background image

4  

Specifications 

Before Starting Installation 

Tools, Pipe, and Fittings, Other Materials

 

• 

Pliers 

• 

Screwdriver 

• 

Teflon tape 

• 

Razor knife 

• 

Two adjustable wrenches 

• 

Additional tools may be required if modification to home 
plumbing is required. 

• 

Plastic inlet and outlet fittings are included with the sof-
tener.    To  maintain  full  valve  flow,  3/4”  or  1”  pipes  to 
and  from  the  softener  fittings  are  recommended.  You 

should  maintain  the  same,  or  larger,  pipe  size  as  the 
water supply pipe, up to the softener inlet and outlet. 

• 

Use copper, brass, or PEX pipe and fittings. 

• 

Some codes may also allow PVC plastic pipe. 

• 

ALWAYS  install  the  included  bypass  valve,  or  3  shut-off 
valves.  Bypass  valves  let  you  turn  off  water  to  the  sof-
tener  for  repairs  if  needed,  but  still  have  water  in  the 

house pipes. 

• 

5/8” OD drain line  is needed  for the valve drain.  A 10’ 
length of hose is included. with some models. 

• 

A  length  of  5/8”  OD  drain  line  tubing  is  needed  for  the 
brine tank over flow fitting (optional). 

• 

Nugget or pellet water softener salt is needed to fill the 
cabinet or brine tank. 

• 

Continuous operation at flow rates greater than the service flow rate may affect capacity and efficiency performance. 

• 

The manufacturer reserves the right to make product improvements which may  deviate  from the  specifications  and 
descriptions stated herein, without obligation to change previously manufactured products or to note the change. 

 

These softeners conform to NSF/ANSI 44  for the specific performance claims as verified and substantiated by test data.  
These models are efficiency rated.  The efficiency rating is valid only at the stated salt dose and maximum service flow 

rate.  They have  a demand initiated regeneration (D.I.R.) feature  that complies with  specific performance  specifications 
intended to minimize the amount of regenerant brine and water used  in their operation.  These  softeners have a rated 

softener efficiency of not less than 3350 grains of total hardness exchange per pound of salt (based on sodium chloride) 
and shall not deliver more salt than their listed ratings.  The rated salt efficiency is measured by laboratory tests described 

in NSF/ANSI Standard 44.  These tests represent the maximum possible efficiency that the systems can achieve.  Opera-
tional efficiency is the actual efficiency after the system has been installed.  It is typically less than the efficiency due to 

individual  application  factors  including  water  hardness,  water  usage,  and  other  contaminants  that  reduce  the  softener’s 
capacity.  These systems are not intended for use with water that is microbiologically unsafe or of unknown quality without 

adequate  disinfection  before  or  after  the  system.    For  best  results,  use  plain,  white  block  salt.    Refer  to  Installation/
operation manual and warranty for further details on installation, parts and service, maintenance and further restrictions or 

limitations to the use of the product. 

Содержание 15100300

Страница 1: ...applying provided with install kit NSF cer ed lubri cant to all seals 3 This system is not intended for trea ng water that is microbiologically unsafe or of unknown quality without adequate disinfec o...

Страница 2: ...treating water that is microbiologi cally unsafe or of unknown quality without adequate disinfection before or after the system For your safety the information in this manual must be followed to mini...

Страница 3: ...ces Use only lead free solder and flux for all sweat solder connections as required by state and federal codes Maximum allowable inlet water pressure is 125 psi If daytime pressure is over 80 psi nigh...

Страница 4: ...viously manufactured products or to note the change These softeners conform to NSF ANSI 44 for the specific performance claims as verified and substantiated by test data These models are efficiency ra...

Страница 5: ...ot covered by the war ranty Put the softener in a place water damage is least likely to occur if a leak develops The manufacturer will not repair or pay for water damage A 120 volt electric outlet to...

Страница 6: ...his could cause damage to the valve 5 Connect the drain hose 10 ft included to the valve and secure it with a hose clamp also included Run the drain hose to the nearest laundry tub or drain pipe This...

Страница 7: ...7 Installation...

Страница 8: ...or the full amount of time as dis played on the screen to insure a proper brine solution for the next regeneration 7 The valve will automatically advance to the SERVICE position Open the outlet valve...

Страница 9: ...daily use and the reserve ca pacity of the system SALT SETTING There are 3 settings to choose in the MENU SET TINGS These settings will determine the salt dosage and capacity for the system For SIM un...

Страница 10: ...ll pause on the Date and Time page for 5 seconds Then it will continually scroll through all of the system diagnostic display pages Depending on the Valve Type some pages will not be dis played To man...

Страница 11: ...metime during the night and manual regenerations should be performed when little or no water will be used in the household Normal regeneration time is 2 00 AM When the system capacity is near exhauste...

Страница 12: ...Use only crystal water softener salt Check the salt level monthly It is important to main tain the salt level above the water level To add salt simply lift the salt lid and add the salt directly into...

Страница 13: ...ontrol valve body 3 Carefully remove the assembly and disassemble as shown in above figure 4 The injector orifice is removed from the valve body by carefully turning it out with a large screwdriver Re...

Страница 14: ...t the BLFC holder apart and remove the flow washer 4 Reassemble using the reverse procedure TIP Markings on the BLFC washer should face the direction as shown here Replacing Drain Line Flow Control DL...

Страница 15: ...a to form or grow However during shipping storage installing and operating bac teria could get into the softener For this reason sanitizing as follows is suggested when in stalling Sani System Liquid...

Страница 16: ...16 Brine Tank Res Up Feeder Assembly Step 3 Install brine well Feed wick from feeder into the opening in the brine well cap...

Страница 17: ...17 Main Repair Parts Connectors A A A B D F E A C...

Страница 18: ...STON ASSEMBLY 60010035 INJECTOR SET 00 VIOLET 60010130 85HE SEAL SPACER KIT 60010034 INJECTOR SET 0 RED 60010131 85HE DLFC 1 1 5 GPM 60010033 INJECTOR SET 1 WHITE 60010132 85HE DLFC 2 2 0 GPM 60010032...

Страница 19: ...19 Control Valve Parts List...

Страница 20: ...20 Power Head Exploded View...

Страница 21: ...21 Power Head Parts List...

Страница 22: ...22 Trouble Shooting...

Страница 23: ...anature WaterGroup will provide a replacement mineral tank or brine tank to any original equipment purchaser in possession of a tank that fails provided that the water conditioner is at all times oper...

Отзывы: