Hydromatic SK75 Скачать руководство пользователя страница 5

5

Attach one meter lead to the
white cord wire and the other
meter lead to the black cord
wire. See Winding Resistance
Chart for an appropriate 
resistance reading. Repeat this
procedure for the black cord
wire and red lead wire. This
reading is the start winding
resistance. Also repeat this
procedure for the white cord
wire and the red cord wire.
This reading is the total motor
winding resistance. If no 
resistance is obtainable for
either the start or main 
winding, either there is a bad
connection or the winding 
is defective.

4. For three phase models, remove

hex head cap screws (8) and lift
off motor dome (25). Prop the
motor dome (25) so as to not
pull and make taut the motor
connection leads. Remove motor
connections (26) from motor
(7) and remove power cord (27)
from pump.

5. Twist the three leads of one

end of the power cord together.
Then at the other end, with an
ohmmeter, check any two
leads. Check the third lead
with either of the first two. If 
a zero reading is indicated 
for any wire, the wire is 
broken and a new power cord 
assembly must be ordered.

6. Set ohmmeter scale pointer to

R X 100K scale. Connect one
meter lead to one lead of the
stator and touch the other
meter lead to the motor 
housing (25). If the resistance
to the ground is less than
500,000 ohms, there is 
moisture in the winding or
leakage through stator 
insulation. The stator must be
dried out and then rechecked
on the ohmmeter. If the 
resistance is still less than
500,000 ohms after drying, the

stator must be replaced. A zero
reading indicates a direct short,
and the stator will have to 
be replaced.

7. If the wiring is grounded,

remove the pipe plug (3) in the
top of the pump and drain the
oil into a glass container. A
milky appearance to the oil
will indicate that water has
entered through and worn or 
damaged seals or O-rings. If
this is the case, the mechanical
seals and all O-rings will have
to be replaced. If no apparent
moisture is seen, the stator
must be checked with a high
pot tester. Using a voltage of
1500 volts for 115 volt motors
and 2000 volts for 230 volt
motors, touch one probe to the
white lead and the other probe
to the stator laminations for
only one second. Buzzing will
indicate arcing is occurring at 
a breakdown of insulation or 
a small amount of moisture 
is present. The stator will 
then have to be dried out 
or replaced.

The high pot test is very 
destructive. So, each time the
same stator is checked, the
voltage should be lowered
about 250 volts. If not, 
you may cause the stator 
to short by breaking down 
the insulation.

Caution: Due to the high 
voltage, use extreme care when
using the high pot tester. A
dangerous shock can be avoided
with careful handling of the 
test probes.

8. Repeat step 3, this time 

attaching the meter leads to the
stator wires. If a zero reading is
obtained, the winding is 
defective and the stator must
be replaced.

9. Unscrew the hex head cap

screws (11) and remove the
volute (14).

10.On the three phase models first

remove the impeller screw (16)
and impeller washer (17) and
then on all models unscrew the
impeller (15). Hold the
rotor/shaft assembly with a
screwdriver and carefully tap
impeller with a plastic or rubber
hammer.

11.Remove the flat head machine

screw (23) from seal plate (24).
Remove clamp ring (13) and
motor cover assembly (10, 25)
off the seal plate (24).

12.Remove the four hex head 

stator bolts and lift the 
stator (7) from the seal plate
(24). A

screwdriver can 

be inserted under the stator
shell in order to remove the
stator (7).

13. Bump the end of the shaft with

a plastic hammer. This will
push the rotating half of the
mechanical seal (18) from the
shaft and also push the lower
bearing from the seal plate
(24). Now remove the shaft,
rotor and bearing assembly
from the seal plate (24).

14. If water is found in the oil, the

rotating and stationary halves
of the mechanical seal (18,19)
must be replaced. Remove the
stationary seal half by inserting
a screwdriver into seal plate
(24) from the top and tapping
lightly with a hammer.

15. Turn the bearing by hand and

if it feels rough when turned or
looks rusted, it should be
replaced. Obtain a bearing
puller to remove the bearing. If
a puller cannot be placed over
the bearing, remove the outer
face by cracking in a vise. Now
the outer face and balls can be
removed, allowing the inner
face to be pulled.

Содержание SK75

Страница 1: ...age Ejector Pumps SK75 100 NOTE To the installer Please make sure you provide this manual to the owner of the pumping equipment or to the responsible party who maintains the system Pump Installation and Service Manual ...

Страница 2: ...ed above cautions could result in injury or death General Information Pump Warning NOTE Some city regulations do not allow installing a pump with plastic pipe Check local regulations 5 In applications where the pump may sit idle for months at a time it is recommended that the pump s be cycled every month to ensure the pumping system is working properly 6 A Hydromatic check valve should be installe...

Страница 3: ...3 Pump Installation Simplex SK75 Duplex SK100 40 0 10 20 30 0 32 64 96 128 160 192 TOTAL DYNAMIC HEAD FEET CAPACITY U S G P M 3 4 HP 1 HP ...

Страница 4: ...se when you re looking at the impeller Correct improper rotation on three phase pumps by reversing any two line leads No rotation check is necesary on single phase pumps 8 Closed discharge gate valve 9 Plugged impeller or pipeline 10 Discharge head may be too high Check elevation against design point of pump 11 Floats not hanging free in the sump 12 Malfunctioning floats WARNING Be certain power t...

Страница 5: ...s for 230 volt motors touch one probe to the white lead and the other probe to the stator laminations for only one second Buzzing will indicate arcing is occurring at a breakdown of insulation or a small amount of moisture is present The stator will then have to be dried out or replaced The high pot test is very destructive So each time the same stator is checked the voltage should be lowered abou...

Страница 6: ...ler 15 on the pump shaft On the three phase models fasten the impeller washer 17 with the impeller screw 16 to the pump shaft 10 Turn impeller 15 It should turn freely with no drag 11 Set the seal housing and motor housing assembly into the volute case 14 and secure with three hex head screws 11 12 Reach in the eye of the volute 14 and turn impeller 15 again It should turn freely with no drag 13 I...

Страница 7: ...0 1 Motor 1 HP 200 3 60 1 10838 700 1 Motor 1 HP 575 3 60 1 8 19100A012 Cap Screw 4 9 77 003 1 O Ring 1 10 12709 000 2 Adaptor Ring 1 11 101 010 1 Cap Screw 3 12 77 003 1 O Ring 1 13 5677 000 3 Clamp Ring 1 14 6818 002 2 Volute 1 15 7187 101 2 Impeller SK100 1 7187 102 2 Impeller SK75 1 16 984 001 1 Machine Screw 3Ø only 1 17 7532 003 1 Roll Pin 3Ø only 1 19 14525A010 Shaft Seal 1 20 324 001 1 Gas...

Страница 8: ...disposition Any transportation charges involved in such disposition shall be for the Buyer s account The Buyer s exclusive and sole remedy on account or in respect of the furnishing of material that does not conform to this contract or to this written warranty shall be to secure replacement thereof as aforesaid Hydromatic shall not in any event be liable for the cost of any labor expended on any s...

Отзывы: