Hydrolevel Company FUEL SMART HydroStat 3200-Plus Скачать руководство пользователя страница 8

8

High Limit Differential

When the Economy feature is on, the control’s Thermal Targeting feature actively sets varying differentials based on system
conditions. This option allows for selecting a 10, 20 or 30 degree fixed differential when the Economy feature is turned OFF.
These optional differential settings are subtractive from the HIGH LIMIT setting. 

Note: 

If the Economy feature is on, this setting

will be overridden by the control's Thermal Targeting function.

To change the high limit differential

1. Turn the LO TEMP dial to access the Program Mode –indicated in the display as 

Pro

2. Turn the HI TEMP dial to select feature 

9

3. Push the Test/Settings Button to select a high limit differential of 

10

20

, or 

30

4. Reset LO TEMP and HI TEMP settings to desired temperatures (see page 4)

Restore Factory Default Settings

To restore all features to the factory default settings

(see following chart for default settings)

1. Turn the LO TEMP dial to access the Program Mode – indicated in the display as

Pro

2. Turn the HI TEMP dial to select feature 

dEf

 

3. Push the Test/Settings Button to

Y

to reset all features to the default settings.

4. Reset LO TEMP and HI TEMP settings to desired temperatures (see page 4)

OPTIONAL FEATURES continued

NOTE: If the HydroStat is factory-equipped on a boiler, some options may be set differently from the default settings.

SEE PAGE 4 FOR ADDITIONAL SETTINGS

Dial 

Setting

Feature

Options

Description

Default 
Setting

1

Thermal Pre-Purge

OFF

on

Purge Inactive

Purge Active

OFF

2

Fahrenheit or Celsius

F

c

Degrees Fahrenheit

Degrees Celsius

F

3

LWCO Manual or

Automatic Reset

A

b

Automatic Reset

Manual Reset

A

4

Circulator Options

A

b

c

Circulator operation on TT call only
Circulator operation on ZC/ZR call only
Circulator operation on call from either

A

5

Circulator Hold Off

on

OFF

Circulator Hold Off – Active

Circulator Hold Off – Inactive

on

6

Not available 

on this control

7

Not available 

on this control

8

Well Type

A

b

Hydrolevel Electro-Well

Standard Immersion Well

A

9

High Limit 

Differential

10

20

30

10° Differential
20° Differential
30° Differential

10

dEF

Restore Factory

Defaults

Y

n

Restore Defaults

Do Not Restore Defaults

n

Содержание FUEL SMART HydroStat 3200-Plus

Страница 1: ...Hydrolevel OS 100 Outdoor Sensor Kit sold separately for out door reset and warm weather shut down functionality INSTALLATION INSTRUCTIONS and OPERATING MANUAL Saves Fuel Features Thermal Targeting te...

Страница 2: ...circuit to B1 B2 B2 is common STEP 4 Connect the thermostat to T TV STEP 5 If the boiler is equipped with a plug in style vent damper unplug the factory installed jumper from the recepta cle on the ci...

Страница 3: ...s must not exceed 1 2 amps 30 VA Connect zone valve end switch to T TV as shown below STEP 6 For Systems with Indirect Water Heaters When installing with an indirect water heater the signal from the i...

Страница 4: ...zone house turn the dial to 2 or 1 Conversely if the boiler provides adequate heat added fuel savings can be achieved by selecting a higher setting example 4 or 5 If the heating and indirect water hea...

Страница 5: ...time to satisfy the heat load NOTE Smart DHW Priority During a call from an indirect water heater the control will de energize the circulator contacts C1 C2 to heat only the indirect tank ensuring an...

Страница 6: ...Turn the HI TEMP dial to select feature 2 3 Push the Test Settings Button to c for Celsius or F for Fahrenheit 4 Reset LO TEMP and HI TEMP settings to desired temperatures see page 4 Manual Reset Low...

Страница 7: ...desired temperatures see page 4 Setting the Well Type Electro Well vs Standard Immersion Well When used to replace older temperature only controls the HydroStat can be installed on the existing well...

Страница 8: ...n the display as Pro 2 Turn the HI TEMP dial to select feature dEf 3 Push the Test Settings Button toY to reset all features to the default settings 4 Reset LO TEMP and HI TEMP settings to desired tem...

Страница 9: ...e the LED illuminates and the burner will shut down The boiler water will continue to circulate and heat the house as long as the thermostat call continues The LED will stay lit until the boiler tempe...

Страница 10: ...with the inside of the well tube Check that the well does not have excessive build up of heat transfer grease that may interfere with the clip contacting the well 2 Remove well and examine for excessi...

Страница 11: ...erve fuel see How Thermal Targeting Works on page 5 The burner will not fire until the boiler temperature drops to the automatically calculated Target Temp Differential YES NO Is the Green LED TEMP AC...

Страница 12: ...should never fire when red or yellow LED is lit Is either Yellow LED On The Control has Reached Target or High Limit Temperature The Control is Operating Normally The Control is Operating Normally Th...