WIRING

STEP 1  

Connect 120 VAC Hot to

terminal 

L1.

Connect 120 VAC Neutral

to terminal 

L2.

Disconnect means and

overload protection as required (pro-

vided by others).

STEP 3  

Connect the circulator 

to 

C1-C2. 

(C2 is neutral.)

STEP 2  

Connect the burner 

circuit to 

B1-B2. 

(B2 is neutral.)

WARNING

Electrical shock hazard.

To prevent electrical shock, death or equipment damage, disconnect power supply before 

installing or servicing this control.

3

STEP 4  

Connect the thermostat

to 

T-TV.

STEP 5  

If the boiler is equipped

with a plug-in style vent damper, unplug

the factory installed jumper from the

receptacle on the circuit board and

replace it with the vent damper plug.

NOTE: 

Once a vent damper plug is

connected to the HydroStat, the control

is permanently altered and will no

longer function when the vent damper

plug is disconnected. 

ZONE VALVE WIRING

IMPORTANT: 

Use  a  separate  transformer  to

power  zone  valves.  Connecting  zone  valves  to 

Z-TV  may  overload  the  HydroStat  and  cause  a

lock-out condition (see 

Troubleshooting on page 6

for more information). The total load, including the

burner circuit, vent damper, and Z-TV connections

must not exceed 1.2 amps (30 VA). Connect zone

valve end-switch to T-TV as shown below.

STEP 6  For Systems with Indirect Water Heaters

When installing with an indirect water heater, the signal from the indirect must be

separated from the heating zone signals and wired to 

I1

and 

I2

as shown above.

Calls to I1 and I2 will bypass the Thermal Targeting feature and allow the boiler to

fire to the high limit setting to heat the indirect tank. 

NOTE:

If you choose not to separate the indirect signal from the heating zones,

the Economy Feature should the turned OFF to insure that the boiler supplies ade-

quate temperature to heat the indirect tank (see page 4).

Содержание Fuel Smart HydroStat 3200

Страница 1: ...l boilers Low Water Cut Off Provides protection against potentially dangerous low water conditions when installed with the Hydrolevel Electro Well see page 2 for details Boiler Reset Control Utilizes...

Страница 2: ...osen Fig 3 IMPORTANT Make sure that the immersion well or Electro Well is installed in the boiler manufacturer s designated temperature limit control tapping N NO OT TE E If installing an Electro Well...

Страница 3: ...he vent damper plug is disconnected ZONE VALVE WIRING IMPORTANT Use a separate transformer to power zone valves Connecting zone valves to Z TV may overload the HydroStat and cause a lock out condition...

Страница 4: ...P Differentials are automatic and will vary based on control settings and boiler temperature Thermal Targeting technology analyzes thermostat activity and continually evaluate how much heat the house...

Страница 5: ...ed using the ECONOMY dial See How Thermal Targeting Works on page 4 for more information ECONOMY TARGET When the Economy feature is active the Fuel Smart HydroStat continually sets target temperatures...

Страница 6: ...anticipator settings common on non digital thermostats 3 Check the Economy setting The Economy feature much like outdoor reset controls lowers average boiler temperature and can slow or in some cases...

Страница 7: ...rol is Operating Properly Replace Control The burner will not fire until the boiler water has dropped to the high limit differential set point 10 below high limit setting Check that the high temperatu...

Страница 8: ...ck wiring Make sure that burner is wired to B1 Burner should never fire when red or yellow LED is lit Is either Yellow LED On The Control has Reached Target or High Limit Temperature The Control is Op...

Страница 9: ...riod of two years from the date of manufacture or one year from the date of installation whichever occurs first In the event of any claim under this warranty or otherwise with respect to our products...

Отзывы: