Hyfire Wireless Fire Solutions Limited 

-

 Unit B12a, Holly Farm Business Park, Honiley, 

 

Warwickshire, CV8 1NP 

-

 United Kingdom

 

www.hyfirewireless.com

 

[email protected]

 

L20

-

VMICX

-

1400 (vA.1Q)

 

 

THE SUPERVISED OUTPUT CHANNEL AND ITS WIRING

 

 

This channel (picture 12) provides control of external, loop

-

unrelated auxiliary devices such 

as fire shutters; it performs two main functions:

 

 

a) supervises the connection to the controlled external load through an 

end of line

” 

resistor 

(R

EOL

)

 

 

b) supervises the presence of an external power supply for the output.

 

 

The purpose of the supervision functionality of this channel is to distinguish between the 

following conditions:

 

 

a) Normal condition.

 

 

b) Short circuit fault condition on the load

loop

”.

 

 

c) Open circuit fault condition on the load

loop

”.

 

 

d) External power supply shortage fault condition; this can be caused by a short or open 

circuit on the power supply 

loop

”, 

or by the V

EXT

 value under a certain threshold. 

 

 

 

 

 

 

 

 

 

 

THE FORM C OUTPUT CHANNEL AND ITS WIRING

 

 

This output channel provides relay

s double pole contacts changeover for the 

control of auxiliary devices (picture 13 illustrates a wiring example). This non

-

supervised form C output is controlled and can be switched over by the 

control panel.

 

 

This channel type is characterized by 3 terminals:

 

 

a) C: 

common

” 

terminal

 

 

b) NC: 

normally closed

” 

terminal

 

 

c) NO: 

normally open

” 

terminal

 

 

By default, C is switched over the NC terminal; when activated, C is switched 

over the NO terminal.

 

 

Please note that due to the non supervised nature of this output, only techno-

logic devices can be connected to it (fire shutters hold / release devices and 

so on).

 

 

 

 

 

 

 

 

 

TESTING

 

 

In order to try out the functionality of the installed multi

-

module, the following tests must be performed:

 

 

All active output channels 

-

 alarm test:

 trigger an alarm condition on the control panel (by a call

-

point or sensor in the installed system): 

the control panel will activate or switch

-

over the multi

-

module

s output (or outputs).

 

 

All active input channels 

-

 alarm test:

 activate the external device: the control panel must trigger a system alarm.

 

 

All active supervised input and output channels 

-

 fault tests:

 generate open and short circuit conditions on the supervised channel

loops: the control panel must signal one or more fault conditions.

 

 

After each test the device must be reset by the specific command on the control panel (see the RESET paragraph). 

 

 

All devices must be tested after installation and, successively, on a periodic basis.

 

 

RESET

 

 

To reset the multi

-

module from an alarmed or a fault condition, it is necessary to:

 

 

1) solve the cause of the abnormal condition

 

 

2) reset the system from the control panel.

 

Picture 13 

-

 form C output channel

s wiring

 

NO

 

C

 

NC

 

LOAD

 

LOAD

 

Output channel

 

Picture 12 

-

 supervised output channel

s wiring

 

External power (

-

)

 

External power (+)

 

Channel

s output (

-

)

 

Channel

s output (+)

 

R

EOL

 

V

EXT

 

+

 

LOAD

 

Diode

 

 