each bar corresponds to a certain combination
of injection time and in terval t ime. W hile the
middle position bar (bar 6) reflects the settings
of in jection time an d inter val time directly, the
intensity correlated with the other bars results
from scaling up and down, resp. .
Steam bath/
Essence/Inten-
sity
G1
Hysteresis 1-step
controller
0 -10 K
factory setting =
1K
This parameter allows for determing the switch-
on/switch-off dif ferential temperature of the
temperature contr oller. A sing le-heater ste am
generator is s witched-off at a t emperature
resulting from
(G2 + G1)
, with
G2 = st eam
bath
°C temperature set value
and
G1 = Hys-
teresis 1-step controller.
Example:
G2 is set to 45°C and G1 is set to 1K
t. The s team generator will be switched of at
46° C and will be switched on again at 45 °C.
Steam bath/
temperature/
Hysteresis
temp.
G2
Steam bath °C
set value
0 - 49 °C
factory setting =
45 °C
determines steam bath temperature set value.
The setting is preserved on power-down of the
steam generator.
Steam bath/
temperature/Set
value tempera-
ture
G3
Hysteresis
exhaust fan
0 -10 K
factory setting =
1K
determines the of f-switching po int of the
exhaust fan. Th e fan is switched -off when the
steam bath temperature falls equals (G2 -G3),
with
G 2 = st eam b ath
°C t emperature s et
value
and
G3 = hysteresis exhaust fan.
Example:
G2 is set to 45 °C and G3 is set to 2
Kt.The fan will be switched-off at 43° C.
Steam bath/
Fans/Exhaust
fan
G4
Injection time
0 - 25 sec
factory setting =
2 sec
determines the d uration o f esse nce injection
when D2 = on
Steam bath/
Essence/Inten-
sity/Injection
time
G5
Interval time
0 - 99 min
factory setting =
5 min
determines the p ause be tween 2 essence
injections when D2 = on
Steam bath/
Essence/Inten-
sity/Pause time
G6
Essence hystere-
sis
0 - 25K
factory setting =
5K
determines the start point of essence injection
with re spect to the temperature set va lue
based on (G7 - G6)
Steam bath/
Esssence/Hys-
teresis
Para-
meter
Designation
Range
Description of parameter
Menu/Sub-
menü