Page 14
The concentration of dissolved salts increases over time, which
can lead to a rise in the conductivity of the water. If this contin-
ues, conductivity may increase until a short circuit occurs. This
could damage the unit, but in any case would significantly
reduce the life span of the electrodes.
For this reason, regular, periodic blow-downs of some of the
concentrated water are very important. Following this procedure
as recommended provides stable cylinder water conductivity as
well as minimal water loss for the expected service life of the cyl-
inder.
Water blow-down is performed by a blow-down pump (32). The
functioning of the blow-down pump is continuously monitored
during operation. If the pump is damaged, the steam humidifier
shuts down.
With normal water quality, the blow-down loss rate is between
7% and 15% of the amount of steam produced. The steam cylin-
der requires complete drainage every 3-8 days, regardless of
the water quality.
Mineral deposits settle in the open area below the electrodes
and are removed through periodic maintenance. The blow-down
pump itself has wide openings and can flush out smaller pieces
of mineral deposit. This extends the service life of the unit and
reduces the required maintenance interval.
During blow-downs, water flows from the pump into the drainage
system.
A sensor electrode (10) monitors the maximum
water capacity
of the cylinder. When the water level reaches the sensor elec-
trode, the water supply is interrupted. This can occur when the
water has low conductivity or when the electrodes are worn out.
In the case of low water conductivity, however, this state usually
lasts only a short time. The built-in control and the large area
electrodes combine to produce a rapid rise in conductivity by
increasing the concentration of the water.
The steam cylinder consists of a top (16) and lower (19) part
joined with a cylinder flange. The seal between the cylinder and
cylinder base (37), as well as between the top and lower part of
the cylinder, is maintained using an o-ring (35+17).
Содержание CompactLine
Страница 1: ...Electrode Steam Humidifier Manual IMPORTANT READ AND SAVE THESE INSTRUCTIONS...
Страница 29: ...Page 29 5 7 2 Drill Pattern DN40 not to scale Note Due to variable print media the dimensions are not to scale...
Страница 46: ...Page 46...
Страница 56: ...Page 56 10 EC Declaration of Conformity...
Страница 64: ...Page 64 14 Exploded View...
Страница 65: ...Page 65 15 View of housing...