Page 32
5.10 Steam Solenoid Valves
When humidifying a number of loads, which are to be controlled
separately, using a single steam humidifier, steam solenoid
valves can be included in the steam hoses. Valve control has to
provided by the customer.
•
Install the vertical risers with flow from bottom to top.
•
The best position is just above the steam humidifier.
Installation of Steam Solenoid Valve
5.11 Unit Installation Check
Attention:
This unit may only be operated by qualified and prop-
erly trained personnel.
Please check the installation using the following list:
;
Does unit hang vertically?
;
Are wall distances to the unit within the range
;
Does steam hose have a slope of 5-10%?
;
Is condensate hose installed with a loop of min. 200
mm?
;
Is steam manifold positioned correctly? Are all bolts and
clamps tightened?