MODEL 3200

Temp Limit / LWCO Control

with Thermal Targeting

for Water Boilers

120 VAC Input / 24 VAC Burner Circuit

PATENT PENDING

WARNING

Electrical shock hazard.

To prevent electrical shock, death or

equipment damage, disconnect power supply before

installing or servicing control. Only qualified personnel may install or service this control in
accordance with local codes and ordinances. Read instructions completely before proceeding.

CAUTION

To prevent serious

burns, boiler

should be thoroughly cooled before installing or
servicing control.

Three Function
Design

Temperature Limit Control

Designed for cold start and tankless

coil boilers.

Low Water Cut-Off

Provides protection against potentially

dangerous low water conditions

when installed with the Hydrolevel

Electro-Well™ (see page 2 for details).

Boiler Reset Control

Utilizes

Thermal Targeting™

technology to conserve fuel by

monitoring heating demand and

establishing target boiler temperatures

below the high limit setting (see page 4

for details).

INSTALLATION INSTRUCTIONS
and OPERATING MANUAL

• Saves Fuel –

Features Thermal Targeting™ technology and

Thermal Pre-Purge capability

• Universal Design –

Replaces common cold-start and triple-action

Aquastats*

• Easy to Install –

Industry standard wiring, dial-type settings,

no external sensors

• Operating Indicators –

LEDs, Dynamic Display and Test Button provide

continual and on-demand status checks

• Prioritizes Hot Water –

Gives priority to low limit setting or to calls from

indirect water heater

*Aquastat is a registered trademark of Honeywell International, Inc.

Содержание Fuel Smart HydroStat 3200

Страница 1: ...l boilers Low Water Cut Off Provides protection against potentially dangerous low water conditions when installed with the Hydrolevel Electro Well see page 2 for details Boiler Reset Control Utilizes...

Страница 2: ...osen Fig 3 IMPORTANT Make sure that the immersion well or Electro Well is installed in the boiler manufacturer s designated temperature limit control tapping N NO OT TE E If installing an Electro Well...

Страница 3: ...he vent damper plug is disconnected ZONE VALVE WIRING IMPORTANT Use a separate transformer to power zone valves Connecting zone valves to Z TV may overload the HydroStat and cause a lock out condition...

Страница 4: ...P Differentials are automatic and will vary based on control settings and boiler temperature Thermal Targeting technology analyzes thermostat activity and continually evaluate how much heat the house...

Страница 5: ...ed using the ECONOMY dial See How Thermal Targeting Works on page 4 for more information ECONOMY TARGET When the Economy feature is active the Fuel Smart HydroStat continually sets target temperatures...

Страница 6: ...anticipator settings common on non digital thermostats 3 Check the Economy setting The Economy feature much like outdoor reset controls lowers average boiler temperature and can slow or in some cases...

Страница 7: ...rol is Operating Properly Replace Control The burner will not fire until the boiler water has dropped to the high limit differential set point 10 below high limit setting Check that the high temperatu...

Страница 8: ...ck wiring Make sure that burner is wired to B1 Burner should never fire when red or yellow LED is lit Is either Yellow LED On The Control has Reached Target or High Limit Temperature The Control is Op...

Страница 9: ...riod of two years from the date of manufacture or one year from the date of installation whichever occurs first In the event of any claim under this warranty or otherwise with respect to our products...

Отзывы: