• Refit the lid to the back box, using the supplied screws.
• Put the QR code available in the box either on the system
map or on the dedicated pages at the end of translator
or expander manual.
6
5
+
Unsupervised relay
switch output
WIRING EXAMPLE FOR THE RELAY SWITCH OUTPUT
• Ensure the device connected to the unit is not drawing
more than 2 A at 30V (no 220 VAC). Drawing too much
current through the output relay or connecting mains
voltage could possibly damage the unit and void warranty.
Note: install a properly fire rated cable (according
to national code of practice) between the third-party
device and the output module.
R
EOL
Supervised relay switch
output (needs polarised load)
V
EXTERNAL
DEVICE
- +
- +
- +
- +
port B input
port A output
power supply
V
+
External
device
R
EOL
WIRING EXAMPLE FOR 100MA/12 VDC OR 50 MA/24
VDC EXTERNAL DEVICE DRIVING CAPABILITY
• The 10K
Ω
R resistor monitors whether the cable
has been damaged or the connection is no longer available.
• If you fail to install these resistors correctly the device will
not operate as intended.
- +
- +
R
EOL
R
EOL
10 K
Ω
external
device
- +
- +
EOL
R
EOL
10 K
Ω
TAU-MO-SB-01
HYFIRE TAURUS OUTPUT MODULE
QUICK START GUIDE
Unit B12a, Holly Farm Business Park, Honiley, Warwickshire, CV8 1NP
T: +44 (0)1926 485282, E: [email protected], W: www.hyfirewireless.com