HAZARDOUS LOCATION
SUBMERSIBLE PUMP

Model S4NX 

(Class I, Division 1, Groups C & D): FM

10/10

Item # E-03-332

Part # 5625-332-1

© 2010 Pentair Pump Group, Inc. 

 

Installation and Service Manual

NOTE! To the installer: Please make sure
you  provide  this  manual  to  the  owner  of
the equip ment or to the responsible party
who maintains the system.

For use with product
built with Regal Beloit/
Marathon motor.

Содержание S4NX

Страница 1: ... E 03 332 Part 5625 332 1 2010 Pentair Pump Group Inc Installation and Service Manual NOTE To the installer Please make sure you provide this manual to the owner of the equipment or to the responsible party who maintains the system For use with product built with Regal Beloit Marathon motor ...

Страница 2: ... longer and prior to electrical start up Seal Failure Probes All hazardous location submersible pumps have two factory installed moisture detectors seal failure probes They are in a normally open series circuit in the seal chamber Under normal operating conditions the circuit remains open If the lower seal leaks and moisture enters this chamber the moisture would settle to the bottom of the chambe...

Страница 3: ...s recommended Hydromatic warranty is void See Pages 5 6 Heat Sensor and Seal Failure Connections If a Hydromatic control panel is used terminal blocks are provided for heat sensor and seal failure connections See Panel Schematic If a control panel is supplied by others it must allow heat sensor and seal failure terminations Starting System 1 Double check all wire connections 2 Turn pumps to Off po...

Страница 4: ... on a pump the following instructions should be followed carefully Disconnecting Pump Cords If a Hydromatic hazardous location pump is to be removed from its location one of two ways may be used to disconnect the pump cords from the rest of the system Pump cords may be disconnected at control panel on sump mounted control panels and cord assembly taken with pump CAUtioN if cord openings from sump ...

Страница 5: ...NNECTIONS O L O L L2 FUSES GREEN RED BLACK WHITE PUMP MOTOR F E RED 330K D C GREEN HEAT SENSORS 120 VAC 5A SEAL PROBES 300 VAC 20 MA POWER CORD CONTROL CORD SEE TYPICAL CONTROL CIRCUITRY BELOW CRS RUN CAPACITOR CRS START CAPACITOR CAPACITOR PACK PANEL M RUN LIGHT SEAL FAILURE INDICATOR D C TO SEAL PROBES IN PUMP MOTOR SEAL FAILURE RELAY LEVEL CONTROL CIRCUITRY H O A H A R OVERLOADS CAPACITORS AND ...

Страница 6: ... PUMP MOTOR RED 330K D C GREEN HEAT SENSORS 120 VAC 5A SEAL PROBES 300 VAC 20 MA POWER CORD CONTROL CORD SEE TYPICAL CONTROL CIRCUITRY BELOW CRS RUN CAPACITOR CRS START CAPACITOR CAPACITOR PACK PANEL M RUN LIGHT SEAL FAILURE INDICATOR R F E PUSH TO RESET R TO HEAT SENSOR IN PUMP MOTOR D C PUSH TO TEST SEAL PROBE CONTINUITY TEST LIGHT TO SEAL PROBES IN PUMP MOTOR SEAL FAILURE RELAY LEVEL CONTROL CI...

Страница 7: ...p Maintenance 7 After ring is removed turn housing upright and bump on hardwood block This should jar the stator loose and allow it to drop out 8 Thoroughly clean housing before replacing new stator Replace stator and make all wire connections to connection box before replacing housing on pump See motor lead connection drawing This is important as leads must be tucked behind the windings by using ...

Страница 8: ...e shaft by tapping the end of the impeller blades 4 To remove seal plate take out socket head screws and using screws in back off holes pry plate loose This will also force seal off if not already removed 5 Remove snap ring Pull seal if it is free If not free it can be forced off when shaft is removed 6 Set seal housing in upright position and bump end of shaft on hardwood block This will push the...

Страница 9: ...PROBE TEST RESISTOR ON HAZARDOUS LOCATION ONLY PROBE TEST RESISTOR ON HAZARDOUS LOCATION ONLY PROBE TEST RESISTOR ON HAZARDOUS LOCATION ONLY PROBE TEST RESISTOR ON HAZARDOUS LOCATION ONLY Wiring Diagrams ...

Страница 10: ...ator 3 HP 230 1 60 1750 1 14698 203 1 Stator 3 HP 200 1 60 1750 1 24407C202 Stator 3 HP 230 460 3 60 1750 1 24407C201 Stator 3 HP 200 3 60 1750 1 24407C203 Stator 3 HP 575 3 60 1750 1 24407C204 Stator 5 HP 230 1 60 1750 1 24407C206 Stator 5 HP 230 460 3 60 1750 1 24407C205 Stator 5 HP 200 3 60 1750 1 24407C207 Stator 5 HP 575 3 60 1750 1 Ref Part Part No No Description Qty 24407C209 Stator7 1 2HP2...

Страница 11: ...34 48 25 47 39 45 41 40 46 1 2 3 4 5 6 7 8 9 10 12 11 13 14 16 17 18 19 20 21 22 23 43 44 S4NX CONNECTION DIAGRAM FOR LEADS IN MOTOR AND CONNECTION BOX 230 VOLTS 460 VOLTS GREEN GREEN L3 L2 L1 L3 L2 L1 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 Figure 1 ...

Страница 12: ..._____________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ __________...

Страница 13: ..._____________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ __________...

Страница 14: ...rdance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal maintenance services and parts used in connection with such service d to units which are not installed in accordance with applicable local codes ordinances and good trade practices e if the unit is moved from its original installation location f if unit is used for purposes other tha...

Страница 15: ......

Страница 16: ...oltage _________________________________Actual ___________________________________ Voltage to Pumps _____________________________________Actual ___________________________________ Type of Junction Box __________________________________Manufacturer of Junction Box ______________ Are Floats Installed in Wet Well T Yes T No Are Floats Set to Engineer s Specs T Yes T No Are Floats Wired for Proper Seq...