Hydrolevel Company Fuel Smart HydroStat 3200 Скачать руководство пользователя страница 5

5

 

TEMP 

ACTIVE

Indicates that the

Fuel Smart HydroStat control is

powered and that the temperature

function is active.

 

TEMP 

HIGH TEMP

Illuminates

when the boiler water temperature

reaches the high limit setting. It will

remain lit until the water temperature

falls 10° (see High Limit Differential on page 4). The Fuel

Smart HydroStat prevents burner operation while this 

LED is on. 

 

LWCO 

ACTIVE

Indicates that the low water cut-off

(LWCO) function of the Fuel Smart HydroStat is active. When

the control is installed with a Hydrolevel Electro-Well, this

LED will be on at all times when the control is powered.

IMPORTANT: 

If the control is installed with a well other than

the Electro-Well, this LED will not illuminate indicating that

the control is not providing low water cut-off functionality.

 

LWCO 

LOW WATER

Illuminates if the boiler is in a

low water condition. The Fuel Smart HydroStat will prevent

burner operation during this condition. 

IMPORTANT: 

The

system must be checked by a qualified heating professional

prior to resuming operation. 

WARNING: DO NOT ADD WATER UNTIL THE BOILER

HAS FULLY COOLED.

 

ECONOMY 

ACTIVE

Indicates that the Thermal

Targeting function is active and the Fuel Smart HydroStat will

reduce boiler temperature to conserve fuel. The Economy

feature is activated using the ECONOMY dial. (See “How

Thermal Targeting Works” on page 4 for more information).  

 

ECONOMY 

TARGET

When the Economy feature is

active, the Fuel Smart HydroStat continually sets target

temperatures below the high limit setting to maximize fuel

efficiency. When the boiler water reaches the target

temperature, the LED illuminates and

the burner will shut down. The boiler

water will continue to circulate and

heat the house as long as the

thermostat call continues. The 

LED will stay lit until the boiler

temperature drops to the differential

set point (see Target Temp Differential

on page 4) at which point the boiler

will be allowed to fire again. 

NOTE: 

This LED illuminates

regularly during normal boiler operation.

 

TEST/SETTINGS

Button

To Test Low Water Cut-Off:

Press and hold the Test/

Settings button for 5 seconds. The display will read LCO. 

LWCO TEST    

00

The red Low Water light should illuminate and the burner

circuit (B1 and B2) should de-energize. 

NOTE: 

The control

must be installed with a Hydrolevel Electro-Well for low water

cut-off functionality (see page 2 for more details).

To View Current Settings: 

Press and release the

Test/Settings Button in short intervals to sequentially display

the following settings:

HIGH LIMIT SETTING

00

LOW LIMIT SETTING

00

ECONOMY SETTING

000

CURRENT TARGET TEMPERATURE

PRE-PURGE SETTING

000

The display will return to boiler temperature (default) if

Test/Settings Button in not pressed for 5 seconds.

LED LEGEND and TEST/SETTINGS BUTTON

Содержание Fuel Smart HydroStat 3200

Страница 1: ...l boilers Low Water Cut Off Provides protection against potentially dangerous low water conditions when installed with the Hydrolevel Electro Well see page 2 for details Boiler Reset Control Utilizes...

Страница 2: ...osen Fig 3 IMPORTANT Make sure that the immersion well or Electro Well is installed in the boiler manufacturer s designated temperature limit control tapping N NO OT TE E If installing an Electro Well...

Страница 3: ...he vent damper plug is disconnected ZONE VALVE WIRING IMPORTANT Use a separate transformer to power zone valves Connecting zone valves to Z TV may overload the HydroStat and cause a lock out condition...

Страница 4: ...P Differentials are automatic and will vary based on control settings and boiler temperature Thermal Targeting technology analyzes thermostat activity and continually evaluate how much heat the house...

Страница 5: ...ed using the ECONOMY dial See How Thermal Targeting Works on page 4 for more information ECONOMY TARGET When the Economy feature is active the Fuel Smart HydroStat continually sets target temperatures...

Страница 6: ...anticipator settings common on non digital thermostats 3 Check the Economy setting The Economy feature much like outdoor reset controls lowers average boiler temperature and can slow or in some cases...

Страница 7: ...rol is Operating Properly Replace Control The burner will not fire until the boiler water has dropped to the high limit differential set point 10 below high limit setting Check that the high temperatu...

Страница 8: ...ck wiring Make sure that burner is wired to B1 Burner should never fire when red or yellow LED is lit Is either Yellow LED On The Control has Reached Target or High Limit Temperature The Control is Op...